background image

Errors handling

ER02 (automatic reset)
Check the Tout sensor reading from the corresponding menu. Make sure the sensor is properly connected inside
the panel. Replace the sensor at the outdoor fresh air intake point.

ER04 (automatic reset) 
Check the Te sensor reading from the corresponding menu. Make sure the sensor is properly connected inside
the panel. Replace the sensor at the outdoor exhaust outlet.

ER07 (manual reset)
Check whether or not the preheater is actually installed, and if not, verify the status of the Heat parameter in the
Frst menu, which must be disabled. If the preheater is installed and enabled, make sure that it is correctly wired,
then check the 230 Vac power supply and the signal coming from the appliance. Replace the preheater

ER08 (manual reset)
Check the actual Tout air temperature. Check that the temperature read by the sensor is the same as the actual
air  temperature,  and  if  not,  replace  the  sensor.  Check  that  the  preheater  is  installed  at  the  correct  distance.
Check that the preheater switching relay is not faulty.

ER10 (automatic reset, via manual reset of the counter for filter life days) 
Two months after the “FILT” (filter saturated) message is first displayed, the appliance stops or keeps running,
depending on the response set at the time of installation. If it stops, you will need to replace the filter and reset
the respective meter from the RST-FLTR menu in the user panel. Even if the appliance does not stop, it is still
advisable to replace the filter as soon as possible.

Maintenance/cleaning

Before commencing any servicing operation, make sure that the appliance is disconnected from the electrical
power  supply.  Dismantling  and  assembly  are  special  maintenance  operations  and  must  be  entrusted  to
professional technicians.
The  heat  exchanger  does  not  require  special  routine  maintenance:  it  does  not  therefore  need  to  be
disassembled.  Routine  maintenance  of  the  appliance  is  therefore  limited  to  regular  replacement  of  the  filters,
after opening the two doors on the front of the appliance. 

Filters

Recommended maintenance intervals
Because levels of air pollution depend typically on geographical location and are variable, the life of the filters
will be similarly variable. With this general consideration in mind, the following filter maintenance intervals are
recommended:  inspect  filters:
every 50/60 days;
replace  filters:  after  3/12  months
(depending on the value set by the
installer during installation) 
N.B.  Failure  to  clean  or  replace
filters  can  seriously  affect  the
efficiency of the system, causing:
- increased pressure losses in the
air circulation system and reduced
airflow;
- drop in system performance and
comfort levels caused by pressure
losses.
N.B.  Clogged  air  filters  are  the
most  frequent  cause  of  the
appliance locking up:
Removing the filters: see fig.14

19

ENGLISH

 14

 14

Содержание VORT HR 350 EXO

Страница 1: ...VORT HR 350 EXO COD 5 571 084 222 11 04 2019 Libretto istruzioni Instruction booklet Manual de instrucciones...

Страница 2: ...is booklet Following these instructions will ensure a long service life and overall electrical and mechanical reliability Keep this instruction booklet in a safe place Table of Contents EN Description...

Страница 3: ...uso di qualsiasi apparecchio elettrico comporta l osservanza di alcune regole fondamentali tra le quali non toccarlo con mani bagnate o umide non toccarlo a piedi nudi Non utilizzare l apparecchio in...

Страница 4: ...dedicato Il flusso d aria estratto deve essere pulito cio privo di elementi grassi fuliggine agenti chimici e corrosivi o miscele esplosive ed infiammabili Non coprire e non ostruire l aspirazione e l...

Страница 5: ...nteso ad evitare la formazione di condensa e l entrata di acqua piovana Scarico condensa Nel corso del normale funzionamento sul fondo dell apparecchio si raccoglie condensa all interno di una doppia...

Страница 6: ...e dei filtri sono facilmente accessibile sul lato frontale dell apparecchio fig 5a per permettere la rimozione e sostituzione dei filtri dell aria Vedi anche paragrafo Manutenzione pulizia Il pannello...

Страница 7: ...tore La distanza minima del pre riscaldatore dall apparecchio di 500 mm Funzioni utente pannello comandi Generalit fig 7 Pulsanti 1 F1 UP 2 F2 ESC 3 F3 DOWN 4 F4 SET Icone display a allarme b stand by...

Страница 8: ...MP visualizzazioni temperature AL visualizzazione messaggi d allarme RST reset allarmi e contatore giorni residui di vita del filtro Menu TEMP fig 11 Premendo il tasto F4 set si accede alle opzioni de...

Страница 9: ...RST premere F1 up F3 down per spostarsi da una all altra ALR allarmi premere F4 set per entrare nelle opzioni di reset ON per resettare OFF per non resettare tutti gli errori a reset manuale premere F...

Страница 10: ...resettare il contatore relativo dal menu RST FLTR del pannello utente Anche nel caso di non arresto dell apparecchio comuqnue consigliabile procedere al pi presto alla sostituzione del filtro Manutenz...

Страница 11: ...nuova apparecchiatura equivalente L utente responsabile del conferimento dell apparecchio a fine vita alle appropriate strutture di raccolta pena le sanzioni previste dalla vigente legislazione sui ri...

Страница 12: ...amp hands never touch the appliance while barefoot Do not operate the appliance in the presence of inflammable vapours alcohol insecticides petrol etc If the appliance is to be disconnected from the p...

Страница 13: ...f grease soot chemical and corrosive agents and explosive or flammable mixtures Keep the air intake and outlet ports of the appliance free of obstructions to ensure optimum air flow Maximum operating...

Страница 14: ...formation of condensate and the entry of rain water Condensate drain During normal operation condensate collects at the bottom of the appliance in a double tray provided with two drain outlets The co...

Страница 15: ...areas of the filters are easily accessible on the front side of the appliance fig 5a to allow removal and replacement of the air filters see also paragraph Maintenance and cleaning The control panel i...

Страница 16: ...the preheater from the appliance is 500 mm User panel functions General fig 7 Pulsanti 1 F1 UP 2 F2 ESC 3 F3 DOWN 4 F4 SET Display icons a alarm b stand by c no frost d temperature e alphabetic charac...

Страница 17: ...rom one to another TEMP display temperature AL view alarm messages RST reset alarms and counter for filter life days remaining Set TEMP menu Fig 11 Press button F4 set to access the TEMP menu options...

Страница 18: ...ccess the RST menu options press F1 up F3 down to move from one to another ALR alarms press F4 set to enter reset options ON to reset OFF to not reset all manual reset errors press F1 up and F3 down t...

Страница 19: ...to replace the filter and reset the respective meter from the RST FLTR menu in the user panel Even if the appliance does not stop it is still advisable to replace the filter as soon as possible Mainte...

Страница 20: ...se of a replacement It is the user s responsibility to dispose of this appliance through the appropriate channels at the end of its useful life Failure to do so may incur the penalties established by...

Страница 21: ...o personas diversamente h biles El uso de aparatos el ctricos debe implica cumplir con determinadas reglas fundamentales entre ellas no tocarlo con las manos mojadas o h medas no tocarlo con los pies...

Страница 22: ...ectamente al exterior en un conducto individual espec fico El flujo de aire extra do debe estar limpio es decir sin elementos grasos holl n agentes qu micos o corrosivos o mezclas explosivas e inflama...

Страница 23: ...ndensaci n dentro de una cubeta doble dotada de dos descargas hacia el exterior Los puntos de conexi n se encuentran en la zona inferior de la parte posterior del aparato El desagote de la condensaci...

Страница 24: ...del lado frontal del aparato fig 5a para poder quitar y cambiar los filtros de aire V ase tambi n el aparato Mantenimiento limpieza El panel de mando es de f cil acceso desde la puerta en el lado fron...

Страница 25: ...pre calefactor al aparato es de 500 mm Funciones usuario panel de mando Generalidades fig 7 Pulsadores 1 F1 UP 2 F2 ESC 3 F3 DOWN 4 F4 SET Pantalla icono a alarma b stand by c no frost d temperatura...

Страница 26: ...otra son TEMP visualizaci n temperatura AL Visualizaci n mensajes de alarma RST reset alarmas y contador d as que restan de vida del filtro Men TEMP fig 11 Presionando el bot n F4 set se entra en las...

Страница 27: ...F3 down para desplazarse de una a otra ALR alarmas presionar F4 set para entrar en las opciones de reset ON para reajustar OFF para no reajustar todos los errores con reset manual presionar F1 up y F3...

Страница 28: ...el panel usuario Incluso en el caso de no parada del aparato se aconseja realizar el cambio del filtro lo antes posible Mantenimiento y limpieza Antes de comenzar cualquier operaci n comprobar que el...

Страница 29: ...rtadores cumplen con su responsabilidad de recuperaci n tratamiento y eliminaci n respetuosa con el medio ambiente directamente o participando a un sistema colectivo VORTICE LIMITED Beeches House East...

Страница 30: ...CENTRE CACHET SERVICE APRES VENTE TAGLIANDO INTERVENTO IN GARANZIA CERTIFICATE OF WORK PERFORMED UNDER GUARANTEE COUPON INTERVENTION SOUS GARANTIE DATA INTERVENTO DATE OF WORK DATE INTERVENTION TIMBRO...

Страница 31: ...or modified or repaired by any person not authorised by us The correct electricity supply voltage is shown on the rating plate attached to the appliance This guarantee is normally available only to th...

Страница 32: ...e di alimentazione elettrica o per tensione di alimentazione diversa da quella prevista per l apparecchio ovvero diversa dal limite stabilito dalle norme CEI 10 del valore nominale La presente garanzi...

Отзывы: