background image

OSXAB208-EN 

6/7 

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CONTROL 

CONTROL OF SWITCHING   

When using control switch with current leakage   
(more than 0.1 mA) such as TRIAC or relay with CR,     
it can cause malfunction.

DC POWER SUPPLY 

• Cannot use a half or full-wave power supply.   
• Consider an inrush current of motor.   

(It is 1.5 to 3 times of consumed current.)   

• When using a DC voltage, be selected the wire 

thickness by the wiring distance.   

• Do not use power supply that require more than   

1 second with rise and fall time.   

USE OF OPEN/SHUT SIGNALS 

Use signals within the capacity of output signal rating. 

OPERATION 

ABR-Q and HBR-Q (Power failure: OPEN) 

Battery connector is not connected before shipment. 
Please connect before use.   

TESTING 

• Before operation, charge of 24 hours or more is 

performed.   

• Make sure that power supply voltage is correct. Also 

check operating position, wiring, speed and signals.   

• During trial operation, check that valve movement and 

OPEN and SHUT signals are correct.   

DUTY CYCLE 

Confirm that the operation frequency is within the 
specified duty cycle.   
Use beyond the load time rate range will affect 
product life. Also, it may cause burnout.   

Duty cycle is a value that regulates the opening / 
closing frequency of the actuator. The meaning of 
20 % 15 minutes for Duty cycle is that 3 minutes 
(20 % of 15 minutes) operation is possible.   
The calculated value obtained by dividing 3 minutes 
by the operation time is the number of times of 
operation within 15 minutes.   

ATTENTION 

• Be sure to set the DIP-SW before turning on the 

power supply.   

• Keep power supplied for built-in space heater to 

prevent condensation inside actuator.   

• Do not touch the moving parts of actuator in 

operation.   

• Do not insert a reverse signal during operation.   

It may shorten the life of product.   

• Never put anything on the actuator or make it into a 

foothold.   

BATTERY 

HANDLING 

• The battery can be expected a service life over 8 to 9 

years at 25 °C.   

• Built-in battery should be keep reliability of operation, 

we recommend you to exchange every 5 years.   

AFTERCARE 

• Battery exchange can use during the power 

supplying.   

• Please follow the attachment exchange manual or 

procedure with battery.   

• Dispose of used batteries in the correct way. Order 

industrial waste disposers, or send them back to us.   

BATTERY REPLACEMENT 

Remove the battery cover.   

Remove the battery connector.   

Hold the connector body and pull it straight forward. 
Do not pull electric wire by any means.

Remove the bracket fix screw and battery.   

New battery is attached with a bracket fix screw. 

Insert the battery connector. 

  Please be sure to plug it straight in all the way.   

Attach the battery cover.   

Make sure that operation by battery is securely 
performed. 

Battery

Battery cover

Battery connector

Bracket fix screw

Motor cover

Содержание ABR-300 Series

Страница 1: ...is 8 to 9 years at 25 C It s possible to use for a wide range of temperature ambient temperature 20 to 50 C The battery composed by dry type structure the maintenance of saving water is not necessary...

Страница 2: ...N HOLD Battery out Hold the current valve position Battery Compact seal lead acid battery 12 V 2 5 Ah It is recommend to exchange a battery for every 5 years at 25 C Charge system Constant voltage cha...

Страница 3: ...A SHUT OPEN SHUT Factory setting Option Q Mode B OPEN SHUT OPEN Setting is required Standby mode Mode A FINISH mode SHUT OPEN HOLD SHUT HOLD mode HOLD Mode B FINISH mode OPEN SHUT OPEN HOLD mode HOLD...

Страница 4: ...ttery bracket 21 Battery 4 Motor cover 10 Transformer 16 Bracket fix screw 22 Rubber packing 5 Motor 11 Drive shaft 17 Battery connector 23 Earth screw M3 6 Control board 12 Manual clutch 18 Relay boa...

Страница 5: ...spection and replacement work Maintenance space more than 70 mm upward from the actuator is required Be sure to enough space around the actuator for battery replacement CAUTION AFTER PIPING Until the...

Страница 6: ...cycle is that 3 minutes 20 of 15 minutes operation is possible The calculated value obtained by dividing 3 minutes by the operation time is the number of times of operation within 15 minutes ATTENTION...

Страница 7: ...Confirm existence of abnormal noise and vibration during operation Confirm whether screws are loose or not Confirm that water or condensation no remains in the actuator Turn off the power and check if...

Отзывы: