7.2 Reset the Counter (ctr clr/CTR=0?)

To reset the counter to zero, navigate through the menu to ‘ctr clr’ then press the              key. The display will indicate 
‘CTR = 0?’. Clear the counter by pressing the              key again.  Return to the harvesting mode by pressing the                key 
twice.

7.3 Application Rate (Dos ml/t) 

This value defines the inoculant application rate on the crop in ml/t. It can be set from 10 ml/t up to 50 ml/t in steps of 1 
ml/t. The value is factory preset to 20 ml/t (Ecosyl ULV). The flow rate of the pump in ml/min is determined by this and 
the harvest rate set by the dial on the control box. 

7.4 Calibration Value (Cal flow)

The pump flow rate is affected by the physical properties of the inoculant, eg viscosity.  The Ecosyler is delivered with 
the Calibration value set at 1.00 which corresponds to Ecosyl ULV application at 20ml/t. If a different inoculant or flow 
rate is used the pump should be recalibrated to retain accuracy. The Calibration value is a multiplication factor of the 
flow rate shown on the display (0.85 to 1.15 in steps of 0.01) and aligns the flow rate displayed with the actual flow rate.

Calibrating of the Flow Rate

1.  Fill the applicator system with the inoculant to be used
2.  Place a measuring jug at the tank outlet to collect the inoculant 
3.  Configure the pump for use without a table sensor and the display to indicate the flow rate in litres/hour and the  
 

counter in litres, ie in ‘Cfg Dev’ set all three digits to ‘1’.  (Note your original settings for reconfiguration later)

4.  Reset the counter to zero in ‘ctr clr’
5.  Set the calibration value ‘flow rate’ to 1.00, ie ‘cal flow’ = 1.00 (default value for Ecosyl ULV)
6.  Set the flow rate to max 7.6 litres/h using the dial on the side of the control box 
7.  Start the pump by pressing the                key on the control box 
8.  Collect at least 500ml (~4 minutes) then stop the pump by pressing the                 key
9.  View the counter reading in litres
10.  Divide the amount of inoculant collected by the counter reading (the counter measures to the nearest 10ml), eg  
 

0.75 in jug ÷ 0.8 on counter = 0.94 (calibration value of inoculant)

11.  Enter this new value in ‘cal flow’. Values of 0.85 to 1.15 are allowed. Less viscous inoculants will have values closer to  
 0.85.
12.  Reconfigure the control box to your preferred settings (see point 3 above)

7.5 Configuration of the Device (Cfg Dev)

There are 3 configuration parameters that require setting on the control box before you start harvesting.                 
The settings are all independent and you can change the display at any point during harvest:

1.  Whether the harvester has a table sensor or not
2.  Whether the display shows the harvest rate in t/h or the additive usage rate in l/h. 
3.  Whether the counter shows total tonnes of crop harvested or number of litres of inoculant applied 

Note: The control box as supplied is set for a harvester with a table sensor, the display showing harvest rate in 
tonnes/hour and the counter total tonnes.

To change the control box settings:

1.  Navigate to ‘Cfg Dev’ in the menu then press the                  key
2.  The display indicates ‘Cfg: 0 0 0’ - the cursor underlines the position to change.  Use the                  and                   keys  
 

to toggle between 0 and 1. To confirm the new setting and move to the next  position, press 

3.  For harvesters with a table sensor, set the first digit to 0; for those without, set it to 1
4.  For the display to show the harvest rate in tonnes/h, set the second digit to 0; for it to show the Flow rate in litres/h,  
 

set it to 1

5.  For the counter to show total tonnes, set the third digit to 0; for it to show total litres, set the third digit to 1
6.  Confirm your final choice using the                  key 

Note: You must confirm all 3 digits before returning to harvest setting, even if you only change one digit. If you 
do not, the new value will not be registered

-6-

Содержание Ecosyl ECOSYLER 08

Страница 1: ...ting mode 4 5 Counter 4 6 Alerts 4 6 1 Low Level 4 6 2 Pump 4 7 Control Box Menu 4 7 1 View the counter reading Counter tonnes or litres 4 7 2 Reset the counter ctr clr CTR 0 6 7 3 Application rate Do...

Страница 2: ...et supplied 2 3 Nozzle The nozzle should be placed in the lower side of the chute approximately midway along its length eg fit into the centre of a convenient cleaning flap Drill a 14mm diameter hole...

Страница 3: ...ches to Cleaning mode forward or twice 2 rapid clicks to Cleaning mode reverse Pressing the key takes you into the menu where you can reset the counter and change various applicator parameters see sec...

Страница 4: ...both of which cause the Alert LED on the control box to flash and an audible warning which can be cancelled by pressing the key The display will return to normal but the red LED continues to flash un...

Страница 5: ...NB Before returning to harvest mode you must confirm all 3 digits even if only one changed t h or l h rate of harvest or additive use Counter accesses the counter t or l total tonnes harvested or lit...

Страница 6: ...e control box 8 Collect at least 500ml 4 minutes then stop the pump by pressing the key 9 View the counter reading in litres 10 Divide the amount of inoculant collected by the counter reading the coun...