By-alarm

01709

CN5

20

D
E

A B

RS 485

D
E

A B

RS 485

01700-01700.120

01703-01703.120

01709

By-alarm configurable 4-input expansion module for potential-free 
contacts, cord for roller shutter, passive non-piezoelectric shock 
detectors.

TECHNICAL CHARACTERISTICS

• Power supply: 12 V ± 20%
• Absorption: 18 mA max
• Input lines: No. 4 with single, double and triple balancing
• Connections: with 4 wires to one of the serial ports for connection to the RS485 bus
• Operating temperature: -10..+40 °C (indoor use)
• Dimensions: 76x47 mm
• Degree of safety: 2 (EN 50131-3)
• Ambient class: II (EN 50131-3)

INSTALLING THE EXPANSION MODULES

The module is connected to the control panel to one of the bus serial ports, following 
the instructions given in the control panel's installation manual and respecting the 
warnings.
• For installation, use halogen-free shielded cables suitable for installation with 

Category 1 power cables (U0 = 400 V) such as cable art. 01733 (2x0.50 
mm

2

+2x0.22 mm

2

). 

• For the power supply, use wires with a minimum cross-section of 0.50 mm

2

 observ-

ing the c and - polarity. 

• Connect the signal cables A and B using conductors with a minimum section equal 

to 0.22 mm

2

• The length of the connection with the wired sensors must not exceed 100 m.
• The shielding must be connected to the negative on the control panel side and left 

free on the expansion module side.

Input zones

The module has 4 inputs and 2 push-buttons for protection against opening the 
enclosure and against tearing it off the wall. The push-buttons protecting against 
opening and against removal on the zone expansion card can be cut off by closing the 
relevant jumpers alongside the buttons. The power supply to any sensors is carried 
by the 2 terminals marked 

+

 and 

-

  , protected by the 

resettable 500 mA fuse F1

 next 

to the power supply terminals.

Recessed connector

The device has a recessed connector; 

it must not be used under any circumstances 

as it is for internal testing and firmware updating; improper use may damage the 
circuit.

ADDRESSING THE EXPANSION MODULES

For them to be recognised by the control panel, the expansion modules need to be 
addressed by setting the DIP-switches on the printed circuit board; the settings that 
can be made are listed in the following table:

EXPANSION NO.

DIP-SWITCH NO.

1

2

3

4

5

6

EXPANSION 1

OFF

OFF

OFF

OFF

OFF

OFF

EXPANSION 2

ON

OFF

OFF

OFF

OFF

OFF

EXPANSION 3

OFF

ON

OFF

OFF

OFF

OFF

EXPANSION 4

ON

ON

OFF

OFF

OFF

OFF

EXPANSION 5

OFF

OFF

ON

OFF

OFF

OFF

EXPANSION 6

ON

OFF

ON

OFF

OFF

OFF

EXPANSION 7

OFF

ON

ON

OFF

OFF

OFF

EXPANSION 8

ON

ON

ON

OFF

OFF

OFF

EXPANSION 9

OFF

OFF

OFF

ON

OFF

OFF

EXPANSION 10

ON

OFF

OFF

ON

OFF

OFF

EXPANSION 11

OFF

ON

OFF

ON

OFF

OFF

EXPANSION 12

ON

ON

OFF

ON

OFF

OFF

EXPANSION 13

OFF

OFF

ON

ON

OFF

OFF

EXPANSION 14

ON

OFF

ON

ON

OFF

OFF

Caution: The maximum number of expansion modules that can be installed 
depends on the type of control panel used. 
If the addressing made with the DIP-switches is changed with the module 
switched on, to make it operational you need to press the push-button PB1 or 
power cycle the device.

Amber LED  

The amber LED on the expansion module lets you control functionality as follows:
• 

On steady

: module properly powered but no serial communication.

• 

Blinking at a frequency of 1 s

: module powered correctly and receiving serial 

communications but these are sent with an incorrect address or no configuration 
of the device in the control panel.

• 

Blinking with one short pulse every second

: module powered properly and 

correct serial communication.

CONFIGURATION OF THE MODULE 01709

The 4-input expansion module enables connecting also switch-alarms and mechan-
ical inertial sensors that generate short pulses close to each other for detecting the 
opening of shutters or vibration of surfaces (cabinets, partitions, etc.).
The inputs are individually programmable for single, double and triple balancing.
Detection is based on three parameters: minimum duration of the imbalance, num-
ber of repetitions, and maximum length of the time window for counting the repeti-
tions. 

The minimum duration and number of repetitions can be programmed; the 

length of the time window is set at value of 60 s.
Caution

: If the line were to remain permanently out of balance for more than 30 

seconds, an alarm condition of the control panel would in any case be generated.

FRONT VIEW.

CONNECTIONS. 

RS485 bus line

Tear-proof 
cut-off 

S1

Inputs

DIP-switch 
for setting
address

Reset button 

PB1

Connector 
not used

Anti-opening 
cut-off 

S2