
22
6).When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low
side), disconnect the charge hose from the 3-
way valve’s service port immediately and turn off the air
conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a to rque of 18N.m.
Be sure to check for gas leakage.
6.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit
Procedure
1). Confirm that both the 2-way and 3-way valves are set to the opened position
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve
slightly to purge air from the charge hose for 5 seconds
and then close it quickly.
4). Set the 2-way valve to the close position.
Содержание ACP-09CH25AELI
Страница 1: ...ACP 09CH25AELI ACP 12CH35AELI ACP 18CH50AELI ACP 22CH65AELI Service manual ENG RoHS ...
Страница 2: ......
Страница 13: ...12 5 Wiring Diagram 5 1 Indoor Unit ACP 09CH25AELI ACP 12CH35AELI ACP 18CH50AELI ...
Страница 14: ...13 ACP 22CH65AELI ...
Страница 15: ...14 5 2 Outdoor Unit ACP 09CH25AELI ACP 12CH35AELI ACP 18CH50AELI ...
Страница 16: ...15 ACP 22CH65AELI ...
Страница 27: ...26 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...
Страница 64: ......
Страница 65: ......
Страница 66: ......
Страница 67: ......
Страница 68: ......