Set the Temperature T
Setting SLEEP function under HEAT mode, the preset temperature will automatically decrease by 1
after 1hour and
decrease by another 1 after 2 hours. Preset temperature will decrease by 2 in total within 2 hours. After that, the
unit will run at this preset temperature.
ć
Set the Temperature T
preset
3.5 Sleep Function
T
B
preset
B
T
B
preset
B
+2
ć
T
B
preset
B
+1
ć
1 hour
2 hours
Over 2 hours
T
B
preset
B
T
B
preset
B
-1
ć
T
B
preset
B
-2
ć
1 hour
2 hours
Over 2 hours
ć
No sleep function under fan mode and auto mode.
2.TIMER OFF can be set when the unit is running. Upon the time as set ,the unit will be stopped.The interval of time
setting is 0.5h and can be set within 0.5-24h in cycle.
1.TIMER ON can be set when the unit is stopped. Upon the time as set , the controller will run under preset mode. The
interval of time setting is 0.5h and can be set within 0.5-24h in cycle.
3.4 Timer Function
Indoor fan will automatically select high,middle or low fan speed according to ambient temp.During switchover, there is 3min
3.2 Auto Fan Speed of Indoor Fan
and 30s delay protection.
Setting SLEEP function under COOL or DRY mode, preset temperature will automatically rise by 1
after 1hour and rise
by another 1 after 2 hours. Preset temperature will rise by 2 in total within 2 hours. After that, the unit will run at
this preset temperature.
3. Other Control
3.1 Buzzer
When the unit is energized or receives signal from valid button or remote controller , the buzzer will give out a beep.
Stepping motor is controlled for startup and stop by swing button.It's swing is valid only when indoor fan is running.
3.3 Swing Control
As the right figure (Fig.2),A is close position , B is min. position and C is max. position.The angle between A and B is 64
degrees and betwwen B and C is 60 degrees).
1. Power the unit on for reset.Swing motor rotates for 126 degrees to close guide louver.
Swing angle:
2. Turn on the unit.If swing mode is not set,guide louer will turn to position C under
cooling,dry or fan mode, and turn to position B under heating mode.
3.During normal operation of indoor fan , blade swings between B and C under swing
mode and it stops at present position when swing is stopped.
4.If unit is stopped for malfunction or defrosting during operation of indoor
fan, blade stops at present position.
5. Blade stops at present position during blowing residual heat.
6. During anti cold air ,guide louver turns to max. postion C.
Fig.1
Stop control
Test button:
After energize, press this button, without pressing any other buttons or input of remote-control signal,into
3.4 Buttons
forced cooling mode according to nominal cooling condition P1.The unit will be in standby state in 5min.
standby state in 5min.Press this button again during test state to quit and into standby state.
Press this button for above 3s into forced heating mode according to nominal heating condition P1. The unit will be in
Auto button: If
press this button when the unit is off , the unit will run under auto mode.If press it when the unit is on,
the unit will stop running.