Removing the Condenser
(continued)
10. Remove fan by removing the two nuts on fan
mounting bracket at the baseplate. The fan wire
leads can be left. connected. Set fan assembly
to side of mechanical.
11. Remove the three nuts retaining the side of the
fan shroud. Remove the fan shroud.
12. Unbraze the capillary tube from the drier
assembly.
13. Unbraze the hot gas valve tube at the tee on
the drier assembly (see
Figure 4
).
14. Unbraze and remove the drier assembly.
15. Unbraze the hot gas line from the compressor
at the top of the condenser coil (see
Figure 11
).
Installing the Condenser
Reverse the removal procedure. Be sure to
thoroughly flush the system and evacuate to 50
microns before weight charging. If contamination
was found or determined, the evaporator should
also be replaced at this time.
Drain Valve
The drain valve drains water that is left in the
reservoir after ice production. The valve will only
be open for a fixed time of 45 seconds during the
beginning of the harvest cycle.
The drain valve fails by allowing water to flow into
the drain during the ice production cycle (leak-
by). This can be caused by a foreign particle(s) or
build-up of mineral deposits that will not allow
the valve to fully seat or has caused damage to
the seat of the valve. Periodic cleaning of the ice
machine will keep build-up off the valve allowing it
to work properly and should be done before further
evaluation of the valve.
Symptoms of this include thin or no ice slab
(depending on severity of leak) and, more
noticeably, water drainage through to the drain
during ice production cycle (do not mistake this for
reservoir run-off water or melted ice drain
water from the ice bin). The drain valve should be
replaced if it is found to be leaking.
The drain valve solenoid actuator can also possibly
fail. Test the solenoid by checking the resistance.
A resistance of 50-65 ohms should be found. If no
resistance is found, the drain valve will need to be
replaced.
Service Diagnostics and Procedures
(Sealed System Components/Valves)