14 of 16
17
APPLY POWER TO POWER SUPPLY. IF 900-BB IS USED, THEN RECONNECT BATTERIES
18
CHECK OPERATION
a. Activate each input and verify all QEL devices operate properly.
NOTE: During the first activation, each device will perform a one time self calibration, which is normal. For best results, power
each device separately so that the calibration cycles do not overlap.
b. If any device does not operate properly, see step 19 for troubleshooting.