Chapter 3 Deployment
Manual VIPA TM-E
3-18
HB39E - TME - RE_900-1E640 - Rev. 09/11
To test the MPI connection a
Tag
is to be created. In a
Tag
memory areas
of you PLC are defined.
These storage areas may R/W accessed by the
Tag
.
•
To establish a Tag open at the Web page the page "Tag setup" and
click at "Create new Tag ...".
•
Enter the following parameters:
Tag name
:
Test
Server name
: S73&400
Topic name
:
A
Address
:
MW0
Type
:
Boolean
•
Otherwise leave the standard setting and click at [Add/Update...].
•
Switch with
Main menu
>
View I/O
to the Tag list.
•
Enter a new value for the Tag "Test" and click at [Update]. Now this
value is set and may be transferred to the CPU with clicking to [Update]
in the headline.
•
If the new value is accepted by the CPU, so the communication between
the TM-E module and the CPU is secured.
Test PLC
connection
Access via View I/O