SW24.D

EN

4.5 - Stop push-button

99

52

63

51

99 61 62

COM

STOP

5 - Control panel programming

5.1 - Preliminary operations

After powering the unit, the name of the control board written as 

SW2.D, the firmware version FX.XX and 3 flashes with the word FLSH 

appear in the display, then display then goes off.

To function correctly, the control panel requires some minimum and 

essential settings and checks.

- Input status check:

 

Check the diagnostic LEDs of the inputs, the LEDs 61, 62, 63 must be 

on.

  If one of the safety inputs (61, 62, 63) is not used, insert a bridge 

between the common (99) and the unused input.

  If one of the safety inputs (61, 62, 63) is open, the dot at bottom right-

hand corner of the display flashes to indicate a engaged/non-working 

safety that will prevent the gate from moving. It will therefore be neces-

sary to check the connections and the correct functioning status of the 

safety devices.

- Gate travel calibration

  The control panel must know some physical parameters of the gate in 

order to function correctly. The operation allowing the control panel to 

know these physical gate parameters is called travel calibration. If this 

is not done, the control panel may not perform slowdowns or detect 

obstacles correctly.

5.2 - Using the display

Button

Description

OK

Button to turn on the display, to access the menu and to 

confirm the parameter value change. When the motor is 

moving, when pushed once it displays the absorption in A of 

motor M1, when pushed twice it displays the absorption in A 

of motor M2

Button to scroll up the menus and increase the parameter 

value

Button to scroll down the menus and decrease the param-

eter value

ESC

Button to turn off the display, exit the menu and cancel the 

parameter value change

51

Step-by-step command button

5.3 - 

Menus

The control board programming is organized in menus and submenus 

that allow to access and edit the parameters and logics of the control 

board. The control board features the following first level menus:

Menu

Description

LRNE

Quick gate travel calibration

LRNA

Advanced gate travel calibration

PAR

Control board parameter setting menu

RAD

Remote controls management menu

DEF

Factory reset menu

CNT

Cycle counter menu

ALM

Board alarms menu

PASS

Board protection level setting menu

Submenus

All submenus are described in the table below.

LRNE

Quick gate travel calibration.

The calibration is fully self-performed and sets:

- Opening and closing slowdown to 30% of the total travel

- Opening delay between leaves to 3 s

- Closing delay between leaves to 6 s

It requires mechanical stops both on opening and closing

Rows highlighted in grey refer only refer to a double leaf in-

stallation, in a single leaf installations delays between leaves 

are not programmed
Button Display 

msg

Phase description

-

51

Wait for calibration procedure start

51

CLS2

When button pressed: leaf 2 closing and 

search for leaf 2 closing stop

-

CLS1

Leaf 1 closing and search for leaf 1 closing 

stop

-

LOC

Electric lock activation to free leaf 1

-

OPN1

Leaf 1 opening travel measurement at slow 

down speed

-

OPN2

Leaf 2 opening travel measurement at slow 

down speed

-

CLS2

Leaf 2 closing at normal speed and then at slow 

down speed up to leaf 2 closing mechanical stop

-

CLS1

Leaf 1 closing at normal speed and then at slow 

down speed up to leaf 1 closing mechanical stop

-

oooo

Full opening and closing of both leaves for cur-

rent thresholds measurement

-

END

End of procedure

LRNA

Advanced gate travel calibration.

Calibration allows the installer to set:

- Opening and closing slow down position

- Leaves end of travel positions

- Opening and closing delays between leaves

- Pedestrian opening position

It requires mechanical stops on closing only

Rows highlighted in grey refer only refer to a double leaf in-

stallation, in a single leaf installations delays between leaves 

are not programmed
Button Display 

msg

Phase description

-

51

Wait for calibration procedure start

51

CLS2

When button pressed: leaf 2 closing and 

search for leaf 2 closing stop

-

CLS1

Leaf 1 closing and search for leaf 1 closing 

stop

-

LOC

Electric lock activation to free leaf 1

51

OPN1

Leaf 1 opening start. 

When button pressed: leaf 1 opening slow 

down position setting, the leaf proceeds at 

slow down speed

Содержание Elvox SW24.D

Страница 1: ...Installer manual SW24 D 24 Vdc control panel for swing gates...

Страница 2: ...Contents Page 1 Product features 1 2 System type 1 3 Description of the terminal blocks 2 4 Connecting accessories 4 5 Control panel programming 6 6 DIP switch functions 10 7 LED functions 10 8 List o...

Страница 3: ...Accessories power supply 24 Vdc 500 mA Receiver memory 200 remote controls Receiver frequency 433 MHz Remote control encoding Rolling code or hard coded Fuse F1 line protection ATO 15 A Fuse F2 acces...

Страница 4: ...0 mA 1 Accessories positive 1 Accessories positive 24 Vdc 500 mA 0 Accessories negative 10 Flashing light negative 24 Vdc 15 W max 11 Flashing light positive Terminal Description Rated data E Encoder...

Страница 5: ...or 100 s after it has stopped With P20 2CH it is an Auxiliary Radio Output it turns on upon pressing the button that was saved on the remote control as the 2nd radio channel for the amount of time set...

Страница 6: ...hotocell PHC N C If not used jumper with the common 99 63 Photocell PH N C Operating according to the setting for parameter P06 P06 1 Photocell with the gate stopped does not allow the gate to open du...

Страница 7: ...COM NC FSW RX1 RX2 TX1 TX2 PHC PH COM 24V 24V P06 1 P08 OFF 4 3 Photocells and photocells when closing with photo test active 12 19 18 14 1 0 10 11 E E 45 41 99 52 63 51 99 61 62 NO COM NC FSW NO COM...

Страница 8: ...gate travel calibration LRNA Advanced gate travel calibration PAR Control board parameter setting menu RAD Remote controls management menu DEF Factory reset menu CNT Cycle counter menu ALM Board alarm...

Страница 9: ...he opening the command is not ac tive If P01 ON when paused it restarts the pause time and if the input 51 remains en gaged the control board suspends the count until the input is disengaged for the c...

Страница 10: ...erazione massima 1 Accelerazione minima 5 PAR P24 M2 acceleration M2 acceleration ramp until normal speed is reached 3 Accelerazione massima 1 Accelerazione minima 5 P25 M1 deceleration ramp M1 motor...

Страница 11: ...oooo Waiting the code press the remote control button the receiver is set as rolling code rc Waiting the code press the remote control button the receiver is set as fixed code fc Remote control button...

Страница 12: ...51 52 61 62 63 41 45 _ ANT U2 ON 1 DIP2 ESC OK LED Status Description DL1 OFF Power supply not present ON Power supply present 41 OFF When the motor M1 is running encoder signal absent encoder not wor...

Страница 13: ...11 SW24 D EN...

Страница 14: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com SW24 D installer EN 00 1911...

Отзывы: