Replace PFC module
Replace PFC electric
inductance
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Abnormal
Abnormal
Abnormal
Abnormal
Abnormal
PFC protection
Remove the obstruction,
clean and wash
Evenly coated the
coolant on IPM
module then install
the power module
Check whether the coolant is coated evenly, is
there any obstruction in installation position,
whether the screws on power module is tightened
Check whether the outdoor unit heat exchanger radiating
effect is good or not
Check whether the
3-core wire which
connected with
power module is
firmed or not
If there is no voltage
between PN then
replace PFC module
If there is no AC input
then check the circuit
of outdoor unit mainboard
circuit and fuse
5-core has problem
replace 5-core wire,
if there is no problem
replace PFC module
When compressor
start up, the voltage
of the compressor
can not arrive 380V,
then replace the
power module.
If there is 310V between PN but
when compressor start up, the
voltage is still 310V
After wired, then power on
to turn on the unit, check
whether there is AC
input between AC_L1
and AC-N1
Turn on, test voltage between PN, the voltage is
about 310 when compressor doesn’t start up, when
compressor start up normally, the voltage between
PN is about 380
If voltage between PN is normal, then to check
whether the input AC is abnormally fluctuated,
if the voltage fluctuation between procedure
is large or protective unit off momently when power
off, that is normal protection and unit off
Check PFC electric inductance white wire to yellow wire
and green wire, brown wire to yellow wire and green wire,
if there any restance value is 0, PFC electric inductance
short circuit
Under the condition of whole unit is powered off,
pull out the wire on AC_L1, AC_N1, then test
the resistance between AC_L1 and AC_N1,
if the value of resistance is 0, the PfC module
damaged
Turn the whole unit power off, use multi-meter to
test the DC voltage between power module P,N
and make sure if there is no voltage between PN,
pull out the wire on P, N then test the resistance
between P-N, if the value is 0, the module damaged
Temperature sensor F1, F2, F3,F4,F5 or cooling indicator extinguish 3s blink once, extinguish 3s blink twice, extinguish
3s and blink three times, extinguish 3s and blink four times, extinguish 3s and blink five times.
Processing method: Pls check whether the resistance value of corresponding sensor is normal or not;
Reliabily inserted or not; Lead wire damaged or not; Otherwise the sensor electric circuit or controller
have malfunction
Some of indoor unit haven’t display the troubleshooting or processing of malfunction;
Start up failure
Malfunction and phenomenon: After unit is turned on, indoor and outdoor units normally run, but there is no
cooling or heating, observe module of outdoor unit and discover the malfunction indicator firstly blinks 7 times,
after start up for many times later, the malfunction indicator blinks 6 times.
Processing method:
PFC protection HC or Heating indicator extinguish 3s blinks 6 times
Cause: Voltage change suddenly, poor radiating of PfC module, connection wire (PFC control wire)
between power module and PFC module is poor connected, over current ect.
Processing method:
Содержание ACP-24COFM70GEI
Страница 1: ...ACP 24COFM70GEI ACP 28COFM80GEI RoHS Service manual ENG ...
Страница 2: ......
Страница 5: ...Wrench Bolt Nut Unit mm Model ACP 24COFM70GEI ...
Страница 6: ...Wrench Bolt Nut Unit mm Model ACP 28COFM80GEI ...
Страница 11: ...Model ACP 24COFM70GEI ...
Страница 12: ...Model ACP 28COFM80GEI ...
Страница 21: ...7 Exploded View and Replacement Parts List 7 Exploded View and Replacement Parts List 1 ACP 24COFM70GEI ...
Страница 23: ...2 ACP 28COFM80GEI ...
Страница 35: ......
Страница 36: ......
Страница 37: ......