SPRINKLER OVERVIEW

Page 2 of 3

Form No. F_080814  Rev 14.1

VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a 

water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow 

arrow in the direction of discharge. Marked “SIDEWALL” on the deflector with an arrow and the word “FLOW”. (Note: Some 

vertical sidewall sprinklers can only be installed in the upright or pendent position—in this case, the sprinkler will also be marked 

“UPRIGHT” or “PENDENT”.)

HORIZONTAL SIDEWALL (HSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The special deflector 

provides a water spray pattern outward in a quarter-spherical pattern. Most of the water is directed away from the nearby wall 

with a small portion directed at the wall behind the sprinkler. The top of the deflector is oriented parallel with the ceiling or roof. 

The flow arrows point in the direction of discharge. Marked “SIDEWALL” and “TOP” with an arrow and the word “FLOW”.

EXTENDED COVERAGE (EC) SPRINKLER: A spray sprinkler designed to discharge water over an area having the maximum 

dimensions indicated in the individual listings. Maximum area of coverage, minimum flow rate, orifice size, and nominal K-Factor 

are specified in the individual listings. EC sprinklers are intended for Light-Hazard occupancies with smooth, flat, horizontal ceil-

ings unless otherwise specified. In addition to the above markings, the sprinkler is marked “EC”.

QUICK RESPONSE (QR) SPRINKLER: A spray sprinkler with a fast- actuating operating element. The use of quick response 

sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction (AHJ) prior to installing.

QUICK RESPONSE EXTENDED COVERAGE (QREC) SPRINKLER: A spray sprinkler designed to discharge water over an area 

having the maximum dimensions indicated in the individual listing. This is a sprinkler with an operating element that meets the 

criteria for quick response. QREC sprinklers are only intended for Light Hazard occupancies. The sprinkler is marked “QREC”.

FLUSH SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The unit is mounted 

flush with the ceiling or wall, with the fusible link exposed. Upon actuation, the deflector extends beyond the ceiling or wall to 

distribute water discharge. The sprinkler is marked “SSP”, “PEND”, or “SIDEWALL” and “TOP”.

CONCEALED SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The sprinkler is 

hidden from view by a cover plate installed flush with the ceiling or wall. During fire conditions, the cover plate detaches, and 

upon sprinkler actuation, the deflector extends beyond the ceiling or wall to distribute water discharge. The sprinkler is marked 

“SSP”, “PEND”, or “SIDEWALL” and “TOP”.  

RECESSED SPRINKLER: A spray sprinkler assembly intended for installation with a concealed piping system. The assembly con-

sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond 

the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity. Refer to the appropriate technical data page 

for allowable sprinkler models, temperature ratings, and occupancy classifications. DO NOT RECESS ANY SPRINKLER NOT 

LISTED FOR USE WITH THE ESCUTCHEON.

CORROSION-RESISTANT SPRINKLER: A special service sprinkler with non-corrosive protective coatings, or that is fabricated 

from non-corrosive material, for use in atmospheres that would normally corrode sprinklers.

DRY SPRINKLER: A special-service sprinkler intended for installation on dry pipe systems or wet pipe systems where the sprinkler 

is subject to freezing temperatures. The unit consists of a sprinkler permanently secured to an extension nipple with a sealed 

inlet end to prevent water from entering the nipple until the sprinkler operates. The unit MUST be installed in a tee fitting. Dry 

upright sprinklers are marked with the “B” dimension [distance from the face of the fitting (tee) to the top of the deflector]. Dry 

pendent and sidewall sprinklers are marked with the “A” dimension [the distance from the face of fitting (tee) to the finished 

surface of the ceiling or wall].

LARGE DROP SPRINKLER: A type of special application sprinkler used to provide fire control of specific high-challenge fire haz-

ards. Large drop sprinklers are designed to produce an umbrella-shaped spray pattern downward with a higher percentage of 

“large” water droplets than standard spray sprinklers. The sprinkler has an extra-large orifice with a nominal K-Factor of 11.2. 

Marked “HIGH CHALLENGE” and “UPRIGHT”.

EARLY SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLER: A sprinkler intended to provide fire suppression of specific high-

challenge fire hazards through the use of a fast response fusible link, 14.0, 16.8, or 25.2 nominal K-Factor, and special deflector. 

ESFR sprinklers are designed to produce high-momentum water droplets in a hemispherical pattern below the deflector. This 

permits penetration of the fire plume and direct wetting of the burning fuel surface while cooling the atmosphere early in the 

development of a high-challenge fire. Marked “ESFR” and “UPRIGHT” or “PEND”.

INTERMEDIATE LEVEL/RACK STORAGE SPRINKLER: A standard spray sprinkler assembly designed to protect its operating 

element from the spray of sprinklers installed at higher elevations. The assembly consists of a standard or large orifice upright 

or pendent sprinkler with an integral upright or pendent water shield and guard assembly. Use only those sprinklers that have 

been tested and listed for use with the assembly. Refer to the technical data page for allowable sprinkler models.

RESIDENTIAL SPRINKLER: A sprinkler intended for use in the following occupancies: one- and two-family dwellings with the fire 

protection sprinkler system installed in accordance with NFPA 13D; residential occupancies up to four stories in height with the 

fire protection system installed in accordance with NFPA 13R; and where allowed by the Authority Having Jurisdiction in resi-

dential portions of any occupancy with the fire protection system installed in accordance with NFPA 13.

Содержание V-SD

Страница 1: ...us Listing was achieved using full scale fire tests within wood truss construction The Model V SD Single Directional sprinkler provides a reduced response time due to its narrow ridge spacing of 6 ft 1 8 m and long throw pattern up to 40 ft in a single direction measured horizontally and is offered in three different slope ranges and one orifice size K 5 6 Listed for specific pitches 4 12 7 12 7 1...

Страница 2: ...ough the sprinkler orifice strikes the deflector forming a uniform spray pattern to extinguish or control the fire and protect the piping in the interstitial space 6 INSPECTIONS TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY The Viking V SD Specific Application Sprinkler is available through a network of domestic and international distribu...

Страница 3: ...tible and Non Combustible Sloped Attic Spaces Part Number1 SIN Maximum Pressure Thread Size Nominal K Factor Overall Length Listings and Approvals3 NPT BSP U S metric2 Inches mm cULus4 FM LPCB 19578 VK693 175 psi 1 2 15 mm 5 6 80 6 2 3 4 69 A1 A2 19799 VK694 175 psi 1 2 15 mm 5 6 80 6 2 3 4 69 A1 A2 19759 VK695 175 psi 1 2 15 mm 5 6 80 6 2 3 4 69 A1 A2 Approved Temperature Rating A 200 F 93 3 C Ap...

Страница 4: ...19578 VK693 V SD 1 2 15 mm 5 6 80 6 40 12 2 36 137 41 3 2 8 4 12 7 12 See footnote 2 19799 VK694 V SD 1 2 15 mm 5 6 80 6 30 12 2 24 91 18 4 1 3 7 12 10 12 See footnote 2 19799 VK694 V SD 1 2 15 mm 5 6 80 6 40 12 2 35 133 39 1 2 7 7 12 10 12 See footnote 2 19759 VK695 V SD 1 2 15 mm 5 6 80 6 30 12 2 24 91 18 4 1 3 10 12 12 12 See footnote 2 19759 VK695 V SD 1 2 15 mm 5 6 80 6 40 12 2 35 133 39 1 2 ...

Страница 5: ...alculations Because of the density of freezemaster antifreeze the K factor must be adjusted and the friction loss must be considered in the system design Piping Types Steel wet and dry CPVC wet systems only Occupancy Classification Light hazard only Viking V SD Sprinkler Spacing Maximum Coverage Area 339 ft2 31 5 m2 as measured along the slope Coverage area is determined by the maximum distance th...

Страница 6: ...vers a maximum of 6 152 mm laterally from the center line of the branch line Model V SD or V BB sprinklers are installed on Vertical Sprigs attached to the branchline Model V SD or V BB sprinklers are installed on angled sprigs a maximum of 6 152 mm laterally from the centerline of the branchline Installed with a minimum lateral distance of 18 457 mm from any device that produces and releases heat...

Страница 7: ...al data page www vikinggroupinc com Figure 4 Allowed V SD Attic Sprinkler Under Asymmetrical Slopes 8 203 mm Minimum Draft curtain or full wall to deck X X Y Y Refer to Figure 4 V SD Sprinklers are permitted when the slope angles are not equal to each other In this situation install the appropriate sprinklers for each respective slope as shown at right Vertical riser Vertical riser Vertical sprig ...

Страница 8: ...rinkler Larger or closer obstructions require an additional sprinkler on the opposite side of the obstruction This criteria only limits the obstructions that run across the trusses or rafters not the top chord of the trusses or the depth of the rafter Refer to Figures 8 and 9 below where the maximum spacing for Attic Upright Sprinklers is 12 ft 3 7m and standard spray sprinklers is 15 ft 4 6m Any ...

Страница 9: ... Refer to Figure 10 below For vertical obstructions the maximum dimension of the obstruction is the width and the horizontal distance is measured horizontally TABLE 2 OBSTRUCTION CRITERIA Dimension X Distance Y Additional Sprinklers Required Beyond Obstruction Maximum Horizontal Dimension of Obstruction Minimum Horizontal Distance to Obstruction All vertical obstructions 6 152 mm YES 1 2 1 13 mm 2...

Страница 10: ...ion Criteria 6 Figure 12 Obstruction Criteria 7 36 914 mm or more Mechanical space 36 914 mm or more Additional sprinklers are not required 36 914 mm or more 4 102 mm TO 6 152 mm 4 102 mm TO 6 152 mm Mechanical space Intermediate level sprinkler 12 304 mm TO 36 914 mm If a V SD Sprinkler is 36 914 mm or greater above the space and 36 914 mm or greater clearance above the space is present additiona...

Страница 11: ...8 3 m roof span Figure 13 V SD Sprinklers Figure 14 V SD Sprinklers and Attic Upright or Standard Spray Sprinklers at the Ridge Wet Systems Calculate the most demanding 5 V SD sprinklers Dry Systems Calculate the most demanding 9 V SD sprinklers Wet Systems Calculate the most demanding 5 sprinklers of one type Use the most demanding calculation Dry Systems Calculate the most demanding 9 SD Sprinkl...

Страница 12: ...this technical data page www vikinggroupinc com Figure 15 V SD Sprinklers and Attic Upright or Standard Spray Sprinklers Separated by Compartmentalization Calculate the Model V SD demand as described in Figures 13 and 14 then calculate the Standard Spray Sprinklers per NFPA 13 use the most demanding calculation Dormer on top of roof or sheathing Wall RIDGE RIDGE 60 18 3 m roof span 60 18 3 m roof ...

Страница 13: ...sprinkler used DO NOT install sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Tak...

Страница 14: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to re...

Страница 15: ...hese sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkler...

Страница 16: ...r installation to protect the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of th...

Страница 17: ...ler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may affect the co...

Страница 18: ...tile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents cond...

Страница 19: ...er To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkler ...

Страница 20: ...moving the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the piping 2b ...

Страница 21: ...show the highest readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent ...

Страница 22: ...ended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and occupan...

Страница 23: ... TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking di...

Страница 24: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: