- 15 -
Fig. 5 Temperature Controller (4.25”L X 3.75D X 4.25”H)
Parts included:
Packaged Cooling system
Temperature Controller (4.5”LX4.5”WX3.75”D) + Air Probe
Parts not included:
Insulated ducts
CAUTION:
Low ambient condition kit is required if the installation area will be below
50°F.
2. Location
•
Place the unit in a properly ventilated location. If it is not, heat exhausted by
the condensing unit will build up and the cooling system will not operate
properly.
•
Cooling unit shall be elevated to avoid possible flooding and shaded from
direct sun. It shall not be exposed to temperatures higher than 110 °F or
lower than 50 °F.
•
Leave minimum 5 feet clearance for hot air exhaust and leave minimum 1 foot
clearance for the ambient fresh air intake.
•
Supply air flow shall be unobstructed for minimum 12” for a direct blow
installation; leave 2” clearance for a deflector installation; return air shall be
unobstructed for minimum 6”.
•
Overall cold –air supply and room-air return duct length can be up to 50 ft
long; overall hot-air exhaust and ambient-air intake duct length can be up to
50 ft long.
•
Secure the ducts with conduits to the cellar exterior walls and make sure they
are not curled, twisted, bent and clogged.