background image

Service Procedures

©2012 Viking Preferred Service

37

ALARMS

There are five alarms that signify faulty conditions, 

they will each be covered in detail.

1. High Temp Alarm

Freezer High Temp alarm

When the freezer temperature reaches the high temp 

level (15

o

 F) ,set in the EEPROM at factory, for a 

predetermined time (3 hours), also set in EEPROM, 

the "HIGH TEMP" indicator will come on and the 

"FREEZER" indicator will flash. You will also get 

a continuous audible alarm, consisting of a beep 

pattern (ON - 0.5 sec, OFF 2 sec's).
If the condition(s) change and the units temperature(s) 

are brought back within limits as described above, 

the audible alarm will turn off. The "HIGH TEMP" 

and  the appropriate zone (Refrigerator or Freezer) 

indicator will continue to operate as described above.

To  cancel  the  audible  alarm  when  condition  first 

occurs, press and release "ALARM OFF", this will 

result in shutting off the audible alarm only. To clear 

the "HIGH TEMP" and flashing zone light (FREEZER 

), the temperature must be brought down below the 

limit temperature as described in the appropriate 

zone above. Then pressing and releasing "ALARM 

OFF" once will clear the "HIGH TEMP" off the screen 

and the zone indicator will stop flashing.

2. Open Thermistor Alarm

The controller will sense an open thermistor condition 

within 15 seconds of power on.

Open Freezer Thermistor Alarm

When the control senses that the units' thermistor 

is open, "oPn" is displayed on the control along 

with the zone, "FREEZER". If the control was in 

the Refrigerator zone when the condition occurred, 

it automatically switches over to the faulty zone 

("FREEZER"). You also receive an audible alarm 

consisting of five beeps that occurs only one time. 

The visual alarms as described above will continue 

until the condition is corrected.

The unit will continue to execute temperature control 

and defrost operations as required until the condition 

is corrected. The control does this through software 

programming, acting as if the cut-out temperature 

is never reached in the faulty zone, temperature 

control in the other zone is unaffected.

The visual alarms will reset by themselves within 

15 seconds of the open thermistor condition being 

corrected and temperature control reverts back to 

normal operation.

Содержание Quiet Cool VCFB5301

Страница 1: ...s to be used by qualified appliance technicians only Viking does not assume any responsibility for property damage or personal injury for improper service procedures done by an unqualified person This...

Страница 2: ...9 Program Mode A 29 Display Frz Temperature 29 Defrost mode selection 29 Conventional defrost time adjustment CRTD 29 Compressor low speed frequency 30 Adjust Cut In Hysteresis 30 Adjust Cut Out Hyste...

Страница 3: ...ill be preceded by the safety alert symbol and the word DANGER WARNING or CAUTION These words mean IMMEDIATE HAZARDS WHICH WILL RESULT IN SEVERE PERSONAL INJURY OR DEATH Hazards or unsafe practices wh...

Страница 4: ...rovided This appliance is equipped with a power supply cord having a 3 prong grounding plug To minimize possible shock hazard the cord must be plugged into a mating 3 prong grounding type wall recepta...

Страница 5: ...36 Wide Refresh Right Hinge Stainless Model Numbers Serial Numbers 02 15 12 R1000264 Month Day Year of Manufacture Serial Number General Information 2012 Viking Preferred Service 5 The serial number...

Страница 6: ...ty seconds the digital display will change to numbers indicating temperature in the freezer compartment along with the word FREEZER and degrees Fahrenheit Electronic Temperature Settings Settings and...

Страница 7: ...FRZ extinguishing from display Max Frz is enabled by pressing and releasing the ACTIVATE CONTROLS pad and then Pressing MAX FRZ When FAST COOL is selected by pressing the pad FAST COOL is illuminated...

Страница 8: ...imultaneously Continue holding until three beeps are heard The display will revert to normal operation To enter Forced defrost first press and release ACTIVATE CONTROLS then press and hold HIGHER pad...

Страница 9: ...h will remain illuminated whether the door s are open or closed it will not change state Sabbath mode is used to control the refrigerator without interior lights LED display changes and enunciators Al...

Страница 10: ...d FAST COOL will light up enabling the fast cool function which changes the freezer set point to max frz and the ref set point to max ref for a fac tory default of 2 hours Press FAST COOL pad A second...

Страница 11: ...ned by resistance levels of freezer or refrigerator thermistors Freezer Thermistor NTC As temperature decreases resistance increases As temperature increases resistance decreases Note Open thermistor...

Страница 12: ...here grille was removed with ratchet to get to hinge bolts 2 Loosen the four hinge bolts Adjust door 3 Reverse procedure for reinstallation Door Hinge Adjustment Removal of the upper grille assembly a...

Страница 13: ...mage Height Adjustment Removal of the kickplate allows access to rollers and stabilizing legs for height adjustment 1 Remove lower kickplate screws using a Phillips screwdriver 2 Remove upper kickplat...

Страница 14: ...es are connected before certifying unit as repaired and or operational WARNING ACTIVATE CONTROLS LOWER HIGHER FRZ TEMP FAST COOL MAX FRZ ALARM OFF DISPLAY OFF FREEZER SAB SHOW FAST COOL MAX FRZ MAX RE...

Страница 15: ...ol boards 1 To access the control panel remove the upper air grill assembly see Upper Grill Removal section remove 2 screws securing the control panel Control Panel Screws 2 Pull control panel from se...

Страница 16: ...Reverse procedure to reinstall Overlay Switch The unit uses an overlay switch to communicate user input to the control boards The overlay connects to the control board via a ribbon cable 1 To replace...

Страница 17: ...onents 1 To access the high voltage board remove the upper air grill assembly and control panel see Air Grill and Control Panel Removal sections Page 15 2 Compress plastic standoffs securing the high...

Страница 18: ...nnect is now accessible on the right side 2 Verify contacts 4 5 open when the switch is in the 0 position and contacts 4 5 close when in the position 120 VAC should be measured when in the 0 position...

Страница 19: ...he condenser fan is located in the upper machine compartment of the unit 120 VDC is supplied to the fan when the Compressor Condenser Fan relay closes to E4 on the High Voltage Board 1 To access the c...

Страница 20: ...es require power to be connected Discharge capacitor through a resistor before attempting to service Ensure all ground wires are connected before certifying unit as repaired and or operational WARNING...

Страница 21: ...er to let air circulate will help make ice faster After the ice forms the ice maker continues to wait until it reaches 15 F before it starts the harvest cycle This ensures that the ice is solid in all...

Страница 22: ...on T Thermostat connection L L1 hot side of line voltage V Water valve connection Place a 14 gauge jumper wire across test points T and H With hands clear of the ice maker manually close the freezer d...

Страница 23: ...creen in water ll valve or particles of sand can keep valve from seating properly If water valve does not operate properly the following could occur no ice production small or hollow ice cubes ooding...

Страница 24: ...ctrically open this indicates an overheat in the ice maker and the ice maker must be replaced TCO Freezer Thermistor The freezer thermistor is a device that reads freezer temperatures The temperature...

Страница 25: ...to pull air over the evaporator coil and circulate it throughout the unit The 36 unit uses two fan motors to pull air over the evaporator coil and circulate it throughout the unit Freezer Fan Note Th...

Страница 26: ...nd wires are connected before certifying unit as repaired and or operational WARNING Disassembly 26 2012 Viking Preferred Service 5 Remove screws securing freezer fan disconnect wiring and repair repl...

Страница 27: ...rminal E6 on the HV board Using an ohm meter check the brown wire and Neutral and you should read approximately 30 During the defrost cycle line voltage passes through the Defrost Terminator the into...

Страница 28: ...isconnect wiring and repair replace as necessary Water Valve The All Freezer uses a 120 VAC 35 watt valve to supply water to the ice maker 1 To access remove the lower access panel and the valve is ac...

Страница 29: ...es on the freezer thermistor as shown in illustration next column Display Frz Temperature Unit is shipped in Adaptive defrost mode this can be changed to Conventional defrost mode using the following...

Страница 30: ...is value can be set in Mode A as a separate adjustment or can be set automatically in Mode C when selecting model code where several control values are set by eeprom Table 1 Page 39 lists eeprom value...

Страница 31: ...s the display will change to COH To exit the cut in adjustment press and release ACTIVATE CONTROLS one time which will result in PrA being displayed You are now back in Mode A Adjust Cut Out Hysteresi...

Страница 32: ...is now in Program Mode B see illustration below Adjust Freezer Temperature Offset Freezer temperature offset is a predetermined value based upon model of refrigerator This value can be set in Mode B...

Страница 33: ...ious actions Adjust Compressor High Frequency This adjustment is not a field adjustment and should not be performed by technicians This is a factory only adjustment If you see CHF in the display immed...

Страница 34: ...or three seconds until you get three audible beeps Return to your previous actions Exiting Mode B ACTIVATE CONTROLS To exit Mode B and retain any changes made in system up to this point you must press...

Страница 35: ...nd releasing HIGHER and LOWER pads will increase or decrease the set point which should be set at 7o F MAX FRZ LOWER Adjust Freezer Lower Temperature Limit While in Mode C press and hold MAX FRZ and a...

Страница 36: ...up to this point you must press and release ACTIVATE CONTROLS one time the display changes to Prb This signifies that the changes were written to the eeprom and that the system has left Mode C and re...

Страница 37: ...mit temperature as described in the appropriate zone above Then pressing and releasing ALARM OFF oncewillclearthe HIGHTEMP offthescreen and the zone indicator will stop flashing 2 Open Thermistor Alar...

Страница 38: ...Power Loss Alarm If the control experiences a power loss condition and power is restored the Power Loss alarm is displayed This consists of the POWER indicator beingflashedonandoffalongwiththetemperat...

Страница 39: ...ut o F FRZ Cut In o F FRZ Cut out o F REF user default temp REF user default temp BM36 136 65 9 0 6 6 7 8 38 0 SxS42 342 75 6 2 6 6 7 7 38 0 SxS42D 242 75 8 4 6 6 7 7 38 0 SxS48 348 75 4 5 6 6 7 7 38...

Страница 40: ...circuit 2 Compressor winding open circuit Check compressor inverter cable connection Check compressor winding resistances among the 3 terminal hermetic pins If resistances are within specifications an...

Страница 41: ...5 VAC Compressor Con denser Fan E4 E11 115 VAC Defrost Terminator closed E5 E11 0 VAC Defrost Terminator open E5 E11 115 VAC Defrost Heater E6 E11 115 VAC Ref door switch top right light E7 E11 115 VA...

Страница 42: ...26 V p p to 34V p p ref P4 12 See Note 1 below P4 5 DC Fan enable 17 8 vdc 38 vdc ref to chassis grnd DC P4 6 Defrost termination 17 8 vdc 38 vdc ref to chassis grnd See Note 2 below P4 7 Evaporator f...

Страница 43: ...Water supply Verify freezer temperature Verify the arm is in the ON position Replace Ice Maker Verify valve operation Verify water supply Freezer too warm AF Model Control setting Door seal Dirty cond...

Страница 44: ...er at connector socket Determine discontinuity by tracing power No power to water valve Determine discontinuity by tracing power Ice Maker No Water AF Models Action No water to refrigerator Turn on su...

Страница 45: ...roblems Action Raised shut off arm Lower shut off arm to ON position Broken or bent shut off arm Repair arm or replace ice maker Shut off arm stuck or obstructed Remove obstruction Ice maker not level...

Страница 46: ...ocedures require power to be connected Discharge capacitor through a resistor before attempting to service Ensure all ground wires are connected before certifying unit as repaired and or operational W...

Страница 47: ...it unless test procedures require power to be connected Discharge capacitor through a resistor before attempting to service Ensure all ground wires are connected before certifying unit as repaired and...

Страница 48: ...Schematic 48 2012 Viking Preferred Service 30 All Freezer Schematic Upper Section...

Страница 49: ...Schematic 2012 Viking Preferred Service 49 30 All Freezer Schematic Lower Section...

Страница 50: ...Schematic 50 2012 Viking Preferred Service 36 All Freezer Schematic Upper Section...

Страница 51: ...Schematic 2012 Viking Preferred Service 51 36 All Freezer Schematic Lower Section...

Страница 52: ...Wiring Diagrams 52 2012 Viking Preferred Service UPPER SECTION WIRING 30...

Страница 53: ...Wiring Diagrams 2012 Viking Preferred Service 53 LOWER SECTION WIRING 30...

Страница 54: ...Wiring Diagrams 54 2012 Viking Preferred Service UPPER SECTION WIRING 36...

Страница 55: ...Wiring Diagrams 2012 Viking Preferred Service 55 LOWER SECTION WIRING 36...

Отзывы: