By-alarm

01709

Setting parameters  

The detection parameters can be configured by using the keyboard 01705 or by 
using the By-alarm Manager programming software.

Important

: particular care must be taken when setting impulse lengths in seconds 

with a high number of repetitions: if the time taken to measure all the impulses 
exceeds the time window set at 60 s the system resets the counter and does not 
trigger an alarm.

Reset button

Pressing the push-button

 PB1

 located on the side of the card resets the micro-

processor without losing the configuration of the device and of the control panel 
governing it.

ZONE BALANCING

 

The module has 4 input lines that are individually configurable for single, double 
and triple balancing.

Single balancing

When programming the line for single balancing you need to connect a resistance 
of 3.3 kΩ (orange, orange, red) in series with the normally closed output of the 
switch-alarm or inertial sensor.

ALARM

TAMPER

To the Tamper input of

the control panel

To the alarm input of

the control panel

3.3 kΩ

3.3 kΩ

Double balancing

When programming the line for double balancing, two resistors must be connected, 
one of 3.3 kΩ (orange, orange, red) in series with the tamper-proof line and the 
other of 4.7 kΩ (green, purple, red) in parallel with the normally closed output of the 
switch-alarm or inertial sensor.
In this way, by using just two wires, the control panel distinguishes the alarm status 
from the line tampering status; depending on the control panel programming, you 
can activate different outputs for each different alarm status detected.

ALARM

TAMPER

To the alarm input of

the control panel

3.3 kΩ

4.7 kΩ

Triple balancing

If the detector is provided with a masking detection output, you can make sure 
that the control panel recognizes this state. To do this, three resistors must be 
connected, one of 3.3 kΩ that detects tampering (orange, orange, red) in series 
with the line, another of 4.7 kΩ (yellow, purple, red) in parallel with the alarm con-
tact and another of 15 kΩ (brown, green, orange) in parallel with the anti-masking 
alarm contact.
In this way, by using just two wires, the control panel distinguishes between the 
alarm, tampering and detector masking recognition statuses; lastly, depending on 
the control panel programming, you can activate different outputs for each alarm 
status detected.

ALARM

TAMPER

MASKING

3.3 kΩ

4.7 kΩ

15 kΩ

To the alarm input of

the control panel

INSTALLATION RULES

• Installation should be carried out in compliance with the current regulations 

regarding the installation of electrical equipment in the country where the prod-
ucts are installed. 

• The module can be installed on the control panels art. 01700, 01700.120, 01703, 

01703.120 and on the power supply unit art. 01717, 01717.120.

•  The module can be installed inside the box 01714 that, made of plastic, is 

equipped with protection against opening and against tearing off the wall, thus 
keeping the degree of IMQ-security systems certification of the entire system 
unchanged. This enclosure is specially designed to contain all the accessory 
devices of the intrusion detection alarm system.

Installation 

1. Install the back of the box 01714 on the wall using a screw for fixing the 

tamper.    

2. Fix the springs provided on the module 01709 (conical spring on the front and 

cylindrical spring on the back).

1

ON

ECE

2

3

4

5

6