As soon as the parameter data do not fit to the sequence
of the modules on the System SLIO bus, the DeviceNet
coupler goes to an error state and signals this with its
status LEDs.
Due to the system, modules which are not yet parameter-
ized are supplied with their default parameters as soon as
you start a read access from your configuration tool.
4.2.3 Accessing diagnostics data
The DeviceNet coupler only supports passive diagnostics. This
means for the diagnostics that there is no alarm activation on module
side necessary. You have to request the diagnostics. For this select
in your configuration tool the diagnostics data of the corresponding
DeviceNet-Slot. Then you get the diagnostics data of this module as
byte sequence. Information concerning structure of the diagnostics
data may be found in the description of the corresponding System
SLIO module.
If this is supported by your configuration tool, via the corresponding
DeviceNet-Slot you may get more information about the current ver-
sion of your System SLIO.
System SLIO DeviceNet coupler - Class Code: 100 (64h)
No. Name
Information
Format
Example
1
DeviceName
Name of the
device
String
VIPA
053-1DN00
2
HwVersion
Hardware ver-
sion
String
02
3
SwVersion
Software ver-
sion
String
V101
4
SerialNumber
Serial number
Unsigned32,
String
00000205
5
FpgaVersion
FPGA version
Unsigned16,
String
V208
6
MxFile
Mx file
String
MX000053.101
7
ProductVersion Product version String
01V01.00
8
OrderCode
Order no.
String
053-1DN00
Accessing firmware
information
VIPA System SLIO IM 053DN
Deployment
Accessing the System SLIO > Accessing diagnostics data
HB300 | IM | 053-1DN00 | GB | 15-33