INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HANDLING & STORAGE
HANDLING
Proper care in handling the actuator should be taken
to prevent damage. Do not drop or throw it.
STORAGE
• Store the actuator in the protected area from dust,
moisture, and direct sunlight. If possible, should be
kept in the original packaging.
• If it is not used more than 30 days, remove a battery
from actuator and keep it in a place with little humidity.
CHECKING
• Check the product code, power supply, and voltage
before installation.
• Make sure that the bolts are not loose.
• DIP switch be sure perform set up before a power
supply injection.
Should not change an unnecessary switch.
BATTERY CONNECTOR (Power failure: OPEN)
• For the following models, Battery connector is not
connected before shipment.
Please connect before use.
ABR (Option: Q)
HBR (Option: Q)
• It may move unexpectedly by connecting the battery
connector. Please be careful.
INSTALLATION
ENVIRONMENT
• Do not install in place where corrosive gas is present
or where vibration is heavy (0.5 G or more).
• When radiant heat causes the surface temperature of
the control unit to exceed 50°C, provide an
appropriate shielding plate.
• If there is a possibility that the fluid and drive part
freeze, please take measures to prevent freezing.
POSITIONING
• Should be positioned through 90° upward from
horizontal. Provide space around the product to allow
manual operation, inspection and replacement work.
• Maintenance space more than 70 mm upward from
the actuator is required.
• Be sure to enough space around the actuator for
battery replacement.
CAUTION AFTER PIPING
Until the wiring is completed there must be no
condensation or flooding in the interior of the actuator,
after piping. Protective caps on the cable gland are
not waterproof.
WIRING
PRECAUTIONS
• Remove the actuator cover before wiring.
• Two G1/2 electrical connections are provided with a
cable gland and plug. Usable cable size is 6 to 12
mm.
• When using a flexible tube, dew condensation may
occur inside the actuator due to respiration from the
inside of the tube and malfunction may result. Seal the
flexible tube connector part with a sealant.
• Sealants that affect the electrical contacts should not
be used inside the electric actuator.
• If long distance wiring or low voltage operation, check
that terminal voltage is in the proper range.
• Do not remove the body cover lower screw.
CONNECTION
• Do not wiring outdoors on a rainy day.
• Check the power supply and voltage.
Connect the signal as shown in the wiring diagram.
Do not connect unnecessarily terminal.
• Actuator should be electrically grounded.
Use the terminal marked ( ) inside the actuator.
PREVENT DEW CONDENSATION
• When installing the cover after wiring, perform the bolt
by the temporary tightening procedure and the
permanent tightening procedure to tightly and
securely tighten the rubber packing so that water does
not enter from the outside.
• Tighten the cable gland nut so that there is no leakage
from the wire entrance.
Battery
cover
Warning
message