--2--
Connection:
Always disconnect the power supply to the battery prior to working on the electric system to avoid
short circuit!
It is recommendable to use connection cables of different colours to avoid malfunctions due to mixed up
connections.
•
The unit will not be damaged by wrong polarity, but it will not be operating.
•
Strictly observe the cable cross-sections. The power cable must be as short as possible. Observe the
polarity.
•
Insert fuses as cable protection near the battery.
Connection Plan:
•
Position the fuses for protection of the cables as close as possible to the battery,
for instance Votronic power fuse holder.
•
The charging sources (mains supply charger, solar controller, generator, charging converter etc.) are
connected directly to the battery to ensure battery charging, even with switched-off battery protector.
•
Powerful inverters with own low voltage disconnection are also connected directly to the battery.
Option: Operation with
Sensor Line ““
Selector Switch
6
: “Sens.
Set
Batt.”
to
position “ON” (
-
)
.
Particularly in case of powerful consumer loads being equipped with long charging cables, it is recommendable to measure the
battery voltage unfalsified via a "sensor line"
directly
at the battery. This allows a more precise observation of the charging
voltage rates for connection and disconnection of the battery.
The correct installation of the sensor line is
directly
at the
positive pole (+)
of the
battery
, and never at a distribution or the
like.
The same applies to the
minus
supply. Connect the cable “Battery
–
“ directly to the battery.