Connection:  

 

Always disconnect the power supply to the battery prior to working on the electric system to avoid 

short circuit! 

 

It is recommendable to use connection cables of different colours to avoid malfunctions due to mixed up 

 

 connections. 

 

The unit will not be damaged by wrong polarity, but it will not be operating. 

 

Strictly observe the cable cross-sections. The power cable must be as short as possible. Observe the 

polarity.  

 

Insert fuses as cable protection near the battery.  

 

Connection Plan:  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Position the fuses for protection of the cables as close as possible to the battery,

 

for instance Votronic power fuse holder. 

 

The charging sources (mains supply charger, solar controller, generator, charging converter etc.) are 

connected directly to the battery to ensure battery charging, even with switched-off battery protector. 

 

Powerful inverters with own low voltage disconnection are also connected directly to the battery. 

 

Option:  Operation with

 

Sensor Line ““

 

Selector Switch

 

6

:   “Sens. 

Set 

Batt.”  

to 

position “ON”  ( 

.

 

Particularly in case of powerful consumer loads being equipped with long charging cables, it is recommendable to measure the 

battery voltage unfalsified via a "sensor line" 

directly 

at the battery. This allows a more precise observation of the charging 

voltage rates for connection and disconnection of the battery.  
The correct installation of the sensor line is 

directly 

at the 

positive pole (+) 

of the

 battery

, and never at a distribution or the 

like.  
The same applies to the 

minus

 supply. Connect the cable “Battery 

“ directly to the battery. 

 

 

Содержание Battery Protector 100

Страница 1: ...ry alarm as soon as the switch off level is reached Visual indication of the operating state Audible indication in case of preliminary alarm and disconnection can be deactivated optionally Output for external alarm indication max 0 2 A short circuit proof Input for separate sensor line for unfalsified measurement of the battery voltage Immediate emergency shut down in case of defective battery or ...

Страница 2: ... controller generator charging converter etc are connected directly to the battery to ensure battery charging even with switched off battery protector Powerful inverters with own low voltage disconnection are also connected directly to the battery Option Operation with Sensor Line Sensor Selector Switch 6 Sens Set Batt to position ON Particularly in case of powerful consumer loads being equipped w...

Страница 3: ...he preliminary alarm will be reset If a low voltage disconnection had been released for all that restart can be effected Automatically according to the connection voltage rates which are listed in the table charging mode or Manually at any time by means of the key EMERGENCY ON OFF or remote switch OFF and again ON Key EMERGENCY ON OFF The laterally installed key allows the following functions 1 Ma...

Страница 4: ...delay times or automatic switching threshold 3 2 1 Disconnection Voltage 24 V Connection Voltage 21 2 V 40 s 24 8 V 1 s x 23 0 V 40 s 25 0 V 1 s x 23 6 V 40 s 25 6 V 1 s x x Automatic 25 0 V 2 s 3 2 1 Disconnection Voltage 12 V Connection Voltage x 10 6 V 40 s 12 4 V 1 s x x 11 5 V 40 s 12 5 V 1 s x x 11 8 V 40 s 12 8 V 1 s x x x Automatic 12 5 V 2 s The unit can extend the lifetime of Lithium LiF...

Страница 5: ...rs for the correct disconnection voltage and the time If a battery is permanently discharged with only small current rates disconnection must be effected in case of higher voltage levels By this method the cells are protected from degenerative changes and lasting damages at the electrodes The disconnection will be effected at 12 2 V in 4 weeks Consumer loads with large current draw will cause a qu...

Страница 6: ...rs are protected by disconnection of the supply voltage at 15 5 V 31 5 V Reconnection is effected 20 seconds after a drop below this voltage level If such high voltage levels will be reached repeatedly the charging controller the battery the charger and the battery terminals should be checked Lifetime of the battery The battery protector 100 can extend the lifetime of the battery considerably The ...

Страница 7: ...of gas or dust explosion exists Observe the safety regulations Open air operation of the unit is not allowed Cables are always to be laid in such a way that damage is excluded Observe to fasten them tightly Never lay 12V 24cables and 230 V mains supply cables into the same cable conduit empty conduit Check live cables or leads periodically for insulation faults points of break or loosened connecti...

Страница 8: ...ing PNP maximum 0 2 A Internal fuse 1 A self resetting after disconnection of the consumer Output Voltage During Alarm active 12 V 24 V Voltage at terminal Battery minus approx 0 3 V Output Voltage without Alarm not active 0 V Fitting Position of Unit any Working Temperature Range 20 45 C Protection Class IP21 Dimensions mm 105 x 77 x 38 mm Weight 180 g Ambient Conditions Humidity of Air max 95 RH...

Отзывы: