Manual VIPA System SLIO
Chapter 4 Analog Input
HB300E - SM - Rev. 09/38
4-7
... continue RTD
Measuring range (function number)
Measuring value
Signal range
Range
70.55
Ω
32511
overrange
0 ... 60
Ω
0 ... 27648
nominal range
2 wire: 0 ... 60
Ω
(D0h)
--- --- underrange
705.5
Ω
32511
overrange
0 ... 600
Ω
0 ... 27648
nominal range
2 wire: 0 ... 600
Ω
(D1h)
--- --- underrange
3528
Ω
32511
overrange
0 ... 3000
Ω
0 ... 27648
nominal range
2 wire: 0 ... 3000
Ω
(D2h)
--- --- underrange
70.55
Ω
32511
overrange
0 ... 60
Ω
0 ... 27648
nominal range
3 wire: 0 ... 60
Ω
(D8h)
--- --- underrange
705.5
Ω
32511
overrange
0 ... 600
Ω
0 ... 27648
nominal range
3 wire: 0 ... 600
Ω
(D9h)
--- --- underrange
3528
Ω
32511
overrange
0 ... 3000
Ω
0 ... 27648
nominal range
3 wire: 0 ... 3000
Ω
(DAh)
--- --- underrange
70.55
Ω
32511
overrange
0 ... 60
Ω
0 ... 27648
nominal range
4 wire: 0 ... 60
Ω
(E0h)
--- --- underrange
705.5
Ω
32511
overrange
0 ... 600
Ω
0 ... 27648
nominal range
4 wire: 0 ... 600
Ω
(E1h)
--- --- underrange
3528
Ω
32511
overrange
0 ... 3000
Ω
0 ... 27648
nominal range
4 wire: 0 ... 3000
Ω
(E2h)
--- --- underrange
Содержание 021-1BB00
Страница 1: ...Manual VIPA System SLIO Signal modules SM Order No VIPA HB300E_SM Rev 09 38...
Страница 2: ...L...
Страница 6: ...Contents Manual VIPA System SLIO ii HB300E SM Rev 09 38...
Страница 26: ...Chapter 1 Basics and Assembly Manual VIPA System SLIO 1 18 HB300E SM Rev 09 38...
Страница 36: ...Chapter 2 Digital Input Manual VIPA System SLIO 2 10 HB300E SM Rev 09 38...
Страница 44: ...Chapter 3 Digital Output Manual VIPA System SLIO 3 8 HB300E SM Rev 09 38...
Страница 102: ...Chapter 5 Analog Output Manual VIPA System SLIO 5 24 HB300E SM Rev 09 38...