background image

14

EXTENDING THE FLUE

Connect the bend – supplied with the terminal kit – to the top 

of the boiler using clamp (supplied) see fig. 11. The additional 

bends & extensions have push-fit connections, care should be 

taken to ensure that the correct seal is made when assembling 

the flue system. Connect the required number of flue exten-

sions or bends (up to the maximum equivalent flue length) to 

the flue terminal (see fig. 11-15).

 

The flue system should have 

a minimum of 1º; maximum of 3º rise from the boiler to outside, 

to ensure any condense fluid that forms, is allowed to drain 

back to the appliance.

NOTE

When cutting an extension to the required length, you must 

ensure that the excess is cut from the plain end of the extension 

(see fig. 11-15). Remove any burrs, and check that all seals are 

located properly. You must ensure that the entire flue system is 

properly supported and connected. Seal the flue assembly to 

the wall using cement or a suitable alternative that will provide 

satisfactory weatherproofing. The interior and exterior trim can 

now be fitted.

Fig. 14

4.5.2 CONCENTRIC VERTICAL FLUE

The appliance can be used with either the Vokèra condensing 

60/100mm concentric flue system or the optional 80/125mm 

concentric flue system. 

Fig.13

A

Fig. 12

NOTE

These instructions relate 

only

 to the Vokèra condensing 

60/100mm concentric flue system. For specific details on the 

installation of the 80/125mm concentric flue system please refer 

to the instructions supplied.

The  vertical  flue  terminal  can  be  connected  directly  to  the 

appliance flue outlet. Alternatively, an extension or bend can 

be connected to the appliance flue outlet if desired, however 

if additional bends are fitted, a reduction must be made to the 

maximum flue length (see table below).

Reduction for bends

Bend 

Reduction in maximum flue length for each bend

45º bend

1.0 metre (60/100) - 1.0 metre (80/125)

90º bend

1.0 metre (60/100) - 1.0 metre (80/125) 

 

Vertical flue terminal and accessories

Part No.

Description 

Length

29450122

Vertical flue terminal

1000mm

531

Pitched roof flashing plate N/A

532

Flat roof flashing plate

N/A

29450123

90-degree bend

N/A

29450124

45-degree bends (pair)

N/A

29450125

500mm extension

500mm

29450126

1000mm extension

1000mm

29450127

2000mm extension

2000mm

29450128

Telescopic extension

372/519mm

529

Wall bracket pack (5)

208mm

Using the dimensions given in fig. 12 as a reference, mark and 

cut a 125mm hole in the ceiling and/or roof.

Fig. 15

Fit the appropriate flashing plate to the roof and insert the ver-

tical flue terminal through the flashing plate from the outside, 

ensuring that the collar on the flue terminal fits over the flashing.

The fixing holes for the wall-mounting bracket should now be 

drilled and plugged, an ‘appropriate type and quantity of fixing 

should be used to ensure that the bracket is mounted securely. 

Once the bracket has been secured to the wall, mount the ap-

pliance onto the bracket.

IMPORTANT

The vertical flue terminal is 1.0 metre in length and cannot be 

cut; therefore it may be necessary to adjust the height of the 

appliance to suit or use a suitable extension.

Connect the vertical flue assembly to the boiler flue spigot us-

ing the 100mm clip, gasket & screws (supplied), ensuring the 

correct seal is made. The flue support bracket (supplied with 

the vertical flue kit) can now be fitted. 

If the vertical flue requires extension/s or additional bend/s, 

connect the required number of flue extensions or bends (up 

to the maximum equivalent flue length) between the boiler and 

vertical flue assembly.

Ensure that any horizontal sections of the flue system have a 

minimum 1º; maximum 3º fall back to the boiler (1º = 17mm 

per 1000mm).

Содержание Easi-Heat Plus 25C

Страница 1: ...D BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK Easi Heat Plus C High effici...

Страница 2: ...WATER CIRCULATION 12 3A 7 ELECTRICAL SUPPLY 12 3A 8 MOUNTING ON A COMBUSTIBLE SURFACE 12 3A 9 TIMBER FRAMED BUILDINGS 12 3A 10 INHIBITORS 12 3A 11 SHOWERS 12 3A 12 DECLARATION OF CONFORMITY 12 SECTIO...

Страница 3: ...has been designed to meet and exceed the very latest standards in gas central heating technology and if cared for will give years of reliable use and efficiency Please therefore take some time to rea...

Страница 4: ...ounter clockwise to reduce the temperature range 40 C 80 C for standard central heating The automatic temperature control function SARA is factory disabled To enable this function please contact the V...

Страница 5: ...ntly hot enough it may be necessary to reduce the flow of water at the hot water outlet tap NOTE If the appliance fails to ignite during the ignition sequence it will enter a lockout condition Should...

Страница 6: ...position To select OFF mode move the selector switch in the upper position APPLIANCE STATUS LED AND FAULT CODES Fig 3 4 WHAT IF 5 SETTING THE VOK RA Advice for homeowners Please contact Vok ra Custome...

Страница 7: ...tained from Vok ra customer services When the product reaches the end of its life it should not be disposed of as solid urban waste but should be brought to a separated waste collection facility Easi...

Страница 8: ...n and the boiler will perform a three minute anti cycle timer delay When the request for heat has been satisfied the appliance pump and fan may continue to operate to dissipate any residual heat withi...

Страница 9: ...ght mm 792 Width mm 405 Depth mm 253 Dry weight kg 27 30 2 6 Clearances Easi Heat Plus 25C Easi Heat Plus 29C Sides 12mm Top 150mm from casing or 25mm above flue elbow whichever is applicable Bottom 1...

Страница 10: ...rature boilers 37 C and for other heaters 50 C return temperature at heater inlet Seasonal space heating energy efficiency class A Water heating energy efficiency class A Parameter Symbol Value Unit P...

Страница 11: ...lcony level 300 mm J From a surface or boundary facing the terminal 600 mm K From a terminal facing a terminal 1200 mm L From an opening in the car port into the building 1200 mm M Vertically from a t...

Страница 12: ...c directly from the mains supply must be provided see fig 8 This method of filling complies with the current Water Supply Water Fittings Regulations 1999 and Water Bylaws 2000 Scotland If an alternati...

Страница 13: ...s to be fitted on a wall of combustible material There is no requirement to protect the wall 3 9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building it shouldbefittedi...

Страница 14: ...LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make up vessel or tank mounted in a position at least 1 metre above the highest point in the system...

Страница 15: ...talsobemadetothemaximumlength see table below when additional bends are used Reduction for additional bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 metre 60 100 1 0 metre 80 12...

Страница 16: ...flue length see table below Reduction for bends Bend Reduction in maximum flue length for each bend 45 bend 1 0 metre 60 100 1 0 metre 80 125 90 bend 1 0 metre 60 100 1 0 metre 80 125 Vertical flue te...

Страница 17: ...no less than 20mm diameter to the outlet pipe and ensure it discharges in accord ance with building regulations or other rules in force 4 7 ELECTRICAL CONNECTIONS The boiler is supplied with a 2 metre...

Страница 18: ...to remove any installation debris from the boiler prior to lighting Refill the boiler and heating system as described in 5 3 5 5 PRE OPERATION CHECKS Before attempting the initial lighting of the appl...

Страница 19: ...this appliance including these instructions and explain the importance of keeping them in a safe place Explain to the user how to isolate the appliance from the gas water and electricity supplies and...

Страница 20: ...nd remove the pump outlet pipe A from the pump assembly combustion chamber connection Remove the expansion pipe locking pin B from the top of the pump assembly and withdraw the flexible pipe Locate an...

Страница 21: ...the reverse order Check and adjust burner pressure settings WARNING A GAS TIGHTNESS CHECK MUST BE CAR RIED OUT 6 13 ELECTRODES fig 27 Carry out component removal procedure as described in 6 4 Remove t...

Страница 22: ...e carefully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 Ensure all seals are in good condition taking care to ensure they are replaced correctly Replace in the reverse order e...

Страница 23: ...anger DisconnectthewiringtotheDHWflowswitch Slacken and unscrew the inlet connection Unscrew the nut E2 Lift the DHW flow switch housing from its seating If necessary remove the locking pin F2 from th...

Страница 24: ...e gas rate to 75 for a period of 15 minutes The speed of the fan and therefore the output of the boiler is determined by the temperature of the water sensed by the flow temperature sensor consequently...

Страница 25: ...tion analysis check can easily be carried out on the appliance via the test points located on the top of the applian ce see 7 3 Operate the boiler in combustion analysis mode see 7 3 1 Insert the flue...

Страница 26: ...o proceed to next stage If not see 7 7 4 connect test leads between the Neutral Earth connec tions at the appliance terminal strip The meter should read approximately 0 15Vac If so polarity is correct...

Страница 27: ...particular control Further guidance on the recom mended practice for the installation of external controls can be found in CHeSS HC5 HC6 www energyefficiency gov uk 8 4 VOK RA LOWER COVER MECHANICAL...

Страница 28: ...ic hot water temperature WPS Water pressure switch S E Spark electrode TSC2 Ignition transformer 3W 3 way motor F O H T Flow over heat thermostat FS Flue sensor FT Flow thermistor NTC RS Return thermi...

Страница 29: ...37 0 mbar 37 0 mbar Heating maximum gas rate kg hr 1 55 1 94 DHW maximum gas rate kg hr 1 94 2 25 Minimum gas rate kg hr 0 39 0 47 Injector size 3 8 mm 3 9 Silencer flange 27 mm 29 mm CO2 maximum outp...

Страница 30: ...TO MINIMUM RATE In accordance with section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES Is CO 350ppm and CO CO2 ratio less...

Страница 31: ...ommissioning checklist completed in full To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation To maintain the boiler guarantee...

Страница 32: ...terlock Provided ALL SYSTEMS The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer s instructions Yes What system cleaner was used What inhibitor was used Quantity...

Страница 33: ...gister No Record At max rate CO ppm AND CO At min rate Where Possible CO ppm AND CO Comments Signature SERVICE 04 Date Engineer name Company name Telephone No Gas safe register No Record At max rate C...

Страница 34: ......

Страница 35: ......

Страница 36: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited...

Отзывы: