12
WALL INSTALLATION
EXTERIOR-POWER VENTILATOR
Exterior Power Ventilator Kit
1. Choose a position on the outside wall. Min. 24” (61.0 cm
from ground may vary depending on local codes or
location. Make sure that no wall studs, pipes or wires run
through the opening area.
2. From inside, mark and drill a guide hole at the center of
the opening area.
3. From the outside, use the guide hole as a starting point to
lay out the installation.
A. Use a T-square to measure 11
13/16
” (30.0 cm) to the left
of the guide hole, then 14
11/16
” (37.3 cm) to locate the
top-left corner of the layout.
B. Starting from the top-left corner, mark a 22” (55.9 cm) by
29
1/2
” (74.9 cm) rectangle on wall located from guide
hole.
4. Cut a rectangular hole in the siding only. Do not cut the
sheathing. Nail down all siding ends.
5. Mark an 11” (27.9 cm) diameter circle centered on the guide
hole and mark the center of the 1
1/4
” diameter electrical
wiring hole.
6. Cut the 11” (27.9 cm) hole in the sheathing and drill the
1
1/4
”(3.2 cm) as marked.
7. Place a large bead of caulk on the back side of the housing
along the outer edge.
8. Center the blower ring in the 11” (27.9 cm) diameter hole,
making sure that the 1
1/4
” (3.2 cm) diameter electrical wiring
hole aligns with the hole in the wiring box.
9. Attach blower to the wall with the six screws provided. All
six holes in the back panel must be filled, or any moisture
that may get inside the housing could leak into the house.
10. Using a good grade of caulk, seal all around the mounting
screw heads.
11. Bring electrical wiring through the hole in the wiring box and
secure it according to local codes.
12. Make the electrical connections with the proper connector for
the type of wire being used. Connect white to blue, black to
black, and green or bare wire to grounding screw.
13. Replace wiring box cover and screws. Do not pinch wiring
under cover.
14. Check for free movement of the damper before installing
housing cover and screws.
15. Turn on power and check operation of the blower.
16. Top and side flanges of the back plate may be covered with
trim strips. Do not block grill opening at bottom with trim.
It will adversely affect performance of the blower.
WALL CUTOUT
B
3”
(7.6 cm)
14
11/16
(37.3 cm)
C
A
11”
(27.9 cm)
dia. hole
1
1/4
” (3.2 cm)
dia. hole
Black to
Black
120 VAC
Line In
White to
Blue
Ground to
grounding
screw
FILTER INSTALLATION
Number of mesh filters and spacers will vary by model.
See page 17.
29
1/2”
(74.9 cm)
Mesh Filters
A
B
C
DEV1200
22”
17”
11 13/16”
(55.9 cm)
(43.2 cm) (30.0 cm)
DEV1500
25”
20”
14 5/8”
(63.5 cm)
(50.8 cm) (37.2 cm)