ESFR PENDENT 

SPRINKLER VK506 (K22.4)

TECHNICAL DATA

Form No. F_081612    18.10.11     Rev 18.2

Page 5 of 5

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Figure 1:  Sprinkler Wrench

Use Side A for VK506

Wrench flat

Protective 

Sprinkler 

Cap

3-3/16”

(81 mm)

1-3/4”

(45 mm)

1-9/16”

(40 mm)

1-5/8”

(41 mm)

Figure 2:  Sprinkler Dimensions

Dimensions are 

approximate.

TABLE 2

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR MODEL VK506 ESFR PENDENT SPRINKLERS

Storage Type

NFPA

FM

Sprinkler Type

ESFR

Storage

Response Type

ESFR

QR

System Type

Wet Pipe system only

Wet Pipe system only

Temperature Rating(s) ºF (ºC)

165 ºF (74 ºC) and 205 (96 ºC)

165 ºF (74 ºC) and 205 (96 ºC)

Open Frame Single, Double, Multiple-
Row,  or  Portable  Rack  Storage  of  Class  I-IV                                                                 
and Group A or B Plastics

Refer to NFPA 13.

Refer to FM 2-0 and 8-9.

Solid  Pile  or  Palletized  Storage  of  Class  I-IV  and                                                                           
Group A or B Plastics

Refer to NFPA 13.

Refer to FM 2-0 and 8-9.

Idle Pallet Storage

Refer to NFPA 13.

Refer to FM 2-0, 8-9, and 8-24.

Rubber Tire Storage

Refer to NFPA 13.

Refer to FM 2-0 and 8-3.

Rolled Paper Storage (Refer to the standard.)

Refer to NFPA 13.

Refer to FM 8-21.

Flammable Liquid Storage (Refer to the standard.)

Refer to NFPA 30.

Refer to FM 7-29

Aerosol Storage (Refer to the standard.)

Refer to NFPA 30B

Refer to FM 7-31

Automotive  Components  in  Portable  Racks                                                                       

(Control mode only, refer to the standard.)

Refer to NFPA 13.

N/A

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking ESFR Pendent Sprinklers 

are to be installed in accordance with the latest edition of Viking technical data, the latest standards of NFPA, FM Global, 

VdS, LPCB, and any other Authorities Having Jurisdiction, and also with provisions of governmental codes, ordinances, and 

standards whenever applicable.

Replaces Form No. F_081612 Rev 18.1 

(Replaced design criteria tables; added P65 Warning.) 

Содержание VK506

Страница 1: ... followed In addition some storage arrangements of rolled paper flammable liquids aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK506 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets new UL1767 test standard and compliance program for ESFR sprinklers installed in rack storage with high clearances to ceiling 20 ft or greater FM Approved Class 2026...

Страница 2: ...y render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation A Sprinklers must be handled with care They must be stored in a cool dry place in their original shipping container Never install sprinklers that have been dropped or damaged in any way Such sprinklers should be destroyed immediately NOTE Wet pipe systems must be provided...

Страница 3: ...ng and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced When replacing sprinklers use only new sprinklers C The sprinkler discharge pattern is critical for proper fire protection Therefore nothing should be hung from attached to or other wise obstruct the discharge pattern All obstructions must be immediately removed or if necessary addi...

Страница 4: ... 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 5 Listed by Underwriters Laboratories Inc for use in the U S and Canada as a Specific Application ESFR Sprinkler refer to the deflector position re quirements on page 4 Approval Chart 2 FM ESFR Pendent Sprinkler VK506 Maximum 175 PSI 12 bar WWP B...

Страница 5: ...e of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Solid Pile or Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21...

Отзывы: