- 18 -
Fig. 7 Liquid Filter Fig. 8 Liquid Indicator
Fig. 9 Temperature Controller (4.25”L X 3.75D X 4.25”H)
2. Evaporator Unit Installation
1) The WM-25~85SFCD evaporator units shall be installed for ceiling mount with
the supply air toward horizontal and return air on the bottom.
2) Air supply shall be unobstructed minimum 12” for a direct blow installation;
leave 2” clearance for a deflector installation; air return shall be unobstructed
minimum 6”.
3) The units may be recessed into the ceiling with short curved rectangular ducts;
CFM must be checked.
4) There is a gravity drain system used, so the unit shall be installed level or with
a slight slope downward the drain connection and the drain line shall be
installed slope down toward the drain. If rise-up is needed, a condensation
pump must be used.
3. Condensing Unit Installation
CAUTION:
Low ambient condition kit is required if the installation area will be below
50
°
F.
If the condensing unit is equipped with a low ambient condition kit,
do not turn on the compressor until the condensing unit has been powered
for minimum 12 hours.