SPIRIT G XL 1-3KVA PF.09 - UPS www.visionups.com
26
interface. Press and hold the
function setting key
for more
than half a second(less than 2
seconds) at this time, the letters
“bPS” will stop flashing. The
“ON” (or OFF) below the bPS
will flash. Press and hold the
scroll key
for more than half a
second (less than 2 seconds) to
determine whether the BPS
function is enabled or disabled.
③ Confirm the BPS selecting
interface. After selecting ON or
OFF, press and hold the
function setting key
for more
than half a second (less than 2
seconds). Now, the BPS setting
function is completed and the
“ON” or “OFF” below the
“bPS” will light without
flashing.
④ If you choose “OFF”, then
go to step 7, otherwise go
ahead to step 5.
⑤ Set the BPS tolerance range.
Short
press
the
scroll
key
or for more than half a
second (shorter than 2 seconds)
to select the voltage range in
percentage.
+5%,+10%,+15%,+25%(default
is +25%) , then short press
function setting key
for
more than half a second
(shorter than 2 seconds)to
confirm the selection, then to
set the minus range
⑥ To set the minus range in the
same way.
⑦ After the minus range is
confirmed. Long press function
setting key
for more than 2
seconds to exit setting menu.