background image

Fig ure 2: In stal la tion Guide lines

Sprin klers in stalled at peak of a sloped ceil ing with spray di rected  down the slope.

NOTES:

1.

Ac tual in stal la tions may re quire mul ti ple sprin klers. A sin gle sprin kler in stal la tion  has been

       shown for clar ity.
2.

This fig ure de scribes in stal la tions at the peak of sloped ceil ings. In stal la tions in this  configura-
tion are lim ited to a 6/12 (26.6°) pitch.  

3.

Sprin kler  must be in stalled 6" (152 mm) down from peak.

4.

Max i mum height from fin ished floor to sprin kler de flec tor is 18’-0".

5.

Max i mum width of com part ment re gard less of sprin kler area of cov er age is 32’-0".
Max i mum com part ment sizes are based on sprin kler list ings (i.e.:  12’ x 32’, 14’ x 32’, etc.)

6.

Listed ar eas of cov er age are mea sured along ceil ing (for sloped ceil ing in stal la tions, ac tual
floor cov er age will be less than listed area).

7.

A max i mum of two sprin klers are re quired to be hy drau li cally cal cu lated per com part ment.

Sprin kler 142 n

May 27, 1999

TECH NI CAL DATA

Microfast

®

 MODEL M-5

RES I DEN TIAL HOR I ZON TAL

SIDE WALL SPRIN KLER

26.6° max.

Microfast

®

 Model M-5

Res i den tial Hor i zon tal Side wall

in stalled with Micromatic

®

 Model

E-1 Ad just able Re cessed 

Es cutch eon. Top of de flec tor

must be 6" from ceil ing. 

Top of de flec tor  must

 be 6" from ceil ing.

Al ways align top of

de flec tor par al lel to ceil ing.

Max i mum height

from de flec tor to fin ished

floor = 18’-0".

OBSOLETE

Содержание Microfast M-5

Страница 1: ...ta may be found on The Viking Corporation s Web site at http www vikingcorp com The Web site may include a more recent edition of this Technical Data page 6 GUARANTEES For details of warranty refer to Viking s current price schedule or contact The Vi king Corporation directly 7 INSTALLATION WARNING Viking sprinklers are manu factured and tested to meet the rigid re quirements of approving agencies...

Страница 2: ...ct that when the joint seal leaks the sealing compound is washed out of the joint 8 MAINTENANCE NOTICE The owner is responsible for maintaining the fire protection system and devices in proper operating condi tion For minimum maintenance and in spection requirements refer to the Na tional Fire Protection Association s pamphlet that describes care and main tenance of sprinkler systems In addi tion ...

Страница 3: ... kPa A1X A1X Sloped Ceilings with Sprinklers at Side Spraying Across the Slope Maximum Area of Coverage6 7 Width x Length Minimum Water Supply Requirements Listings4 Single Sprinkler Two or More Sprinklers UL5 C UL8 12 x 12 3 7 m x 3 7 m 21 0 gpm 14 6 psi 79 5 L min 101 0 kPa 15 0 gpm 7 4 psi 56 8 L min 51 0 kPa A1X A1X 16 x 16 4 9 m x 4 9 m 24 0 gpm 19 0 psi 90 9 L min 131 0 kPa 21 0 gpm 14 6 psi...

Страница 4: ... Two Sprinklers Single Wall 32 Width x 16 Throw Calculate two sprinklers Two Sprinklers Each Opposite Walls 32 Width x 32 Throw Calculate two sprinklers Three Sprinklers Single Wall 48 Width x 16 Throw Calculate three sprinklers Three Sprinklers Each Opposite Walls 48 Width x 32 Throw Calculate three sprinklers 5 Maximum allowable number of sprinklers per compartment is six 6 Sprinklers may be ins...

Страница 5: ...f coverage is 32 0 Maximum compartment sizes are based on sprinkler listings i e 12 x 32 14 x 32 etc 6 Listed areas of coverage are measured along ceiling for sloped ceiling installations actual floor coverage will be less than listed area 7 A maximum of two sprinklers are required to be hydraulically calculated per compartment Sprinkler 142 n May 27 1999 TECHNICAL DATA Microfast MODEL M 5 RESIDEN...

Отзывы: