background image

16

Fig. 17 

A

Fig. 18

5.1  GAS SUPPLY INSTALLATION

Inspect the entire installation including the gas meter, test for 

tightness and purge. Refer to BS 6891 (I.S. 813 in ROI) for 

specific instruction.

5.2  THE HEATING SYSTEM

The appliance contains components that may become damaged 

or rendered inoperable by oils and/or debris that are residual 

from the installation of the system, consequently it is essential 

that the system be flushed in accordance with the following 

instructions.

5.3  INITIAL FILLING OF THE SYSTEM

Ensure both flow and return service valves are open, remove 

appliance casing as described in 4.7.1, identify the automatic air 

release valves (AAV) and loosen the dust cap/s by turning the 

cap anti-clockwise one full turn. Ensure all manual air release 

valves located on the heating system are closed. Connect the 

filling loop as shown in fig. 5, slowly proceed to fill the system 

by firstly opening the inlet valve connected to the flow pipe, and 

then turning the lever on the fill valve, to the open position. As 

water enters the system the pressure gauge will begin to rise. 

Once the gauge has reached 1 BAR close both valves and begin 

venting all manual air release valves, starting at the lowest first. 

It may be necessary to go back and top-up the pressure until 

the entire system has been filled. Inspect the system for water 

tightness, rectifying any leaks.

5.3.1  MANUAL AIR RELEASE (fig. 19)

When the boiler has been filled for the first time or the system 

has been drained and refilled, it will be necessary to release 

any air that may have become trapped within the appliance 

heat exchanger. Slacken the bleed screw until water is released 

and then close.

IMPORTANT, THERE ARE NO OTHER MANUAL AIR RE-

LEASE VALVES LOCATED ON THE APPLIANCE.

Fig. 19

SECTION 5 - COMMISSIONING

5.4  INITIAL FLUSHING OF THE SYSTEM

The whole of the heating system must be flushed both cold 

and hot as detailed in 5.8. Open all radiator or heating valves 

and the appliance flow & return service valve. Drain the boiler 

and system from the lowest points. Open the drain valve full 

bore to remove any installation debris from the boiler prior to 

lighting. Refill the boiler and heating system as described in 5.3.

5.5  PRE-OPERATION CHECKS

Before attempting the initial lighting of the appliance, the fol-

lowing checks must be carried out:

•  ensure all gas service valves from the meter to the appliance 

are open and the supply pipe has been properly purged;

•  ensure the proper electrical checks have been carried out, 

(see 7.8) particularly continuity, polarity and resistance to 

earth;

•  ensure the 3 AMP fuse – supplied with the appliance – has 

been fitted;

•  ensure the system has been filled, vented and the pressure 

set to 1 BAR;

•  ensure the flue system has been fitted properly and in ac-

cordance with the instructions;

•  ensure all appliance service valves are open.

5.6  INITIAL LIGHTING

Ensure the electrical supply to the appliance is switched on. 

Ensure any external controls are switched to an ‘ON’ position 

and are calling for heat. Move the selector switch to the ON 

position, the appliance will now operate as described in 1.2. 

Should the appliance fail to ignite, refer to 5.6 and/or section 7 

(mode of operation, parameter setting & faultfinding).

5.7  CHECKING GAS PRESSURE AND 

COMBUSTION ANALYSIS

The appliance is factory set so should require no additional 

adjustment once installed. However to satisfy the require-

ments of GSIUR 26/9 (I.S. 813 ROI), it will be necessary to 

gas rate the appliance using the gas meter that serves the 

appliance and carry out a combustion analysis check in accor-

dance with BS 7967 (UK) to ensure that correct combustion is 

occurring, see flow chart on page 30.

Additionally, if the gas valve has been adjusted, replaced, or 

the appliance has been converted for use with another gas 

type, then it becomes necessary to carry out a combustion 

analysis check to ensure that correct combustion is occurring.

If there are no means to carry out a combustion analysis 

check, then it will not be possible to complete the commissio-

ning procedure.

Details on how to carry out the combustion analysis can be 

found in section 7.

IMPORTANT

It’s imperative that a sufficient dynamic – gas – pressure is 

maintained at all times. Should the dynamic gas pressure fall 

below an acceptable level, the appliance may malfunction or 

sustain damage.

Содержание Easi-Heat Plus 25C

Страница 1: ...D BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Easi Heat Plus C High effici...

Страница 2: ...WATER CIRCULATION 12 3A 7 ELECTRICAL SUPPLY 12 3A 8 MOUNTING ON A COMBUSTIBLE SURFACE 12 3A 9 TIMBER FRAMED BUILDINGS 12 3A 10 INHIBITORS 12 3A 11 SHOWERS 12 3A 12 DECLARATION OF CONFORMITY 12 SECTIO...

Страница 3: ...has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to rea...

Страница 4: ...ounter clockwise to reduce the temperature range 40 C 80 C for standard central heating The automatic temperature control function SARA is factory disabled To enable this function please contact the V...

Страница 5: ...ntly hot enough it may be necessary to reduce the flow of water at the hot water outlet tap NOTE If the appliance fails to ignite during the ignition sequence it will enter a lockout condition Should...

Страница 6: ...position To select OFF mode move the selector switch in the upper position APPLIANCE STATUS LED AND FAULT CODES Fig 3 4 WHAT IF 5 SETTING THE VOK RA Advice for homeowners Please contact Vok ra Custome...

Страница 7: ...tained from Vok ra customer services When the product reaches the end of its life it should not be disposed of as solid urban waste but should be brought to a separated waste collection facility Easi...

Страница 8: ...n and the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat withi...

Страница 9: ...ght mm 792 Width mm 405 Depth mm 253 Dry weight kg 27 30 2 6 Clearances Easi Heat Plus 25C Easi Heat Plus 29C Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 1...

Страница 10: ...rature boilers 37 C and for other heaters 50 C return temperature at heater inlet Seasonal space heating energy efficiency class A Water heating energy efficiency class A Parameter Symbol Value Unit P...

Страница 11: ...lcony level 300 mm J From a surface or boundary facing the terminal 600 mm K From a terminal facing a terminal 1200 mm L From an opening in the car port into the building 1200 mm M Vertically from a t...

Страница 12: ...c directly from the mains supply must be provided see fig 8 This method of filling complies with the current Water Supply Water Fittings Regulations 1999 and Water Bylaws 2000 Scotland If an alternati...

Страница 13: ...s to be fitted on a wall of combustible material There is no requirement to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedi...

Страница 14: ...LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system...

Страница 15: ...talsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 metre 60 100 1 0 metre 80 12...

Страница 16: ...flue length see table below Reduction for bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 metre 60 100 1 0 metre 80 125 90 bend 1 0 metre 60 100 1 0 metre 80 125 Vertical flue te...

Страница 17: ...no less than 20mm diameter to the outlet pipe and ensure it discharges in accord ance with building regulations or other rules in force 4 7 ELECTRICAL CONNECTIONS The boiler is supplied with a 2 metre...

Страница 18: ...to remove any installation debris from the boiler prior to lighting Refill the boiler and heating system as described in 5 3 5 5 PRE OPERATION CHECKS Before attempting the initial lighting of the appl...

Страница 19: ...this appliance including these instructions and explain the importance of keeping them in a safe place Explain to the user how to isolate the appliance from the gas water and electricity supplies and...

Страница 20: ...nd remove the pump outlet pipe A from the pump assembly combustion chamber connection Remove the expansion pipe locking pin B from the top of the pump assembly and withdraw the flexible pipe Locate an...

Страница 21: ...the reverse order Check and adjust burner pressure settings WARNING A GAS TIGHTNESS CHECK MUST BE CAR RIED OUT 6 13 ELECTRODES fig 27 Carry out component removal procedure as described in 6 4 Remove t...

Страница 22: ...e carefully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 Ensure all seals are in good condition taking care to ensure they are replaced correctly Replace in the reverse order e...

Страница 23: ...anger DisconnectthewiringtotheDHWflowswitch Slacken and unscrew the inlet connection Unscrew the nut E2 Lift the DHW flow switch housing from its seating If necessary remove the locking pin F2 from th...

Страница 24: ...e gas rate to 75 for a period of 15 minutes The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the flow temperature sensor consequently...

Страница 25: ...tion analysis check can easily be carried out on the appliance via the test points located on the top of the applian ce see 7 3 Operate the boiler in combustion analysis mode see 7 3 1 Insert the flue...

Страница 26: ...o proceed to next stage If not see 7 7 4 connect test leads between the Neutral Earth connec tions at the appliance terminal strip The meter should read approximately 0 15Vac If so polarity is correct...

Страница 27: ...particular control Further guidance on the recom mended practice for the installation of external controls can be found in CHeSS HC5 HC6 www energyefficiency gov uk 8 4 VOK RA LOWER COVER MECHANICAL...

Страница 28: ...ic hot water temperature WPS Water pressure switch S E Spark electrode TSC2 Ignition transformer 3W 3 way motor F O H T Flow over heat thermostat FS Flue sensor FT Flow thermistor NTC RS Return thermi...

Страница 29: ...37 0 mbar 37 0 mbar Heating maximum gas rate kg hr 1 55 1 94 DHW maximum gas rate kg hr 1 94 2 25 Minimum gas rate kg hr 0 39 0 47 Injector size 3 8 mm 3 9 Silencer flange 27 mm 29 mm CO2 maximum outp...

Страница 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Страница 31: ...ommissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarantee...

Страница 32: ...terlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Страница 33: ...gister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate C...

Страница 34: ......

Страница 35: ......

Страница 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited...

Отзывы: