The line connection sizes of liquid filter & indicator, the valve connection 
sizes of condensing unit and the line connection sizes of evaporator unit 
are not necessary the same as the listed refrigeration line sizes. 

 

If  the  condensing  unit  is  installed  above  the  evaporator  unit,  use  the 
suction line one listed size smaller. 

 

Expansion and solenoid valves have been installed on the liquid line in 
the evaporator unit. 
 

1)  The  installation  order  starts  from  condensing  unit  (including  receiver  and 

discharge valve), liquid line filter-drier, moisture-liquid indicator, liquid line, to 
evaporator  unit  (including  liquid  line  connection,  solenoid  valve,  expansion 
valve, and suction line connection), returning to insulated suction line, suction 
valve and then back to condensing unit. 

2)  If the condensing unit is located below the evaporator unit, use inverted U trap 

to  prevent  liquid  from  flooding  back  to  the  compressor;  if  the  elevation 
difference is more than 10 ft or the line set exceeds 75 ft, use both inverted U 
trap and suction accumulator. 

3)  If the condensing unit is located more than 10 ft above the evaporator unit, use 

U trap to aid oil returning to the compressor. 

4)  Complete pipe brazing, check solenoid valve and expansion valve restrictions 

and test leak. 

5)  Hook up the drain line and check if water drains. 
 
The line sizes and refrigerant charges are listed as follows. 

 

Model No 

Equivalent  

Line Set 

Liquid 

Line 

Suction 

Line 

Drain Line 

Recommended 

Charge 

WM-1520SSL 

<= 75 FT 

1/4" OD 

3/8” OD 

1/2” OD 

R134a/15 OZ 

WM-2520SSL 

<= 75 FT 

1/4" OD 

3/8” OD 

1/2” OD 

R134a/19 OZ 

WM-4520SSL 

<= 75 FT 

1/4" OD 

1/2” OD 

1/2” OD 

R134a/26 OZ 

WM-6520SSL 

<= 75 FT 

1/4" OD 

1/2” OD 

1/2” OD 

R134a/32 OZ 

 

7.  Connecting Electrical Wires 

 
Connect all electrical components using the wiring diagrams in accordance with all 
state and local codes.  

8.  Evacuating, Charging and Starting the system 

 

CAUTION:  

 

Always use the superheat and subcooling, pressure readings to charge 
refrigerant  properly;  the  listed  charge  amounts  are  used  for  reference 
only.  

 

If the unit is equipped with a low ambient condition kit and installed in the 
summer, charge 15% more refrigerant. 

 

If the low ambient condition kit is used, turn off the compressor before 
power  the  condensing  unit.  Only  turn  on  the  compressor  after  the 
condensing unit has been powered for 12 hours.

 

Содержание WINE-MATE WM-1520SSL

Страница 1: ...1 www winemate com Ceiling Split Cooling System Installation Operation Care Manual WM 1520SSL WM 2520SSL WM 4520SSL WM 6520SSL www vinotemp com...

Страница 2: ...is the personal responsibility of the consumer to have a proper 3 prong wall receptacle installed by a qualified electrician DO NOT UNDER ANY CIRCUMSTANCES REMOVE THE POWER CORD GROUNDING PRONG A sepa...

Страница 3: ...le of Contents Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 15 Electrical Wirings 25 Customer Support 28 Warran...

Страница 4: ...erature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer...

Страница 5: ...sing units can be located away from the wine cellars 50 ft so that noise and compressor vibration are isolated SSL evaporator units provide low profile and whisper quiet operation The evaporator units...

Страница 6: ...WM 152SFCL 16 75x14 5x4 75 14 75x14 75 WM 152SCU 18x14x12 1200 150 140 R134a 220V 50Hz 0 2A 220V 50Hz 1 6A 15 30 WM 2520SSL WM 252SFCL 31 75x14 5x4 75 29 75x14 75 WM 252SCU 18x14x12 2100 230 230 R134a...

Страница 7: ...the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys press...

Страница 8: ...nstrument 2 Temperature Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of...

Страница 9: ...probe faulty min 15 CoF compress off with probe faulty min 30 CF temperature unit F C F Fahrenheit rES display resolution in integer dLy temperature display delay min 1 ot probe calibration 0 LS mini...

Страница 10: ...1 Speech notice will be sent to your phones when the cellar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After test...

Страница 11: ...lean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Removing...

Страница 12: ...ure It may be higher than 59 F if it is in anti short cycle or defrost cycle and turns off at 55 F of air temperature The average air temperature is 57 F and then the wine temperature is around 57 0 5...

Страница 13: ...nections b Check start relay start capacitor overload protector compressor c Call service 9 Compressor running but condenser fan not running a Fan blade stuck b Incorrect or loose wirings c Failed mot...

Страница 14: ...ive condensate in wine cellar a Air leak in the wine cellar causing excessive condensate b High humidity causing excessive condensate c Drain restricted a Check for any air leak b Use drain line c Cle...

Страница 15: ...lation is critical Vinotemp can only warrant the quality of the components The installation and proper operation of the system must be warranted by the installer Installation of the system must be don...

Страница 16: ...copper tubing CAUTION Liquid and suction line locations may differ from what are shown here please check on the units for proper installation Fig 3 WM 152 252SFCL Evaporator Unit Fig 4 WM 452 652SFCL...

Страница 17: ...17 Fig 5 WM 152 452SCU Condensing Unit Fig 6 WM 652SCU Condensing Unit...

Страница 18: ...ional wires are needed 18 gauge wires may be used to extend the air probe 3 Evaporator Unit Installation 1 The WM 152 652SFCL evaporator units shall be installed for ceiling mount with the supply air...

Страница 19: ...flooding and shaded from direct sun It shall not be exposed to temperatures higher than 110 F or lower than 50 F 3 Leave minimum 5 ft clearance for the exhaust side and leave minimum 1 foot clearance...

Страница 20: ...e control if applicable for pump down Suction pressure setting Cut out 5 psig Cut in 25 psig Differential 20 psig Head pressure setting Cut out 230 psig Cut in 150 psig Differential 80 psig It may nee...

Страница 21: ...Head pressure setting Cut in 170 psig Cut out 110 psig Differential 60 psig It closes on rise of pressure It may need to adjust the setting in the field to avoid fan short cycle Fig 14 Condenser Fan...

Страница 22: ...he condensing unit is located more than 10 ft above the evaporator unit use U trap to aid oil returning to the compressor 4 Complete pipe brazing check solenoid valve and expansion valve restrictions...

Страница 23: ...ressure setting gives a dew point to maintain the proper humidity for storing wine 4 The temperature split across the evaporator shall be 8 10 F at 55 F wine cellar temperature 5 Again you must verify...

Страница 24: ...l subcooling 13 Low suction pressure and high head pressure High superheat and high subcooling 14 Low suction pressure and high head pressure High superheat and high subcooling 15 low to normal suctio...

Страница 25: ...are the field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the co...

Страница 26: ...26 Fig 17 WM 6520SSL Electrical Wiring Diagram Fig 18 Low Ambient Temperature WM 1520 4520SSL LA Electrical Wiring Diagram...

Страница 27: ...27 Fig 19 Low Ambient Temperature WM 6520SSL LA Electrical Wiring Diagram...

Страница 28: ...8 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp co...

Страница 29: ...s and is in lieu of all other warranties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever An...

Страница 30: ...ES BASED UPON INCONVENIENCE LOSS OF USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTH...

Отзывы: