Manual VIPA System SLIO
Chapter 3 Digital Output
HB300E - SM - Rev. 09/38
3-3
For wires with a cross section of 0.08mm
2
up to 2.5mm
2
.
2
6
3
7
4
8
1
5
1
2
3
4
5
6
7
8
2
6
3
7
4
8
1
5
DO
DC24V
0V
0
1
Pos.
Function
Type Description
1
DO 0
O
Digital output DO 0
2
DC 24V
O
DC 24V
3
0V
O
GND for actuator
4 ---
--- not
connected
5
DO 1
O
Digital output DO 1
6
DC 24V
O
DC 24V
7
0V
O
GND for actuator
8 ---
--- not
connected
O: Output
Data
VIPA 022-1BB00
Number of outputs
2
Nominal load voltage
DC 24V (20.4 ... 28.8V)
Current consumption
5V
24V
55mA
5mA + load
Isolation
500Veff (field voltage to the bus)
Load
resistive, inductive or lamp load
Output current (per channel)
max. 0.5A (short-circuit proofed)
Switch rate
for resistive load
for ind. load (IEC947-5-1, DC13)
for lamp load
max. 1kHz
max. 0.5Hz
max. 10Hz
Module ID
0101 AF90
Bit-width in the process image
2bits
Configurable no
Pin assignment
Technical data
Содержание 021-1BB00
Страница 1: ...Manual VIPA System SLIO Signal modules SM Order No VIPA HB300E_SM Rev 09 38...
Страница 2: ...L...
Страница 6: ...Contents Manual VIPA System SLIO ii HB300E SM Rev 09 38...
Страница 26: ...Chapter 1 Basics and Assembly Manual VIPA System SLIO 1 18 HB300E SM Rev 09 38...
Страница 36: ...Chapter 2 Digital Input Manual VIPA System SLIO 2 10 HB300E SM Rev 09 38...
Страница 44: ...Chapter 3 Digital Output Manual VIPA System SLIO 3 8 HB300E SM Rev 09 38...
Страница 102: ...Chapter 5 Analog Output Manual VIPA System SLIO 5 24 HB300E SM Rev 09 38...