- 13 -
inside ducts
b. Continually running not stopping
c. Too cold supply air
b.
raise temperature setting or
increase defrost cycle
c.
Increase air flow or raise
temperature setting
13.Condensate
outside
ducts
a. Duct not insulated
b. High humidity
c. Too cold supply
a. Check for insulation
b. Use
dehumidifier
c.
Increase air flow or raise
temperature setting
14.Circuit
tripping
a. Incorrect fuse or breaker
b. Incorrect
wirings
c. Failed
components
a. Check for proper fuse or breaker
b. Check for wirings and connections
c. Call service
15.Noisy
operation
a. Mounting area not firm
b. Loose
parts
c. Compressor overloaded due to
improper condenser cooling
d. Defective
components
a. Add support to improve installation
b.
Check fan blades, bearings,
washers, tubing contact and loose
screws.
c. Check water flow
d. Call service for checking internal
loose, inadequate lubrication and
incorrect wirings