ELECTRIC ACTUATOR SPECIFICATIONS 

3 way valve: SHUT / Position , OPEN / Position

Actuator type   
( : Voltage code) 

ABR-300-   ABR-700-   HBR-300-   HBR-700-   HBR-02K-  

HBR-06K-

Voltage   

100 / 110 V AC ±10 %  50/60 Hz  (Code: 1) 
200 / 220 V AC ±10 %  50/60 Hz  (Code: 2) 
24 V DC 

 

(Code: 0) 

Note) Cannot use a half or 

full-wave DC power.

Rated torque 

[N m]  30 

70 

30 

70 

200 

600 

Operation time 

[s]  3 to 4 

6 to 10 

1 to 2 

3 to 5 

AC:  8 to 15 

DC: 12 to 17 

AC: 24 to 45 

DC: 36 to 50 

Power consumption 
(Max) 

[VA] 

AC power  100   
DC power  80   

AC power  150   
DC power  120   

Motor 

DC motor 

Overload protection 

Current limiter 

Control switch 

a-contact input type, with built-in relay 

Operation *¹ 

[Mode A]    SW is OFF      SHUT.    SW is ON      OPEN.    (Standard) 
[Mode B]    SW is ON      SHUT.    SW is OFF      OPEN.    (Option: Q) 

Power failure *² 

[Response mode] (Standard) 

Mode A : SHUT.
Mode B : OPEN.

[Standby mode] 

After power failure, waiting for an external signal input to the switch in 
a fixed period.   
Waiting time of power failure: more than 50 hours   
(It becomes short due to the influence of use environment.) 
Shift the valve to OPEN / SHUT (or HOLD) by battery out.   
Stop waiting for the external input signal. 

[FINISH]  Battery out      [Mode A] SHUT 
 

 

 

[Mode B] OPEN 

[HOLD]  Battery out      Hold the current valve position. 

Battery 

Compact seal lead acid battery: 12 V, 2.5 Ah 
* It is recommend to exchange a battery for every 5 years (at 25 °C). 

Charge system 

Constant voltage charge current 

Input signal current 

2.5 mA 12 V DC (O-terminal)    Leakage current in SW: less than 0.5 mA 

Output signal rating 

Resistance load : 0.5 A  120 V AC  / 0.6 A  120 V AC 
Micro load 

: 1 mA 

5 V DC 

Alarm signal 

Overtorque : It returns by power supply OFF or reverse operating signal. 
Battery out  : The contacts turn on as battery consumption progresses. 

Duty cycle 

20 % 15 min.   

Ambient temperature 

-20 to 50 °C 

Space heater 

Built in to the control board   

Manual operation 

Manual over-ride with clutch. (Direct operation / 06K: Operation by manual shaft.) 

Enclosure 

Equivalent to IP65 (IEC 60529)   

Housing material 

AC4C Aluminum alloy castings (acrylic resin baking finish) 

Terminal block 

For bare wire 0.2 to 2.5 mm² (AWG 24 to 12) , Ground terminal: M3 

Conduct port 

2-G1/2 Attachments: Cable gland (for  6 to 12 mm cable), plug. 

*¹  Change by DIP switch.  (Standard      Mode B) 
*²  Change by DIP switch.  (Standard      Standby mode) 

OPERATION MODE / POWER FAILURE 

 

Power failure 

 

 

Factory settings 

Response mode [Mode A] SHUT.   

 

Standard (Nil) 

 

[Mode B] OPEN.   

 

Option: Q 

Standby mode 

HOLD 

Battery out    [FINISH] [Mode A] SHUT. 

Setting is required 

 

 

 

[Mode B] OPEN. 

 

 

 

Battery out    [HOLD]  Hold the current valve position.

Содержание ABR-300 Series

Страница 1: ...is 8 to 9 years at 25 C It s possible to use for a wide range of temperature ambient temperature 20 to 50 C The battery composed by dry type structure the maintenance of saving water is not necessary...

Страница 2: ...N HOLD Battery out Hold the current valve position Battery Compact seal lead acid battery 12 V 2 5 Ah It is recommend to exchange a battery for every 5 years at 25 C Charge system Constant voltage cha...

Страница 3: ...A SHUT OPEN SHUT Factory setting Option Q Mode B OPEN SHUT OPEN Setting is required Standby mode Mode A FINISH mode SHUT OPEN HOLD SHUT HOLD mode HOLD Mode B FINISH mode OPEN SHUT OPEN HOLD mode HOLD...

Страница 4: ...ttery bracket 21 Battery 4 Motor cover 10 Transformer 16 Bracket fix screw 22 Rubber packing 5 Motor 11 Drive shaft 17 Battery connector 23 Earth screw M3 6 Control board 12 Manual clutch 18 Relay boa...

Страница 5: ...spection and replacement work Maintenance space more than 70 mm upward from the actuator is required Be sure to enough space around the actuator for battery replacement CAUTION AFTER PIPING Until the...

Страница 6: ...cycle is that 3 minutes 20 of 15 minutes operation is possible The calculated value obtained by dividing 3 minutes by the operation time is the number of times of operation within 15 minutes ATTENTION...

Страница 7: ...Confirm existence of abnormal noise and vibration during operation Confirm whether screws are loose or not Confirm that water or condensation no remains in the actuator Turn off the power and check if...

Отзывы: