6
11
10
When properly adjusted, secure
strike with additional screw(s).
IMPORTANT!
Perform operational check.
B.
With door closed, push device pushbar.
Device should allow door to open.
A.
With door closed, push against
door without touching device.
Device should NOT allow door to open.
C.
If device does not function as described,
adjust strike position and continue
operational check until device functions
as described above.
Strike plate
#7 Drill
1/4”-20 tap
Meta
l
Locate hole at
center of slot
#7 Drill
1/4”-20 tap
2 places
909 Strike
954 Strike
A
B
9
Verify gap between latch bolt and
strike and adjust strike as needed.
Strike MUST have some gap
Gap
(no more than 3/16”)
12
Note about the XP latch operation
The XP latch bolt operates differently from a
standard latch bolt. When the pushbar is
depressed, the latch bolt does not retract.
This is normal because the XP latch bolt can
swivel in both directions.
Latch bolt
IMPORTANT!