n

In special use cases you should appoint special EMC actions.
– Consider to wire all inductivities with erase links.
– Please consider luminescent lamps can influence signal lines.

n

Create a homogeneous reference potential and ground all elec-

trical operating supplies when possible.
– Please take care for the targeted employment of the grounding

actions. The grounding of the PLC serves for protection and

functionality activity.

– Connect installation parts and cabinets with your PLC in star

topology with the isolation/protected earth conductor system.

So you avoid ground loops.

– If there are potential differences between installation parts and

cabinets, lay sufficiently dimensioned potential compensation

lines.

Electrical, magnetically and electromagnetic interference fields are

weakened by means of an isolation, one talks of absorption. Via the

isolation rail, that is connected conductive with the rack, interference

currents are shunt via cable isolation to the ground. Here you have to

make sure, that the connection to the protected earth conductor is

impedance-low, because otherwise the interference currents may

appear as interference cause.
When isolating cables you have to regard the following:

n

If possible, use only cables with isolation tangle.

n

The hiding power of the isolation should be higher than 80%.

n

Normally you should always lay the isolation of cables on both

sides. Only by means of the both-sided connection of the isolation

you achieve high quality interference suppression in the higher

frequency area. Only as exception you may also lay the isolation

one-sided. Then you only achieve the absorption of the lower fre-

quencies. A one-sided isolation connection may be convenient, if:
– the conduction of a potential compensating line is not possible.
– analog signals (some mV respectively µA) are transferred.
– foil isolations (static isolations) are used.

n

With data lines always use metallic or metallised plugs for serial

couplings. Fix the isolation of the data line at the plug rack. Do not

lay the isolation on the PIN 1 of the plug bar!

n

At stationary operation it is convenient to strip the insulated cable

interruption free and lay it on the isolation/protected earth con-

ductor line.

n

To fix the isolation tangles use cable clamps out of metal. The

clamps must clasp the isolation extensively and have well contact.

n

Lay the isolation on an isolation rail directly after the entry of the

cable in the cabinet. Lead the isolation further on to your PLC and

don't lay it on there again!

CAUTION!
Please regard at installation!

At potential differences between the grounding points,

there may be a compensation current via the isolation con-

nected at both sides.
Remedy: Potential compensation line

Isolation of conductors

 VIPA System SLIO IM 053DN

Basics and Assembly

Installation guidelines

HB300 | IM | 053-1DN00 | GB | 15-33

 

29

Содержание System SLIO IM 053DN

Страница 1: ...IM 053 1DN00 Manual HB300 IM 053 1DN00 GB 15 33 VIPA System SLIO IM 053DN...

Страница 2: ...053 1DN00_000_IM 053DN 2 GB 2015 VIPA GmbH Ohmstr 4 91074 Herzogenaurach Telephone 49 9132 744 0 Fax 49 9132 744 1864 Email info vipa com Internet www vipa com...

Страница 3: ...ata 30 3 Hardware description 32 3 1 Properties 32 3 2 Structure 33 3 2 1 Interfaces 33 3 2 2 Address switch 34 3 2 3 LEDs 36 3 3 Technical data 37 4 Deployment 39 4 1 Basics DeviceNet 39 4 2 Accessin...

Страница 4: ...y effort has been made to ensure that the information contained in this document was complete and accurate at the time of publishing Nevertheless the authors retain the right to modify the information...

Страница 5: ...bH Ohmstra e 4 91074 Herzogenaurach Germany Telefax 49 9132 744 1204 EMail documentation vipa de Contact your local VIPA Customer Service Organization representa tive if you encounter problems with th...

Страница 6: ...Safety information The System SLIO is constructed and produced for n communication and process control n general control and automation applications n industrial applications n operation within the e...

Страница 7: ...out when the system has been disconnected from power Installation and hardware modifications only by prop erly trained personnel The national rules and regulations of the respective country must be s...

Страница 8: ...have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the conse quent implementation of protection devices and metic...

Страница 9: ...ay be replaced with standing wiring By deploy ment of the power modules in contrasting colours within the system further isolated areas may be defined for the DC 24V power section supply respectively...

Страница 10: ...one casing With the bus interface you get access to a subordinated bus system As head module via the integrated power module for power supply the bus interface is supplied as well as the electronic o...

Страница 11: ...ctive module may be exchanged for a functional module with standing installation At the front side there are LEDs for status indication For simple wiring each module shows a corresponding connection d...

Страница 12: ...10mm x 3mm to connect cable shields Shield bus car riers shield bus and shield fixings are not in the scope of delivery They are only available as accessories The shield bus carrier is mounted undern...

Страница 13: ...o fix the assignment of electronic and terminal module Here coding pins order number 000 0AC00 from VIPA can be used The coding pin consists of a coding jack and a coding plug By combining electronic...

Страница 14: ...Dimensions in mm Dimensions bus cou pler Dimensions periphery module Dimensions electronic module VIPA System SLIO IM 053DN Basics and Assembly Dimensions HB300 IM 053 1DN00 GB 15 33 14...

Страница 15: ...e electronic module may be pulled forward after pressing the unlocking lever at the lower side of the module For installation plug the electronic module guided by the strips at the lower side until th...

Страница 16: ...he same coding Even with an existing coding on the terminal module you can plug an electronic module without coding The user is responsible for the correct usage of the coding pins VIPA assumes no lia...

Страница 17: ...er 1 Start at the left side with the head module e g bus coupler For this turn both locking lever upwards put the head module to the mounting rail and turn both locking lever downward 2 Before mountin...

Страница 18: ...rotect the backplane bus connectors at the last module you have to mount the bus cover now Mounting the bus cover at a clamp module If the last module is a clamp module for adaptation the upper part o...

Страница 19: ...us coupler or a group of modules for mounting reasons you have always to remove the electronic module of the just mounted right module After the mounting it may be plugged again Exchange of an electro...

Страница 20: ...rd 5 For mounting turn the locking lever of the module to be mounted upwards 6 To mount the module put it to the gap between the both modules and push it guided by the stripes at both sides to the mou...

Страница 21: ...urn all the locking lever of the head module to be exchanged upwards 4 Pull the head module forward 5 For mounting turn all the locking lever of the head module to be mounted upwards 6 To mount the he...

Страница 22: ...n all the locking lever of the module group to be exchanged upwards 4 Pull the module group forward 5 For mounting turn all the locking lever of the module group to be mounted upwards 6 To mount the m...

Страница 23: ...AC 30V DC Imax 10A Cross section 0 08 1 5mm2 AWG 28 16 Stripping length 10mm 1 Insert a suited screwdriver at an angel into the square opening as shown Press and hold the screwdriver in the opposite d...

Страница 24: ...supply 5 not connected 6 DC 24V I DC 24V for power section supply 7 0V I GND for power section supply 8 Sys 0V I GND for electronic section supply I Input CAUTION Since the power section supply is no...

Страница 25: ...as the sum current does not exceed 3A With a sum current greater than 3A the LEDs may not be activated Here the power module with the order number 007 1AB10 is to be placed between the peripheral mod...

Страница 26: ...cable shields The shield bus carrier is mounted underneath the terminal of the ter minal module With a flat mounting rail for adaption to a flat mounting rail you may remove the spacer of the shield...

Страница 27: ...is placed which does not corre spond to the configured module Remedy Match configuration and hardware structure Behaviour After PowerON all of the RUN LEDs up to the defective module are flashing With...

Страница 28: ...arts when installing your components Install a central connection between the ground and the pro tected earth conductor system Connect all inactive metal extensive and impedance low Please try not to...

Страница 29: ...rmally you should always lay the isolation of cables on both sides Only by means of the both sided connection of the isolation you achieve high quality interference suppression in the higher frequency...

Страница 30: ...s level electrically isolated Insulation resistance Insulation voltage to reference earth Inputs outputs AC DC 50V test voltage AC 500V Protective measures against short circuit Environmental conditio...

Страница 31: ...N 61000 4 3 HF field immunity casing 80MHz 1000MHz 10V m 80 AM 1kHz 1 4GHz 2 0GHz 3V m 80 AM 1kHz 2GHz 2 7GHz 1V m 80 AM 1kHz EN 61000 4 6 HF conducted 150kHz 80MHz 10V 80 AM 1kHz EN 61000 4 4 Burst d...

Страница 32: ...DeviceNet address 0 63 Transfer rate for the DeviceNet coupler n Supports all baud transfer rates 125 250 and 500kbit s n Configuration of up to 64 peripheral modules n max 255 byte in output data n C...

Страница 33: ...section supply 8 Power module 9 DeviceNet connector bus interface 10 Unlocking lever power module 11 Bus interface 12 Terminal power module 13 Address switch 3 2 1 Interfaces CAUTION Bus interface an...

Страница 34: ...ted on the front of the module n The shield is to be connected to pin 3 DR and grounded at one suited place within its network n You receive a suited plug from VIPA with the order number VIPA 000 0DN0...

Страница 35: ...iceNet address No Description Example Setting 1 Configuration 0 1 2 32 35 Address 35 2 20 1 1 3 21 2 1 4 22 4 0 5 23 8 0 6 24 16 0 7 25 32 1 8 Auto configuration 0 1 Auto configu ration On start up wi...

Страница 36: ...Fuse electronic section supply defective on off not relevant X LED Description PWR green Bus interface is power supplied SF red Error on DeviceNet or System SLIO bus RD green Status System SLIO bus BA...

Страница 37: ...gnostics Status display yes Interrupts Process alarm Diagnostic interrupt Diagnostic functions Diagnostics information read out possible Supply voltage display green LED Service Indicator Group error...

Страница 38: ...Byte Number of TxPDOs max Number of RxPDOs max Housing Material PPE PPE GF10 Mounting Profile rail 35 mm Mechanical data Dimensions WxHxD 48 5 mm x 109 mm x 76 5 mm Weight 155 g Environmental conditi...

Страница 39: ...n the network together with an identifier All devices requiring data listen for messages When devices recognize a suitable identifier they act and consume the respective data n DeviceNet carries two t...

Страница 40: ...tive means that the successful station participating in the arbitration doesn t need to re send its message The most important station is selected auto matically when multiple stations access the bus...

Страница 41: ...tivate the Auto configuration switch the DIP switch A of the address switch to 1 before switching on the power supply To store the module configuration switch the DIP switch A of the address switch to...

Страница 42: ...put bytes is to be preset Information concerning the I O allocation of a module may be found in the corresponding manual n The position offset of the input respectively output bytes within the input r...

Страница 43: ...h attached Value n The parameters themselves are to be separated by a blank n There are only parameter strings with lower case supported Depending on the type hexadecimal decimal or binary values may...

Страница 44: ...as byte sequence Information concerning structure of the diagnostics data may be found in the description of the corresponding System SLIO module If this is supported by your configuration tool via th...

Страница 45: ...0 x00 x00 x00 4x000020EB 4 3 Transfer rate and DeviceNet address With PowerOFF there is the possibility to specify the Transfer rate respectively the DeviceNet address and then to activate these with...

Страница 46: ...dress All stations on the bus must be uniquely identified by means of an ID address The setting of the DeviceNet address happens with the fol lowing proceeding 1 Turn off the power supply 2 Set switch...

Страница 47: ...as well as during opera tion The result of the diagnostics is determined by the combination of the different LEDs and the current operating mode Here the RD LED corresponds to the System SLIO backplan...

Страница 48: ...E X Configuration error System SLIO bus n The number of real modules at the bus differs to the configured modules n The module type of at least one module differs to the type of the configured module...

Отзывы: