Fig. 7 Temperature Controller (4.25”L X 3.75D X 4.25”H)

 

 

2. Evaporator Unit Installation 

 

1)  WM-25~85SFCH evaporator units can be installed outside a wine cellar. It 

shall not be exposed to temperatures higher than 85 °F. 

2)  Air supply shall be unobstructed minimum 12” for a direct blow installation; 

leave 2” clearance for a deflector installation; air return shall be unobstructed 
minimum 6”. 

3)  Secure the ducts with conduits to the cellar exterior walls and make sure they 

are not curled, twisted, bent and clogged. 

4)  There is a gravity drain system used, so the unit shall be installed level or with 

a slight slope downward the drain connection and the drain line shall be 
installed slope down toward the drain. If rise-up is needed, a condensation 
pump must be used. 
 

3.  Condensing Unit Installation 
 

1)  Condensing unit shall be elevated to avoid possible flooding and shaded from 

direct sun. The location shall be adequately ventilated and shall not be 
subject to freezing temperatures. 

2) Water must be supplied to WM-250~850SCU-WC at all times during 

operation, with the maximum outlet temperature of 120 °F. A sufficient 
amount of water must be provided for constant head pressure and proper 
cooling, but excessive water flow will cause the unit working inefficiently. 

3)  The maximum permissible water pressure is 150 PSIG. If water pressure is 

excessive, a pressure reducing valve must be used to reduce the water 
pressure. 

4)  If a water pump is used, install it before the water inlet so that the condenser 

cooling water is fed from the discharge side of the pump. 

5)  Service valve operation 

1 - Process & Manometer 
2 – Receiver Discharge or Compressor Suction  
3 – Liquid Line or Suction Line 
4 - Pressure Control 

Содержание Wine-Mate WM-2500SSHWC

Страница 1: ...uct Split Cooling System Installation Operation Care Manual WM 2500SSHWC WM 4500SSHWC WM 6500SSHWC WM 8500SSHWC w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he...

Страница 2: ...1 Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 20 AMP circuit for WM 2500SSHWC and 30 AMP for WM 4500 8500SSHWC are required...

Страница 3: ...le of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Electrical Wirings 24 Customer Support 26 Warran...

Страница 4: ...erature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer...

Страница 5: ...se and compressor vibration are isolated SSHWC condensing units are water cooled so that exhaust ventilation is not needed SSHWC evaporator units are designed to provide chilled air to wine a cellar t...

Страница 6: ...x18 2500 220 250 R134a 115V 60HZ 0 8A 115V 60HZ 5 7A 35 40 WM 4500SSHWC WM 45SFCH 25 125x22 875 x16 375 18 WM 450SCU WC 24x18x18 4500 380 1000 R134a 115V 60HZ 1 8A 115V 60HZ 6 9A 45 60 WM 6500SSHWC WM...

Страница 7: ...o lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock t...

Страница 8: ...etting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setti...

Страница 9: ...lar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 9 How to set low cellar temper...

Страница 10: ...elay min 1 ot probe calibration 0 US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative...

Страница 11: ...aning To clear any sediment that may accumulate the water regulating valve may be manually flushed Insert screwdrivers under both sides of the valve spring guide and lift upwards to flush 2 Condensate...

Страница 12: ...temperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it...

Страница 13: ...a Check compressor windings start relay and overload protector b Check water flow c Call service for removing refrigerant d Call service for information 9 Evaporator fan running too long a Post compre...

Страница 14: ...ture setting 14 Circuit tripping a Incorrect fuse or breaker b Incorrect wirings c Failed components a Check for proper fuse or breaker b Check for wirings and connections c Call service 15 Noisy oper...

Страница 15: ...ndensing unit and evaporator unit are connected by a liquid line and an insulated suction line that are supplied by the installer These lines must be properly sized for the distance between the two un...

Страница 16: ...15 CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 25 85SFCH Evaporator Unit...

Страница 17: ...16 Fig 4 WM 250 850SCU WC Condensing Unit Fig 5 Liquid Filter Fig 6 Liquid Indicator...

Страница 18: ...p must be used 3 Condensing Unit Installation 1 Condensing unit shall be elevated to avoid possible flooding and shaded from direct sun The location shall be adequately ventilated and shall not be sub...

Страница 19: ...WM 4500SSHWC WM 450SCU WC 0 4 3 8 FPT 1 2 ODF SOLDER 0 2 WM 6500SSHWC WM 650SCU WC 0 6 3 8 FPT 1 2 ODF SOLDER 0 2 WM 8500SSHWC WM 850SCU WC 0 8 3 8 FPT 1 2 ODF SOLDER 0 4 4 Temperature Controller and...

Страница 20: ...on sizes of evaporator unit are not necessary the same as the listed refrigeration line sizes If the condensing unit is installed above the evaporator unit use the suction line one listed size smaller...

Страница 21: ...all electrical components using the wiring diagrams in accordance with all state and local codes 8 Evacuating Charging and Starting the system CAUTION Always use the superheat and subcooling pressure...

Страница 22: ...an Speed Control 3 The subcooling at the condensing unit shall be around 10 F The charge may be complete when there are no more bubbles forming in the liquid indicator 4 Head pressure is maintained co...

Страница 23: ...eat and zero subcooling k High suction pressure and low head pressure Low superheat and low subcooling l High suction pressure and high head pressure Low superheat and high subcooling m High to normal...

Страница 24: ...high subcooling evaporator iced t Evaporator restricted u Expansion valve restricted v Both evaporator and condenser restricted liquid and suction lines connected wrong w Liquid line restricted befor...

Страница 25: ...rical Wiring Diagrams CAUTION Hidden lines are the field wirings Use minimum 14 gauge wires for power lines A safety switch is always recommended for the condensing unit Fig 14 WM 2500 4500SSHWC Wirin...

Страница 26: ...25 Fig 15 WM 6500 8500SSHWC Electrical Wiring Diagram...

Страница 27: ...6 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp co...

Страница 28: ...ties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products...

Страница 29: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...

Отзывы: