19.  Troubleshooting 
 

If no display comes up after connection to the input, check for correct input polarity. 
Disconnect all cables to the unit and check the input fuse. 
 
The LED will display an error code when the converter is in any protection mode. 
The following table denotes the 8 Error Codes.   
 

Error Code

 

Description

 

F01

 

Over Temperature Protection (Self-restart) 
 

When unit’s internal temperature becomes higher than the threshold value, unit shuts down the 
output. Unit will resume normal operation automatically once the temperature becomes normal.

 

F02

 

Output Over Voltage Protection (Self-restart) 
 

In DC-DC Converter Mode, output shuts down when the output voltage is 15% higher than the 
preset voltage level. Unit will self-restart when the output voltage falls 1V below the preset 
level. 
 
In the Bulk Charge Stage of Charger Mode, the unit shuts down >16V and restarts when the 
voltage <15.5V.   
In Float Charge Stage it shuts down when voltage >15.1V and restarts at < 14.6V.

 

F03

 

Over Load Protection (Self-restart) 
 

When the Output current is 2 Amp higher than 20A, the unit will shut down the output. 
The unit will self-

restart once the output current falls back to unit’s rated value.

 

F04

 

Fan Fault (Self-restart) 
 

When the fan does not operate normally, the unit will shut down the output. Unit will resume 
normal operation once the fan fault condition has been removed.

 

F05

 

Input Low Voltage Protection (Self-restart)

 

Input V 

<

 42V

 

Alarm signal On

 

Input V 

>

 50V

 

Alarm signal Off

 

35V 

<

 Input V 

38V for 3 min.

 

Output shuts down; self-restart > 50V

 

Input V 

<

 35V

 

Output instant shut down; self-restart >50V

 

F06

 

Output Short Circuit Protection (Self-restart) 
 

Unit shuts down output when the output is short circuited. 
It will self-restart when the fault condition is removed.

 

F07

 

Output battery terminal reverse polarity protection 
 

Fuse will be blown when the output is reverse polarity connected to the battery.   
Replace the fuse with correct type and rating.

 

F08

 

Input over voltage protection (Self-restart) 
 

Output shuts down when the input voltage is higher than 64V. 
It will self-restart when the input drops below 61V.

 

 
 
 
 
 
 
 

 

Содержание VC-4820

Страница 1: ...4 3V Bulk and 13 6V Float charge 3 3 digit LED display for displaying Voltage Current Operation Mode and Protection Fault Diagnosis 4 Remote Control Terminal for Manual or Automatic On Off control of...

Страница 2: ...rger mode 4 SET button 5 INPUT OUTPUT CONTROL AUXILARY TERMINALS VIEW Remote Remote Terminal for Automatic Manual control of Output On Off 12V 0 5A Always On Auxiliary Output GND Ground terminal NC No...

Страница 3: ...6 Wiring Diagram 6 1 Connection Diagram 1 Example 1 Example 2 Example 3...

Страница 4: ...epeat step 4 to get to programmable mode again 6 Each short press will increase the output voltage setting by 0 2V steps 15 0V CHA Charger Mode And then back to 12 0V as shown in the following cycle c...

Страница 5: ...control of the output via external switch B The remote On Off function can be controlled via many types of On Off switches and with various DC sources between 8V 32V 3 Once the Remote Terminal has be...

Страница 6: ...ter and charger mode Battery is fully charged when the output float voltage is 13 6V and the current to the battery is less than 1Amp Remote Voltage Sensing Voltage converter can be finely tuned to su...

Страница 7: ...rge Quick press the SET button to display charging Voltage and Current Please note that when the battery is full and the float charge current is less than 1A the current display shows 11 DISPLAY INDIC...

Страница 8: ...e display for another 5 minutes 15 ALWAYS ON AUXILIARY OUTPUT The DC DC Converter will provide constant 12V 0 5A to power critical devices such as security or alarm and will supply a positive voltage...

Страница 9: ...and restarts at 14 6V F03 Over Load Protection Self restart When the Output current is 2 Amp higher than 20A the unit will shut down the output The unit will self restart once the output current fall...

Страница 10: ...20A Float Charge 13 6V Remote Control of Output ON OFF Yes Automatic or Manual Control Remote Voltage Sense Yes External Alarm Output 13 5V 0 25A To power warning device when the input is under volta...

Отзывы: