6.
Activate the System SLIO DeviceNet coupler IM 053DN in the
scan list.
7.
Start the DeviceNet scanner.
ð
When the DeviceNet scanner has been configured, the input
and output modules are accessible via the configured
addresses.
4.2.2 Accessing parameter data
The System SLIO modules may also be parameterized by the config-
uration tool. For this your DeviceNet couple must be connected active
at the bus. For parameterization and for the access to the diagnostics
data the data type SHORT_STRING is used. Please consider that
your DeviceNet manager supports this type of data. In your configura-
tion tool you may parameterize your module by means of a character
string. You also may transfer the current parameters from the module
into your configuration tool to adapt them and write them back to the
module.
n
Each DeviceNet-Slot is separately be parameterized with a char-
acter string.
n
Within the character string each parameter consists of a Type with
attached Value.
n
The parameters themselves are to be separated by a blank.
n
There are only parameter strings with lower case supported.
Depending on the type hexadecimal, decimal or binary values may be
preset:
Type Meaning
Value as
Range of values
Character
string
Example
number
x
1byte
hexadecimal
00h ... FFh
x
hh
xA2
2x
2byte
hexadecimal
0000h ... FFFFh
2x
hhhh
2x7FFF
4x
4Byte
hexadecimal
00000000h ...
FFFFFFFFh
4x
hhhhhhhh
4x7FFF80C0
+
1byte
decimal positive
0 ... 255
+
ddd
+255
2+
2byte
decimal positive
0 ... 65535
2+
ddddd
2+65535
4+
4byte
decimal positive
0 ... 4294967295
4+
dddddddddd
4+4294967295
-
1byte
decimal negative -128 ... -1
-
ddd
-128
2-
2byte
decimal negative -32768 ... -1
2-
ddddd
2-32768
4-
4byte
decimal negative -2147483648 ... -1
4-
dddddddddd
4-2147483648
b
1byte
binary
00000000 ...
11111111
b
bbbbbbbb
b10100101
The analog module 031-1BB90 has 18byte parameter data. For the
parameterization with default values this results in the following string:
x00 x00 x00 x00 x00 x02 xC1 x02 2x7FFF 2x8000 xC1 x02 2x7FFF
2x8000
Rules for the parameter-
ization
Example
VIPA System SLIO IM 053DN
Deployment
Accessing the System SLIO > Accessing parameter data
HB300 | IM | 053-1DN00 | GB | 15-33