OSXAB208-EN
2/7
ELECTRIC ACTUATOR SPECIFICATIONS
3 way valve: SHUT / Position , OPEN / Position
Actuator type
( : Voltage code)
ABR-300- ABR-700- HBR-300- HBR-700- HBR-02K-
HBR-06K-
Voltage
100 / 110 V AC ±10 % 50/60 Hz (Code: 1)
200 / 220 V AC ±10 % 50/60 Hz (Code: 2)
24 V DC
(Code: 0)
Note) Cannot use a half or
full-wave DC power.
Rated torque
[N m] 30
70
30
70
200
600
Operation time
[s] 3 to 4
6 to 10
1 to 2
3 to 5
AC: 8 to 15
DC: 12 to 17
AC: 24 to 45
DC: 36 to 50
Power consumption
(Max)
[VA]
AC power 100
DC power 80
AC power 150
DC power 120
Motor
DC motor
Overload protection
Current limiter
Control switch
a-contact input type, with built-in relay
Operation *¹
[Mode A] SW is OFF SHUT. SW is ON OPEN. (Standard)
[Mode B] SW is ON SHUT. SW is OFF OPEN. (Option: Q)
Power failure *²
[Response mode] (Standard)
Mode A : SHUT.
Mode B : OPEN.
[Standby mode]
After power failure, waiting for an external signal input to the switch in
a fixed period.
Waiting time of power failure: more than 50 hours
(It becomes short due to the influence of use environment.)
Shift the valve to OPEN / SHUT (or HOLD) by battery out.
Stop waiting for the external input signal.
[FINISH] Battery out [Mode A] SHUT
[Mode B] OPEN
[HOLD] Battery out Hold the current valve position.
Battery
Compact seal lead acid battery: 12 V, 2.5 Ah
* It is recommend to exchange a battery for every 5 years (at 25 °C).
Charge system
Constant voltage charge current
Input signal current
2.5 mA 12 V DC (O-terminal) Leakage current in SW: less than 0.5 mA
Output signal rating
Resistance load : 0.5 A 120 V AC / 0.6 A 120 V AC
Micro load
: 1 mA
5 V DC
Alarm signal
Overtorque : It returns by power supply OFF or reverse operating signal.
Battery out : The contacts turn on as battery consumption progresses.
Duty cycle
20 % 15 min.
Ambient temperature
-20 to 50 °C
Space heater
Built in to the control board
Manual operation
Manual over-ride with clutch. (Direct operation / 06K: Operation by manual shaft.)
Enclosure
Equivalent to IP65 (IEC 60529)
Housing material
AC4C Aluminum alloy castings (acrylic resin baking finish)
Terminal block
For bare wire 0.2 to 2.5 mm² (AWG 24 to 12) , Ground terminal: M3
Conduct port
2-G1/2 Attachments: Cable gland (for 6 to 12 mm cable), plug.
*¹ Change by DIP switch. (Standard Mode B)
*² Change by DIP switch. (Standard Standby mode)
OPERATION MODE / POWER FAILURE
Power failure
Factory settings
Response mode [Mode A] SHUT.
Standard (Nil)
[Mode B] OPEN.
Option: Q
Standby mode
HOLD
Battery out [FINISH] [Mode A] SHUT.
Setting is required
[Mode B] OPEN.
Battery out [HOLD] Hold the current valve position.