1) Place the condensing units WM-252~652SCUR in a properly ventilated location.
Otherwise, heat exhausted by the condensing unit will build up and the cooling
system will not operate properly.
2) Condensing unit shall be elevated to avoid possible flooding and shaded from
direct sun. It shall not be exposed to temperatures higher than 110 °F or lower
than 50 °F.
3) Leave minimum 5 ft clearance for the air exhaust side and leave minimum 1 foot
clearance for the air intake side.
5. Refrigeration Piping and Leak Testing
NOTE
The line connector sizes of liquid filter and indicator, the valve connector
sizes of condensing unit or the line connector sizes of evaporator unit
may not be the same as the listed refrigeration line sizes.
If the condensing unit is installed above the evaporator unit, use the
suction line one size smaller.
Expansion and solenoid valves have been installed on the liquid line in
the evaporator unit.
The line sizes and refrigerant charges are listed as follows.
Model No.
Equivalent
Line Set
Liquid
Line
Suction
Line
Drain
Line
Recommended
Initial Charge
WM-2520SSV
WM-2520SSV-LA
<= 75 FT
1/4” OD
3/8” OD
3/4” MPT
R134a / 19 OZ
WM-4520SSV
WM-4520SSV-LA
<= 75 FT
1/4” OD
1/2” OD
3/4” MPT
R134a / 26 OZ
WM-6520SSV
WM-6520SSV-LA
<= 75 FT
1/4” OD
1/2” OD
3/4” MPT
R134a / 32 OZ
1) The piping starts from condensing
unit’s receiver discharge valve liquid
filter liquid indicator liquid line to evaporator
unit’s liquid line connection
(assembled with solenoid valve and expansion valve)
suction line
connection
insulated suction line to condensing
unit’s suction valve.
2) If the line set exceeds 75 ft long, use both inverted U trap and suction
accumulator to prevent liquid from flooding back to the compressor.
3) If the condensing unit is located below the evaporator unit, use inverted U trap
to prevent liquid from flooding back to the compressor. If the elevation difference
is more than 10 ft, use both inverted U trap and suction accumulator.
4) If the condensing unit is located more than 10 ft above the evaporator unit, use
U trap to aid oil returning to the compressor.
5) Complete pipe brazing, check solenoid valve and expansion valve restrictions
and perform leak testing.
6) Hook up the drain line and check if water drains.
6. Connecting Electrical Wires
Содержание WINE-MATE WM-2520SSV
Страница 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 252 652SFCV Evaporator Unit...
Страница 18: ...17 Fig 5 WM 252 452SCUR Condensing Unit Fig 6 WM 652SCUR Condensing Unit...
Страница 28: ...27 Fig 17 WM 2520 4520SSV LA Electrical Wiring Diagram Fig 18 WM 6520SSV Electrical Wiring Diagram...
Страница 29: ...28 Fig 19 WM 6520SSV LA Electrical Wiring Diagram...