13
ENGLISH
Remote Input #1 - "Air extraction at maximum speed mode"
2-pole spring clamp from PCB (IN#,COM ), 12Vdc, suitable for cables with maximum cross-section 1.5mm2.
When the contact is closed, all connected devices will work to extract air from the environment at maximum speed:
- Boost on
=
LED BOOST + LED 1 + LED2 + LED 3 + LED 4: on;
- Extraction on
=
EXTRACTION LED: on.
Keeping the function on, the LEDs will switch off automatically after 20 seconds.
Remote Input #2 - "Heat recovery at maximum speed mode"
2-pole spring clamp from PCB (IN#,COM ), 12Vdc, suitable for cables with maximum cross-section 1.5mm2.
When the contact is closed, all connected devices will work to recover heat at maximum speed:
- Boost on
=
LED BOOST + LED 1 + LED2 + LED 3 + LED 4: on;
- Recovery on
=
RECOVERY LED: on.
Keeping the function on, the LEDs will switch off automatically after 20 seconds.
Remote Input #3 - "Air supply at maximum speed mode"
2-pole spring clamp from PCB (IN#,COM ), 12Vdc, suitable for cables with maximum cross-section 1.5mm2.
When the contact is closed, all connected devices will work to supply air into the environment at maximum speed:
- Boost on
=
LED BOOST + LED 1 + LED2 + LED 3 + LED 4: on.
Keeping the function on, the LEDs will switch off automatically after 20 seconds.
Wiring diagrams
See fig.6 - 7
-
Appliance: Vort HRW 20 Mono D
(See Fig. 6)
①
FAN header terminal block;
②
FAN plug terminal block;
③
Vort HRW 20 Mono D FAN.
- Remote Control: HRW RC D
(See Fig. 7)
①
Electronic board (rear view);
②
12 V Electric supply (two alternate solutions):
electric diagram for wall mounting - up to 4 controlled units;
electric diagram for wall mounting - up to 6 controlled units;
electric diagram for DIN electric panel - up to 6 controlled units;
③
Dry contact, without electrical potential (remote switch/relay);
④
Mains 2 poles switch (230V ~50HZ).
⃝
2A
⃝
2B
Mounting schemes
①
Remote Control;
②
Power supply for wall mounting - up to 4 controlled units (cod. 21.187);
③
Power supply for wall mounting - up to 6 controlled units (cod. 21.188);
④
Power supply for electrical panel (DIN bar) - up to 6 controlled units (cod. 21.189);
⑤
Wall electrical box - DIN
49073
,
ØxP = 60 x 66 mm
(not supplied);
⑥
Wall electrical box - DIN
49073
,
ØxP = 68 x 47 mm
(not supplied);
- Mounting with Transformer for wall mounting:
•
Up to 4 controlled units: See Fig. 4A;
•
Up to 6 controlled units: See Fig. 4B;
- Mounting with Transformer for electrical panel:
•
See Fig. 5.
⃝
2C