61
2.Compressor checking
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
DA108X1C-23EZ
DA130M1C-31FZ
DA250S2C-30MT
DA150S1C-20FZ
Blue - Red
1.1Ω
(20
℃
)
0.95Ω
(20
℃
)
0.5
5Ω
(20
℃
)
0.95Ω
(20
℃
)
Blue - Black
Red - Blue
3.IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a
digital tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
V
W
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
U
N
V
W
4.Indoor AC Fan Motor
Measure the resistance value of each winding by using the tester.