Technical Data
TOPS-3205
TOPS-3363
TOPS-3602
Output voltage
1 - 20 V/DC
1 - 36 V/DC
1 - 60 V/DC
Output current
0.25 – 5 A
0.25 – 3 A
0.25 – 1.6 A
Display resolution
0.01 V / 0.001 A
Display accuracy "V"
< 5 V: ±0.05 V
≥ 5 V: ±(0,2% + 0.05 V)
Display accuracy "A"
≤ 1 A: ±0.015 A
> 1 A: ±(0,5% + 0.006 A)
Max. output power
100 W
Residual ripple (p-p)
<120 mV
<150 mV
<180 mV
Control response at
Change of load 10~90%
70 mV
50 mA
Control response at
Mains change 10%
25 mV
20 mA
Output USB AUX 1
5 V/DC, max. 1.8 A
Output USB AUX 2
5 V/DC, max. 1.8 A
Mains fuse
5x 20 mm fine fuse
T2A/250 V time lag
Operating temperature
+5 °C to +40 °C
Rel. Humidity
max. 85%, non-condensing
Max. operating altitude
2000 m above sea level
Pollution degree
2
Operating voltage
100 - 240 V AC, 50/60 Hz
Power consumption max.
1.6 A (at 230 V ca. 0.83 A)
Protection class
1
Power factor (active PFC)
>0.9
Degree of effectiveness
≥80.5 %
Unit' cooling system
Convection
Dimensions (W x H x D)
70 x 150 x 250 (mm)
Weight
2 kg
LVD Directive 2006/95/EC
EN 61010