Sprin kler 142 L

May 27, 1999

TECH NI CAL DATA

Microfast

®

 MODEL M-5

RES I DEN TIAL HOR I ZON TAL

SIDE WALL SPRIN KLER

Sprin kler

Tem per a ture

Clas si fi ca tion

Nom i nal Sprin kler

Tem per a ture Rat ing

(Fusing Point)

Ceil ing Tem per a ture at Sprin kler

Max i mum Am bi ent

Tem per a ture Al lowed

1

Max i mum Rec om mended

Am bi ent Tem per a ture

2

Bulb Color

Ordinary

155 °F (68 °C)

135 °F (46 °C)

100 °F (38 °C)

Red

Intermediate

175 °F (79 °C)

155 °F (68 °C)

150 °F (65 °C)

Yellow

Sprin kler Fin ishes:  Brass, Bright Brass, Chrome-Enloy

®

 (pat ents pend ing), White (paint), and Na vajo White (paint)

1

 Based on Na tional Fire Pre ven tion and Con trol Ad min is tra tion, Con tract No. 7-34860.

2

 Based on NFPA-13. Other lim its may ap ply de pend ing on fire load ing, sprin kler lo ca tion, and other re quire ments of the Au thor ity Hav ing 

Ju ris dic tion. Re fer to spe cific in stal la tion stan dards. 

De flec tor Style

NPT Thread Size

Nom i nal Or i fice

Nom i nal K-Factor

Over all Length

Base Part

Num ber

3

Inch

mm

Inch

mm

US

met ric

9

Inch

mm

Hor i zon tal Sidewall

½

15

½

15

5.5

7,9

2.75

69,9

09533

Ap proval Chart

Microfast

®

 Model M-5

Res i den tial Hor i zon tal Side wall Sprin kler

(Re fer to Fig ures 1 and 2 on pages 142 m-n.)

Smooth, Flat, Hor i zon tal Ceil ings, or Sloped Ceil ings with Sprin klers at Peak Spraying Down the Slope

Max i mum Areas

of Cov er age

6,7

Width x Length

Min i mum Wa ter Sup ply Re quire ments

List ings

4

Sin gle Sprin kler

Two or More Sprin klers

UL

5

C-UL

8

12' x 12'

(3,7 m x 3,7 m)

21.0 gpm @ 14.6 psi

(79,5 L/min @ 101,0 kPa

15.0 gpm @ 7.4 psi

(56,8 L/min @ 51,0 kPa

A1X

A1X

14' x 14'

(4,3 m x 4,3 m)

22.0 gpm @ 16.0 psi

(83,3 L/min @ 110,0 kPa

17.0 gpm @ 9.6 psi

(63,4 L/min @ 66,0 kPa

A1X

A1X

16' x 16'

(4,9 m x 4,9 m)

24.0 gpm @ 19.0 psi

(90,9 L/min @ 131,0 kPa

21.0 gpm @ 14.6 psi

(79,5 L/min @ 101,0 kPa

A1X

A1X

16' x 18'

(4,9 m x 5,5 m)

27.0 gpm @ 24.1 psi

(102,2 L/min @ 166,0 kPa

22.0 gpm @ 16.0 psi

(83,3 L/min @ 110,0 kPa

A1X

A1X

16' x 20'

(4,9 m x 6,1 m)

32.0 gpm @ 33.9 psi

(121,1 L/min @ 234,0 kPa

30.0 gpm @ 29.8 psi

(113,6 L/min @ 206,0 kPa

A1X

A1X

Sloped Ceil ings with Sprin klers at Side Spraying Across the Slope

Max i mum Area

of Cov er age

6,7

Width x Length

Min i mum Wa ter Sup ply Re quire ments

List ings

4

Sin gle Sprin kler

Two or More Sprin klers

UL

5

C-UL

8

12' x 12'

(3,7 m x 3,7 m)

21.0 gpm @ 14.6 psi

(79,5 L/min @ 101,0 kPa

15.0 gpm @ 7.4 psi

(56,8 L/min @ 51,0 kPa

A1X

A1X

16' x 16'

(4,9 m x 4,9 m)

24.0 gpm @ 19.0 psi

(90,9 L/min @131,0 kPa

21.0 gpm @ 14.6 psi

(79,5 L/min @ 101,0 kPa

A1X

A1X

Ap proved

Tem per a tures

A - 155 °F (68 °C) and 

175 °F (79 °C)

Ap proved Fin ishes

1 - Brass, Bright Brass, Chrome- 

Enloy

®

, White (paint), and

Na vajo White (paint)

Ap proved Es cutch eons

X - Stan dard sur face-mounted es cutch eons or Microfast

®

 Model F-1 

Ad just able Es cutch eon

10

,  or re cessed with the Micromatic

® 

Model 

E-1 Ad just able Re cessed Es cutch eon 

Foot notes

3

 Base part num ber shown. For com plete part num ber, see price list.

4

 This chart shows the list ings and ap prov als avail able at the time of print ing. Other ap prov als are in pro cess. Check with man u fac turer for 

any ad di tional ap prov als.

5

 List ing is for res i den tial oc cu pan cies with smooth, flat, hor i zon tal ceil ings and ceil ings with slopes up to a 6/12 (26.6°) pitch. See Foot notes 

6, 7, and 8.

6

 Listed area of cov er age mea sured along ceil ing. Con sult Fig ures 1 and 2 on pages 142 m-n, and "Res i den tial In stal la tion Guide" para-

graphs that per tain to sprin klers with list ings for both smooth, flat, hor i zon tal ceil ings 

and sloped ceil ings for in stal la tion de tails.

7

 For ar eas of cov er age smaller than shown, use the "Min i mum Wa ter Sup ply Re quire ment" for  the next larger area listed. Flows and pres-

sures listed are per sprin kler.

8

 Listed by Un der writers Lab o ra tories Inc. for use in Can ada.

9

 Met ric K-factor shown is for use when pres sure is mea sured in kPa. When pres sure is mea sured  in BAR, mul ti ply the met ric K-factor

shown by 10.0.

 

10

 The Microfast

®

 Model F-1 Ad just able Es cutch eon is con sid ered a sur face-mounted es cutch eon be cause it does not al low the fus ible ele-

ment of the sprin kler to be re cessed be hind the face of the wall or ceil ing.

Ta ble 

1

                

      KEY

                  

 Tem per a ture

                   Fin ish

    A1X

      Es cutch eon (if ap pli ca ble)

OBSOLETE

Содержание Microfast M-5

Страница 1: ...ta may be found on The Viking Corporation s Web site at http www vikingcorp com The Web site may include a more recent edition of this Technical Data page 6 GUARANTEES For details of warranty refer to Viking s current price schedule or contact The Vi king Corporation directly 7 INSTALLATION WARNING Viking sprinklers are manu factured and tested to meet the rigid re quirements of approving agencies...

Страница 2: ...ct that when the joint seal leaks the sealing compound is washed out of the joint 8 MAINTENANCE NOTICE The owner is responsible for maintaining the fire protection system and devices in proper operating condi tion For minimum maintenance and in spection requirements refer to the Na tional Fire Protection Association s pamphlet that describes care and main tenance of sprinkler systems In addi tion ...

Страница 3: ... kPa A1X A1X Sloped Ceilings with Sprinklers at Side Spraying Across the Slope Maximum Area of Coverage6 7 Width x Length Minimum Water Supply Requirements Listings4 Single Sprinkler Two or More Sprinklers UL5 C UL8 12 x 12 3 7 m x 3 7 m 21 0 gpm 14 6 psi 79 5 L min 101 0 kPa 15 0 gpm 7 4 psi 56 8 L min 51 0 kPa A1X A1X 16 x 16 4 9 m x 4 9 m 24 0 gpm 19 0 psi 90 9 L min 131 0 kPa 21 0 gpm 14 6 psi...

Страница 4: ... Two Sprinklers Single Wall 32 Width x 16 Throw Calculate two sprinklers Two Sprinklers Each Opposite Walls 32 Width x 32 Throw Calculate two sprinklers Three Sprinklers Single Wall 48 Width x 16 Throw Calculate three sprinklers Three Sprinklers Each Opposite Walls 48 Width x 32 Throw Calculate three sprinklers 5 Maximum allowable number of sprinklers per compartment is six 6 Sprinklers may be ins...

Страница 5: ...f coverage is 32 0 Maximum compartment sizes are based on sprinkler listings i e 12 x 32 14 x 32 etc 6 Listed areas of coverage are measured along ceiling for sloped ceiling installations actual floor coverage will be less than listed area 7 A maximum of two sprinklers are required to be hydraulically calculated per compartment Sprinkler 142 n May 27 1999 TECHNICAL DATA Microfast MODEL M 5 RESIDEN...

Отзывы: