MODEL V-SD
SPECIFIC APPLICATION
ATTIC SPRINKLER
TECHNICAL DATA
Page 11 of 12
Form No. F_043015 20.07.28 Rev 20.2
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
60’
(18,3 m) roof span
60’
(18,3 m) roof span
Figure 13:
V-SD Sprinklers
Figure 14:
V-SD Sprinklers and Attic Upright or Standard Spray Sprinklers at the Ridge
Wet Systems:
Calculate the most
demanding 5 V-SD sprinklers.
Dry Systems:
Calculate the most
demanding 9 V-SD sprinklers.
Wet Systems:
Calculate the most
demanding 5 sprinklers of one
type. Use the most demanding
calculation.
Dry Systems:
Calculate the most
demanding 9 SD Sprinklers, and
then calculate the most demanding
7 Attic Upright or Standard Spray
sprinklers. Use the most demanding
calculation.
RIDGE
RIDGE
Wall or draft
curtain at ridge.
NOTE: Dry system shown.
NOTE: Wet system shown.