background image

13.2.2   DC Units Second & Third Stage Tone 
Selection 

 

For units set up for –ve switching (default setting): 

 

Stage two (S2) Operation

 

 

Power +ve and –ve, link a -
ve supply line to the S2 
terminal.  
Dip switch alters stage 2 
tone. 

 

Stage three (S3) Operation 

 

Power +ve and –ve, link a -
ve supply line to the S3 
terminal.  
Dip switch alters stage 3 
tone. 

 

For units set up for +ve switching (refer to 13.3): 

 

Stage two (S2) Operation

 

 

Power +ve and –ve, link a 
+ve supply line to the S2 
terminal.  
Dip switch alters stage 2 
tone. 

Stage three (S3) Operation 

 

Power +ve and –ve, link a 
+ve supply line to the S3 
terminal.  
Dip switch alters stage 3 
tone. 

 
 

 

 

Fig. 6 DC Terminals 

 

13.3  Stage Switching Polarity (DC Units 

Only) 

 

The BExS110D DC sounders have the facility to use either 
+ve or –ve switching to change the tone to the second and 
third stages. Negative switching is the default setting. For –ve 
switching connect the two headers on the pcb to the left-hand 
(marked –ve) and centre pins. For +ve switching connect the 
headers to the right hand (ve) and the centre pins. 
(Refer to Fig. 7) 

 

 

 
 
 
 
 
 
 
 
 
 

 
 

 

 

Fig. 7 Stage Switching Polarity 

 

13.4 Line 

Monitoring 

 

On BExS110D DC units, dc reverse line monitoring can be 
used if required. All DC sounders have a blocking diode fitted 
in their supply input lines. An end of line monitoring diode or 
an end of line monitoring resistor can be connected across 
the +ve and –ve terminals. If an end of line resistor is used it 
must have a minimum resistance value of 3k3

 and a 

minimum power rating of 0.5 watts or a minimum resistance 
value of 500

 and a minimum power rating of 2 watts. 

 
The resistor must be connected directly across the +ve and -
ve terminals as shown in the following drawing. The resistor 
leads should be kept as short as possible.  

 

Fig. 8 End of Line Resistor Placement 

 

 

 

 

 

 

 

 

End of Line Resistor 

Volume Control 

DIP Switch 

DC Terminals 

Stage Headers 

Negative Switching Activated 

Positive Switching Activated 

Header Pin Location 

Header Pin Location 

S2
S3

+

 

 

+

 

+

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание BExS110D

Страница 1: ... Zone 2 Explosive gas atmosphere not likely to occur in normal operation but may be present for short periods Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen and Acetylene up to 55 C ambient Temperature Classification T1 450ºC T2 300ºC T3 200ºC T4 135ºC Area Classification Dust Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air m...

Страница 2: ...f the unit The BEx sounder should be secured to any flat surface using the three 7mm fixing holes on the stainless steel U shaped mounting bracket See Figure 1 The required angle can be achieved by loosening the two large bracket screws in the side of the unit which allow adjustment of the sounder in steps of 18 On completion of the installation then two large bracket adjustment screws on the side...

Страница 3: ...ified adapters 10 Earthing Both AC and DC sounder units must be connected to an earth The units are provided with internal and external earth terminals which are both located on the terminal chamber section of the unit Fig 3 Internal View of Cover When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal eart...

Страница 4: ...0 AC sounder Stage two S2 Operation Power L and N link the Common C and S2 terminal Dip switch alters stage 2 tone Stage three S3 Operation Power L and N link the Common C and S3 terminals Dip switch alters stage 3 tone Fig 4 AC Terminals 13 DC Wiring A 4 way terminal block is provided on the DC Sounder There are 1 off ve 1 off ve 1 off stage 2 and 1 off stage 3 terminals in total 13 1 Wiring Diag...

Страница 5: ...o the left hand marked ve and centre pins For ve switching connect the headers to the right hand marked ve and the centre pins Refer to Fig 7 Fig 7 Stage Switching Polarity 13 4 Line Monitoring On BExS110D DC units dc reverse line monitoring can be used if required All DC sounders have a blocking diode fitted in their supply input lines An end of line monitoring diode or an end of line monitoring ...

Страница 6: ...Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical installations inspection and maintenance To avoid a possible ELECTROST...

Страница 7: ...ne 5 15 Continuous at 800Hz 0 1 1 1 0 Tone 2 Tone 5 16 Intermittent 660Hz 150mS on 150mS off 1 1 1 1 0 Tone 18 Tone 5 17 Alternating 544Hz 100mS 440Hz 400mS 0 0 0 0 1 Tone 2 Tone 27 18 Intermittent 660Hz 1 8s on 1 8s off 1 0 0 0 1 Tone 2 Tone 5 19 1400Hz to 1600Hz sweep up over 1s 1600Hz to 1400Hz sweep down over 0 5s 0 1 0 0 1 Tone 2 Tone 5 20 Continuous 660Hz 1 1 0 0 1 Tone 2 Tone 5 21 Alternati...

Страница 8: ...R P T A P 105 6 106 8 107 4 106 4 106 2 103 6 104 1 105 3 106 8 106 7 105 0 103 3 15 800Hz Continuous 100 1 103 3 105 6 107 6 103 0 100 3 10 2 102 9 105 2 106 8 102 4 99 6 16 660Hz 150mS ON 150mS OFF Intermittent 92 5 93 9 97 9 97 5 92 5 91 5 92 1 94 5 98 5 97 9 93 1 92 2 17 544Hz 100mS 440Hz 400mS NF S 32 001 101 0 102 5 106 5 107 5 103 9 100 7 101 7 102 5 105 7 107 9 103 6 101 5 BExS110D Input V...

Отзывы: