background image

INSTALLATION INSTRUCTIONS

Inground & Well Lights

Architectural Series

1162

IMPORTANT NOTE:

• 

Luminaire must be installed and grounded in accordance with the National Electrical Code (NEC) and local codes.

• 

All conduit entries must be sealed from moisture. Use appropriate sealing material on conduit fittings and conduit closure plugs.

• 

Luminaire is wet location listed and suitable for mounting ingrade.

• 

Suitable for all types of construction including poured concrete construction and in soil applications.

• 

Suitable for through wiring: max. of (4) No. 12 AWG conductors (plus ground) rated for 90°C.

MAINTENANCE: To assure proper operation and efficiency, lens must be kept clean and free of dirt, dust, leaves, trash and mineral deposits 
from water. A regular schedule maintenance program is recommended.
NOTE: Save these instructions for future reference.

1625 Surveyor Avenue • Simi Valley, CA 93063 • (805) 527-0987 • (800) 766-VISTA (8478)

FAX: (888) 670-VISTA (8478) • [email protected] • www.vistapro.com

Vista Professional Outdoor Lighting reserves the right to modify the design and/or construction of the fixture shown without further notification.

INGRADE SOIL INSTALLATION:
PRECAUTION:

  Luminaire  is  not  submersible  and  adequate  drainage 

must be provided during installation. It is recommended the luminaire be 
surrounded by 3” to 4” of pea gravel or sand to assure proper drainage. 
Top of luminaire must be above grade so rain and irrigation water will not 
accumulate for long periods of time.
1. To prevent electrical shock, turn main power off at circuit breaker.
2. Dig hole approximately 10” in diameter to a depth suitable to make top 
of temporary cover plate ¾” above grade (see fig. 1). Pea gravel or sand 
is recommended for seating the luminaire housing.
3. Connect conduit to housing. UL listed flexible conduit is recommended 
for in and out connections to ease fixture positioning.
4. Plug any unused NPT holes with closure plugs (provided).
5. Position fixture within hole and back-fill with pea gravel or sand.
6. Pull electrical supply wires (line in) through conduit and luminaire. Pull 
wires  and  make  a  6”  loop,  long  enough  for  manual  connections  with 
safety connectors (4” to 6” above the top rim of luminaire).

CONCRETE POUR INSTALLATION:
IMPORTANT NOTE:

 Temporary cover plate (purchased seperately)  and 

vinyl label must remain in place during housing installation.

PRECAUTION:

 Vinyl label and top of temporary cover plate must be at 

finished grade.
1. To prevent electrical shock, turn main power off at circuit breaker.
2. Dig hole approximately 10” in diameter to a depth suitable to make top 
of fixture flush grade (see fig. 2). Pea gravel or sand is recommended for 
seating the luminaire housing.
3. Connect conduit to housing. UL listed flexible conduit is recommended 
for in and out connections to ease fixture positioning.
4. Plug any unused NPT holes with closure plugs (provided).
5. Position fixture within hole and back-fill with pea gravel or sand.
6. To keep housing from floating, affix to rebar or grid-wire using standard 
masonry methods.
7. Pour concrete at least 2” thick. Trowel concrete so that it is even with 
vinyl label. Allow concrete to cure.
8. To  pull  supply  conductor  wiring,  remove  and  retain  vinyl  label  and 
temporary cover plate.
9. Pull electrical supply wires (line-in) through conduit and luminaire. Pull 
wires  and  make  a  6”  loop,  long  enough  for  manual  connections  with 
safety connectors (4” to 6” above the top rim of luminaire).
10. Stuff wire loop into housing and reinstall temporary cover plate and 
vinyl label.

FIXTURE COVER

FIXTURE HOUSING

GRAVEL/SAND

SOIL

FLEXIBLE CONDUIT

(RECOMMENDED)

RIGID CONDUIT

Figure 1

TEMPORY COVER PLATE/VINYL LABEL

FIXTURE HOUSING

CONCRETE

RIGID CONDUIT

FLEXIBLE CONDUIT

(RECOMMENDED)

CPF1 (Concrete Pour Form)

(Purchased Seperately)

Figure 2

VINYL LABEL

SCREWS

CPF-1

1164 HOUSING

Отзывы: