2. Temperature Controller and Air Probe Location
1) The temperature controller can be mounted either inside or outside the wine
cellar, but the air probe must be located inside the wine cellar or the return
duct.
2) The air probe shall be located in the wine cellar 5 ft above the floor or the air
return area, but it shall not be located in the air supply area or other areas where
air is not circulated.
3) Air probe can be pulled out of the temperature controller up to 5 ft. If additional
wires are necessary, 18 gauge wires may be used to extend the air probe.
3. Evaporator Unit Location
1) The WM-252~652SFCV evaporator units should be installed for corner mount
with the supply air on the top and return air on the bottom.
2) Air supply shall be unobstructed minimum
12”; air return shall be unobstructed
minimum
6”.
3) A grille can be used to cover
the supply and return with 0~2” clearance; or a 2-
3 ft long duct can be added at the supply and return.
4) There is a gravity drain system, so the unit shall be installed level or with a slight
slope downward the drain connection and the drain line shall be installed slope
down toward the drain.
If rise-up is necessary, a condensation pump must be used.
4. Condensing Unit Location
CAUTION
Low ambient condition kit is required if the temperature will be
below 50
°
F.
Содержание WINE-MATE WM-2520SSV
Страница 17: ...16 Fig 3 Temperature Controller 4 5 L X 4 5 W X 3 75H Fig 4 WM 252 652SFCV Evaporator Unit...
Страница 18: ...17 Fig 5 WM 252 452SCUR Condensing Unit Fig 6 WM 652SCUR Condensing Unit...
Страница 28: ...27 Fig 17 WM 2520 4520SSV LA Electrical Wiring Diagram Fig 18 WM 6520SSV Electrical Wiring Diagram...
Страница 29: ...28 Fig 19 WM 6520SSV LA Electrical Wiring Diagram...