The indoor fan, once running at one speed, will not turn to another speed within 3.5 minutes.
6.2.4.8 Power supply for outdoor unit
The power supply for outdoor unit is turned on in AUTO, COOL, HEAT and Dehumidify mode under turn-on state.
The power supply for outdoor unit will delay 3 minutes to turn off under turn-off state or in the FAN mode under turn-on state.
6.2.4.9 Swing control
Use the SWING button of the wireless remote control to control SWING On and Off. Swing will only act when the indoor fan
is running. After power on, the swing motor will reset to close the air outlet vent;after the unit is turned on,if
the swing function has not set, the guide louver will first turn to D1, then turn back to L on standby under
cooling ; while under heating, it will stop at D1. If the swing function has set, the guide louver will swing
between L1 and D1.When the unit is turned off, the guide louver will swing back to 0 position.
When the unit is power on or receives remote control signal or the auto key be pressed,the buzzer will
6.2.4.10 Buzzer control
give out a beep.
6.2.4.11 Power-off memory function
Memory contents: Mode, Swing, Set temp, Set fan speed
and Timer
,etc. If the unit is running before de-energization,
after
re-energized, it needs at least 3 minutes for the outdoor unit be powered on by indoor unit, if the unit is stop before
de-energization, after re-energization, the
outdoor unit will be powered on by indoor unit immediately .
6.2.4.12 Delay Protection for Compressor
Under Cool, Dehumidify , Heat mode, there must be 3minutes delay befor each time the compressor starts.
6.2.4.13 Outdoor Unit Electric Heating Strip Control
If the outdoor ambient sensor is malfunction, the compressor heating strip and condenser heating strip will stop working
or work according to below logic control:
1). If the outdoor ambient temperature is lower and the compressor do not start, the compressor heating strip will work,
if the compressor is running or the compressor is not running but the outdoor ambient temperature is higher then the
specified value, the compressor heating strip will not work. If the compressor is not running and the outdoor ambient
temperature is within the specified value, the compressor heating strip will maintain its original operating status.
2). If the outdoor ambient temperature is lower , the condenser heating strip will work,if the outdoor ambient temperature
is higher then the specified value, the condenser heating strip will not work. If the outdoor ambient temperature is within
the specified value, the condenser heating strip will maintain its original operating status.
6.2.4.14 Outdoor Indicator
Meaning
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Red
Yellow Green
blink 1 time
blink 1 time
blink2times
blinking
blink2times
blink3times
blink3times
blink4times
blink5times
blink6times
blink7times
blink8times
blink4times
blink5times
blink6times
blink7times
blink8times
compressor starts
defrost
Antifreeze Protection
IPM Protection
overcurrent protection
overload stop protection
discharge stop protection
compressor overload
limited frequency(current)
malfunction
(Antifreeze)
outdoor Ttube senor
meeting the temp. for start
Communication normal
protection
dropped frequency
(discharge)
dropped frequency
limited frequency(overload)
malfunction
outdoor Tamb senor
malfunction
outdoor T
discharge
senor
Содержание ACP-09CH25GEI
Страница 1: ...ACP 09CH25GEI ACP 12CH35GEI RoHS Service manual ENG ...
Страница 2: ......
Страница 15: ...5 5 5 5 5 Electrical Diagram ...
Страница 16: ......
Страница 17: ...ACP 09CH25GEI ...
Страница 18: ... L 0 0 0 L 0 0 0 ACP 12CH35GEI ...
Страница 40: ...8 40 Exploded View and Components and Parts List Exploded View of Components and Parts of Indoor Unit ...
Страница 42: ...Exploded View of Components and Parts of Indoor Unit ...
Страница 44: ...Exploded View of Components and Parts of Indoor Unit ...
Страница 46: ...Exploded View of Components and Parts of Indoor Unit ...
Страница 48: ...Exploded View of Components and Parts of Outdoor Unit ...
Страница 50: ...Exploded View of Components and Parts of Outdoor Unit ...
Страница 52: ...Exploded View of Components and Parts of Outdoor Unit ...
Страница 54: ...Exploded View of Components and Parts of Outdoor Unit ...
Страница 56: ...Exploded View of Components and Parts of Outdoor Unit ...
Страница 58: ...Exploded View of Components and Parts of Outdoor Unit ...
Страница 68: ......
Страница 69: ......
Страница 70: ......