Maximum CO2concentration setting (ppm) (Fig. 23d):
• to view the parameter, press: SET and NEXT (several
times);
• set the value of the flashing field with the + and - keys
(from 500 ppm to 3000 ppm, in steps of 50 ppm, or
OFF: no CO2 monitoring).
Speed Vmin setting (fig.23e):
Vmin setting (fig.23e):
• to view the parameter, press: SET and NEXT (several
times);
• set the value of the flashing field with the + and - keys
(from 0 to 69, in steps of 1).
Speed Vmax setting (fig.23f):
• to view the parameter, press: SET and NEXT (several
times);
• set the value of the flashing field with the + and - keys
(from Vmin+10 to 99, in steps of 1).
DISPLAY button
(fig.24)
During normal operation, the following information will
appear on the remote control display when the
appliance is switched on:
the time;
the day of the week;
the operating mode: (AUTO, MAN, BP);
the operating speed: (Min, Max, Mid (the latter in MAN
mode only)).
Press and hold the DISPLAY key for half a second
repeatedly to view the following system parameters in
sequence:
outdoor temperature (fig.24a)
during normal operation, detected by the temperature
sensor located in the house outlet duct, before the heat
exchanger;