Reset
A confirmation box pops up. After selecting "SURE", the lamp parameters return to
the factory settings.
When the power-on mode is selected, the lamp will wait for 30 seconds after the power
is turned on to allow the lamp to fully start. After the internal voltage is stable enough, the
reset procedure is started. If the on-site power capacity is stable, the power-on lighting
mode is recommended.
When the luminaire cannot correct the position, please first check whether the "optical
coupling correction" is turned off.
When the signal is unplugged, if the position of the luminaire is not output as expected,
please check the "Data Hold" setting first.
When setting the XY offset, after completing the setting, first control XY with the
maximum stroke to check that X Y will not hit the positioning rod or the housing after
setting.
6.
View Fixture Status of Lighting
Enter the page shown in Figure 6-6, you can view the information and real-time status
of the luminaire to know the use status of the luminaire. If the luminaire needs to after sale,
please provide the status information displayed on this page as a basis for judgment, as
shown in the following table:
Status information
Motor
information
Display information status of all motors and signals in the light
Hall-calibrated
Not displayed, indicating that the motor is not Hall-calibrated,
0 indicates that the motor is away from the calibration position,
and 1 indicates that the motor is at the calibration position
Status
Display motor reset completion status
X axis
Display real-time position value of X-axis optocoupler
feedback
Y axis
Display real-time position value of Y-axis optocoupler feedback
Optocoupler
Display the level status of two signals of X, Y axis optocoupler,
binary
Fault / status
recording
Display the last 8 fault records during lamp reset and operation. The fault records
will not be saved after power failure. The current power-on cycle is valid
Fault data
Total number of faults detected after power-on
12::03
Power-on time when the fault occurred, Unit is minute
Hall fault
Corresponding motor does not detect a valid Hall signal when
the motor is reset
Hall short
Corresponding to the valid Hall signal detected when the
motor is reset
Optocoupler
failure
No valid optocoupler signal detected when the corresponding
motor is reset
Out of step
Corresponding motor out of step during operation
Impact
positioning rod
Impact positioning rod when the motor is reset