ESFR PENDENT 

SPRINKLER VK506 (K22.4)

TECHNICAL DATA

Form No. F_081612    18.10.11     Rev 18.2

Page 3 of 5

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

5.  OPERATION

During fire conditions, the heat-sensitive fusible element assembly disengages, releasing the seat and belleville spring assembly 

to open the waterway. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to 

suppress the fire.

6.  INSPECTIONS, TESTS AND MAINTENANCE

NOTICE

The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For 

minimum maintenance and inspection requirements, refer to the NFPA standard that describes care and maintenance 

of sprinkler systems. In addition, the Authorities Having Jurisdiction may have additional maintenance, testing, and 

inspection requirements that must be followed.

A. The sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency of 

inspections may vary due to corrosive atmosphere, water supplies, and activity around the device.

B. Sprinklers that have been painted or mechanically damaged must be replaced immediately. Sprinklers showing signs of corrosion 

shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if necessary, 

replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards (e.g., NFPA 25) 

and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Sprinklers 

that have operated cannot be reassembled or reused, but must be replaced. When replacing sprinklers, use only new sprinklers.

C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or other-

wise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers installed.

D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/

or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should be 

given to employment of a fire patrol in the affected area.

1. Remove the system from service, drain all water, and relieve all pressure on the piping.

2. Using the special sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that the 

replacement sprinkler is the proper model and style, with the correct orifice size, temperature rating, and response character-

istics. A fully stocked spare sprinkler cabinet should be provided for this purpose.

3. Place the system back in service and secure all valves. Check the replaced sprinklers and repair all leaks.

E. Sprinkler systems that have been subject to a fire must be returned to service as soon as possible. The entire system must 

be inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of 

combustion, but have not operated, should be replaced. Refer to the Authorities Having Jurisdiction for minimum replacement 

requirements.

7.  AVAILABILITY

The Viking Model VK506 Sprinkler is available through a network of domestic and international distributors. See The Viking 

Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Содержание VK506

Страница 1: ... followed In addition some storage arrangements of rolled paper flammable liquids aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK506 2 LISTINGS AND APPROVALS cULus Listed Category VNWH Successfully meets new UL1767 test standard and compliance program for ESFR sprinklers installed in rack storage with high clearances to ceiling 20 ft or greater FM Approved Class 2026...

Страница 2: ...y render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation A Sprinklers must be handled with care They must be stored in a cool dry place in their original shipping container Never install sprinklers that have been dropped or damaged in any way Such sprinklers should be destroyed immediately NOTE Wet pipe systems must be provided...

Страница 3: ...ng and or replacement is required Sprinklers that have operated cannot be reassembled or reused but must be replaced When replacing sprinklers use only new sprinklers C The sprinkler discharge pattern is critical for proper fire protection Therefore nothing should be hung from attached to or other wise obstruct the discharge pattern All obstructions must be immediately removed or if necessary addi...

Страница 4: ... 3 This chart shows listings and approvals available at the time of printing Other approvals may be in process 4 Refer to the latest standards of NFPA 13 5 Listed by Underwriters Laboratories Inc for use in the U S and Canada as a Specific Application ESFR Sprinkler refer to the deflector position re quirements on page 4 Approval Chart 2 FM ESFR Pendent Sprinkler VK506 Maximum 175 PSI 12 bar WWP B...

Страница 5: ...e of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Solid Pile or Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Rolled Paper Storage Refer to the standard Refer to NFPA 13 Refer to FM 8 21...

Отзывы: