Fig ure 1: In stal la tion Guide lines

Sprin klers in stalled on the side of a sloped ceil ing with throw di rected  across  the slope.

NOTES:

1.

A sin gle sprin kler in stal la tion has been shown for clar ity. Ac tual in stal la tions may re 

quire 

       mul ti ple sprin klers. For mul ti ple sprin kler in stal la tions, sprin klers may be in stalled on op po site

walls, throw ing to ward each other.

2.

This fig ure shows an in stal la tion of a sprin kler on the side of a sloped ceil ing. In stal la tions in
this con fig u ra tion are lim ited to a 6/12 (26.6 °) max i mum ceil ing slope.

3.

For “ca the dral” ceil ing ap pli ca tions, in stall sprin klers in a sym met ri cal mir ror-image  of Fig ure 1.

4.

Max i mum al low able com part ment sizes are as fol lows: (Area mea sured along slope)
One Sprin kler, Sin gle Wall:

16’ Width x 16’ Throw (Cal cu late one sprin kler)

One Sprin kler Each, Op po site Walls:

16’ Width x 32’ Throw (Cal cu late two sprin klers)

Two Sprin klers, Sin gle Wall:

32’ Width x 16’ Throw (Cal cu late two sprin klers)

Two Sprin klers Each, Op po site Walls:

32’ Width x 32’ Throw (Cal cu late two sprin klers)

Three Sprin klers, Sin gle Wall:

48’ Width x 16’ Throw (Cal cu late three sprin klers)

Three Sprin klers Each, Op po site Walls: 48’ Width x 32’ Throw (Cal cu late three sprin klers)

5.

Max i mum al low able num ber of sprin klers  per com part ment is six.

6.

Sprin klers may be in stalled in any com bi na tion of ac cept able in stal la tion lo ca tions, as long as
each sprin kler is lo cated in ac cor dance with its in di vid ual list ings.

May 27, 1999

Sprin kler 142 m

TECH NI CAL DATA

Microfast

®

 MODEL M-5

RES I DEN TIAL HOR I ZON TAL

SIDE WALL SPRIN KLER

Max i mum ceil ing

slope = 6/12

(26.6°). See Note 

2 be low.

Max i mum Throw

16’-0"

De flec tor  must

be 6" (152 mm)
min i mum to 12"

(305 mm) max i -

mum from the

ceil ing. Keep top

of de flec tor

par al lel to the

ceil ing.

Listed ar eas of cov -

er age cor re spond

to ceil ing slope.

(For sloped ceil ing

in stal la tions, ac tual

floor cov er age will
be less than listed

area.)

Max i mum 8’-0"

(2,4 m) high

open ing

al lowed in
 perimeter

walls.

OBSOLETE

Содержание Microfast M-5

Страница 1: ...ta may be found on The Viking Corporation s Web site at http www vikingcorp com The Web site may include a more recent edition of this Technical Data page 6 GUARANTEES For details of warranty refer to Viking s current price schedule or contact The Vi king Corporation directly 7 INSTALLATION WARNING Viking sprinklers are manu factured and tested to meet the rigid re quirements of approving agencies...

Страница 2: ...ct that when the joint seal leaks the sealing compound is washed out of the joint 8 MAINTENANCE NOTICE The owner is responsible for maintaining the fire protection system and devices in proper operating condi tion For minimum maintenance and in spection requirements refer to the Na tional Fire Protection Association s pamphlet that describes care and main tenance of sprinkler systems In addi tion ...

Страница 3: ... kPa A1X A1X Sloped Ceilings with Sprinklers at Side Spraying Across the Slope Maximum Area of Coverage6 7 Width x Length Minimum Water Supply Requirements Listings4 Single Sprinkler Two or More Sprinklers UL5 C UL8 12 x 12 3 7 m x 3 7 m 21 0 gpm 14 6 psi 79 5 L min 101 0 kPa 15 0 gpm 7 4 psi 56 8 L min 51 0 kPa A1X A1X 16 x 16 4 9 m x 4 9 m 24 0 gpm 19 0 psi 90 9 L min 131 0 kPa 21 0 gpm 14 6 psi...

Страница 4: ... Two Sprinklers Single Wall 32 Width x 16 Throw Calculate two sprinklers Two Sprinklers Each Opposite Walls 32 Width x 32 Throw Calculate two sprinklers Three Sprinklers Single Wall 48 Width x 16 Throw Calculate three sprinklers Three Sprinklers Each Opposite Walls 48 Width x 32 Throw Calculate three sprinklers 5 Maximum allowable number of sprinklers per compartment is six 6 Sprinklers may be ins...

Страница 5: ...f coverage is 32 0 Maximum compartment sizes are based on sprinkler listings i e 12 x 32 14 x 32 etc 6 Listed areas of coverage are measured along ceiling for sloped ceiling installations actual floor coverage will be less than listed area 7 A maximum of two sprinklers are required to be hydraulically calculated per compartment Sprinkler 142 n May 27 1999 TECHNICAL DATA Microfast MODEL M 5 RESIDEN...

Отзывы: