background image

 

w

w

w

w

w

w

.

.

w

w

i

i

n

n

e

e

m

m

a

a

t

t

e

e

.

.

c

c

o

o

m

m

 

 

 

Duct Packaged Cooling System 

 

Installation, Operation & Care Manual

 

 

WM-4500DS WM-6500DS WM-8500DS 

 

 

 

 

w

w

w

w

w

w

.

.

v

v

i

i

n

n

o

o

t

t

e

e

m

m

p

p

.

.

c

c

o

o

m

m

 

 

R

R

e

e

a

a

d

d

 

 

a

a

n

n

d

d

 

 

s

s

a

a

v

v

e

e

 

 

t

t

h

h

e

e

s

s

e

e

 

 

i

i

n

n

s

s

t

t

r

r

u

u

c

c

t

t

i

i

o

o

n

n

s

s

 

 

Содержание Wine Mate WM-4500DS

Страница 1: ...c co om m Duct Packaged Cooling System Installation Operation Care Manual WM 4500DS WM 6500DS WM 8500DS w ww ww w v vi in no ot te em mp p c co om m R Re ea ad d a an nd d s sa av ve e t th he es se e i in ns st tr ru uc ct ti io on ns s ...

Страница 2: ... 1 Important Safety Information WARNING Do not use a ground fault interrupter GFI A dedicated 30 AMP circuit is required ...

Страница 3: ...nts Cellar Construction 3 Features Specifications 4 Temperature Humidity 6 Care Guide 10 User Troubleshooting 11 Installer s Instructions 14 Service Instructions 18 Electrical Wirings 24 Customer Support 28 Warranty 29 ...

Страница 4: ...perature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer to insure lights are not left on when the cellar is not occupied The cooling system will not be able to maintain the proper temperature if fresh moisture laden air is constantly being introduced to t...

Страница 5: ...illed air to wine a cellar through ducts and can be located up to 25 ft away for quiet operation It also provides more installation flexibility The systems can be installed both outdoor and indoor Back curved impeller fans are good for total 50 ft long duct Fig 1 DS Duct Packaged Cooling System NOTE Capacity is determined under the cellar the cellar ambient and the condensing unit ambient temperat...

Страница 6: ...imensions are listed as follows Model No Dimension L xW xH Btu h CFM Cellar Size cu ft Refrigerant Electrical Rating Weight lb WM 4500DS 45x34x23 4500 380 1000 R134a 115V 60HZ 8A 140 WM 6500DS 45x34x23 6500 490 1500 R134a 115V 60HZ 14A 170 WM 8500DS 45x34x25 8500 750 2000 R134a 115V 60HZ 17A 220 Fig 2 WM 4500 8500DS Dimensions ...

Страница 7: ...To lock unlock the keypad SET To enter in the programming mode SET To return to the temperature display 2 Lock and unlock the keys To lock the keys press up down keys until POF is displayed to unlock the keys press up down keys until PON is displayed 3 Display During normal operating conditions the display shows the value measured by the air regulation probe In case of active alarm the temperature...

Страница 8: ...Setting Set the temperature at 55 F for the optimum aging of wine On initial start up the time required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize the temperature for each new temperature setting operation 3 How to see temperature set point 1 Press and immediately release the SET key th...

Страница 9: ...llar temperature is ALU higher or ALL lower than the set point Set 2 In order to test the call function set parameters Ald 0 and dAO 0 After testing set Ald 60 and dAO 23 9 How to set low cellar temperature heater The heater turns on at set point SAA minus regulation differential Shy the heater turns off at heater set point SAA NOTES Use a forced air heater to warm up the wine cellar If there is a...

Страница 10: ...delay min 1 ot probe calibration 0 US maximum set point 65 LS minimum set point 50 idF defrost cycle interval time hour 12 MdF defrost cycle endurance time min 30 ALC temperature alarm type rE relative to set point ALU high temperature alarm 10 ALL low temperature alarm 10 AFH alarm recovery differential 5 ALd temperature alarm delay min 60 dAO temperature alarm delay on startup hr 23 SAA heater s...

Страница 11: ...Clean the condenser coil regularly Coil may need to be cleaned at least every 6 months Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty 2 Condensate Removing Remove the excessive condensate if it is accumulated in the wine cellar at high humidity conditions ...

Страница 12: ... temperature is mainly controlled by the average air temperature If the set point is 55 F with the differential 4F the cooling unit turns on at 59 F of air temperature It may be higher than 59 F if it is in anti short cycle or defrost cycle and turns off at 55 F of air temperature The average air temperature is 57 F and then the wine temperature is around 57 0 5 F The air is light enough to change...

Страница 13: ...ust side and leave minimum 1 foot clearance for the ambient air intake side c Check for excessive size d Check for installation location e Clean condenser f Check for fan and air short circulation 8 Condenser fan running but compressor not running a Incorrect or loose wirings b Failed components c Liquid refrigerant in the compressor a Check all wirings and connections b Check start relay start ca...

Страница 14: ... leak No water overflow but water leak a Check for any air leak b Use drain line c Check supply air flow or air TD crossing evaporator d Clean the drip tray e Seal the leak using silicone sealant 15 Condensate inside ducts a Drain line restricted b Continually running not stopping c Too cold supply air a Check for drain b raise temperature setting or increase defrost cycle c Increase air flow or r...

Страница 15: ... shipped ready for use only after a certified refrigeration technician has properly installed the system Proper installation is critical Vinotemp can only warrant the quality of the components The installation of the system must be warranted by the installer Installation of the system must be done in accordance with all state and local building and electrical codes Fig 4 WM 4500 8500DS Cooling Sys...

Страница 16: ...le flooding and shaded from direct sun It shall not be exposed to temperatures higher than 110 F or lower than 50 F Leave minimum 5 feet clearance for hot air exhaust and leave minimum 1 foot clearance for the ambient fresh air intake Supply air flow shall be unobstructed for minimum 12 for a direct blow installation leave 2 clearance for a deflector installation return air shall be unobstructed f...

Страница 17: ... air probe is installed in a return duct the evaporator fans shall be running all the time Meanwhile due to the temperature differential the temperature air probe calibration should be used in order to maintain the proper wine cellar temperature 5 Insulated Duct and Drain Line Installation Secure the ducts with conduits to the cellar exterior walls and make sure they are not curled twisted bent an...

Страница 18: ...turn air and supply air while wine room temperature is maintained 55 F Turn the control knob clockwise to decrease the air flow or counter clockwise to increase the air flow Fig 6 Fan Speed Control CAUTION If the low ambient condition kit is used turn off the compressor before power the condensing unit Only turn on the compressor after the condensing unit has been powered for 12 hours ...

Страница 19: ...sure Control Back Position Normal operation process and manometer port closed Front Position Liquid suction line connection closed Middle Position All ports open for evacuation charge and manometer reading 2 Checking Control Settings 1 Use of the adjustable pressure control Suction pressure setting Cut out 5 psig Cut in 25 psig Differential 20 psig Head pressure setting Cut out 230 psig Cut in 150...

Страница 20: ...Low ambient condition kit if applicable A Use of the condenser fan control Head pressure setting Cut in 170 psig Cut out 120 psig Differential 50 psig It closes on rise of pressure It may need to adjust the setting in the field to avoid fan short cycle Fig 10 Condenser Fan Cycle Control ...

Страница 21: ...ing liquid line connection solenoid valve expansion valve and suction line connection returning to insulated suction line suction valve and then back to condensing unit 2 Use inverted U trap to prevent liquid from flooding back to the compressor 3 Complete pipe brazing check solenoid valve and expansion valve restrictions and test leak The line sizes and refrigerant charges are listed as follows M...

Страница 22: ...es the required CFM 2 The subcooling at the condensing unit shall be around 10 F The charge may be sufficient when there are no more bubbles forming in the liquid indicator 3 Head pressure range 125 150 psig at 70 90 F condensing unit ambient temperature 4 The evaporator s constant pressure expansion valve is set around 30 35 psig 35 40 F at factory This pressure setting gives a dew point to maint...

Страница 23: ...head pressure Low subcooling 5 High suction pressure and high head pressure Low superheat and low subcooling 6 High suction pressure and high head pressure High superheat 7 Low suction pressure and low head pressure High superheat and low subcooling 8 Low suction pressure and low to normal head pressure High superheat and high subcooling 9 Low suction pressure and low head pressure Normal to high ...

Страница 24: ...perheat and high subcooling 10 Air restricted at evaporator evaporator iced 11 Evaporator restricted 12 Expansion valve restricted 13 Both evaporator and condenser restricted liquid and suction lines connected wrong 14 Liquid line restricted before receiver 15 Condenser restricted 7 Condensing Unit Troubleshooting Unit not running 1 Incorrect power supply 2 Incorrect or loose wirings 3 Failed comp...

Страница 25: ...nes are the field wirings Use minimum 14 gauge wires for power lines If equipped with low ambient condition kit use low ambient temperature wiring diagrams A safety switch is always recommended for the condensing unit Fig 15 WM 4500DS Wiring Diagram ...

Страница 26: ... 25 Fig 16 WM 6500DS Electrical Wiring Diagram Fig 17 WM 8500DS Electrical Wiring Diagram ...

Страница 27: ... 26 Fig 18 Low Ambient Temperature WM 4500DS LA Electrical Wiring Diagram Fig 19 Low Ambient Temperature WM 6500DS LA Electrical Wiring Diagram ...

Страница 28: ... 27 Fig 20 Low Ambient Temperature WM 8500DS LA Electrical Wiring Diagram ...

Страница 29: ...28 Customer Support If you need further assistance please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com ...

Страница 30: ...nties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products shall void this warranty Service under Warranty This service is provided to customers within the continental UNITED STATES only VINOTEMP cooling units are warranted to produce the stated number of BT...

Страница 31: ...F USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE While great effort has been made to provide accurate guidelines VINOTEMP cannot warrant its unit...

Отзывы: